TACOFLOW3 MAX / MAX PRO
MKTG-TRA-MAN-E9150400-10/2019-ENG
Instructions for installation and use
37
12.4.1 TECHNICAL MENU (MAX PRO MOD.)
Proceed as follows to access the technical menu:
1)
Press the
UP
and
DOWN
buttons simultaneously for
5 s
and
“tECH”
will appear on the display
2)
Press the
SET
buttons and select the parameter to be displayed by pressing the
UP
or
buttons
3)
Press the
SET
buttons to select the desired parameter
INFORMATION
AFTER
10 S
OF INACTIVITY, THE CIRCULATOR EXITS THE TECHNICAL MENU AND RESUMES NORMAL OPERATION.
FIG. 14
(Technical menu)
Parameter
Meaning
T 0
Display Firmware Version
T 1
Inverter Firmware Version
T 2
Unit of measurement shown on the display:
• SI = Système international (European)
• IU = Imperial units (Anglo-Saxon)
T 3
Maximum head of the pump / model (60-80 or 100)
T 4
0-10 V analogue input voltage
T 5
PWM input duty cycle
T 6
Mains voltage
T 7
Inverter internal voltage
T 8
Pump operating hours (in thousands, 0.010 = 10 hours, 101.0 = 101000 hours)
T 9
Switch-on counter
T 10
Standby counter
T 11
Rotor blocks counter
T 12
Step loss counter
T 13
Undervoltage counter
T 14
Overvoltage counter
T 15
Failed internal board communication counter
TAB. 23
(Technical menu parameters)