5.8
SUITABLE LIQUIDS FOR PUMPING
Types of liquids
Features
Liquids
Clean, non-aggressive and non-explosive, with no solid particles, fibres or mineral
oils
Liquids in the heating systems
Water according to VDI 2035
Mixture of water and glycol with percentages that are not higher than 30%
TAB. 8
(Suitable liquids for pumping)
WARNING
IT IS FORBIDDEN TO USE LIQUIDS OTHER THAN THOSE INTENDED BY THE MANUFACTURER.
WARNING
IT IS MANDATORY FOR THE AUTHORISED OPERATORS TO READ AND BE CERTAIN TO HAVE UNDERSTOOD ALL PARTS OF ANY
SAFETY DATA SHEETS PROVIDED BY THE PRODUCERS OF THE LIQUIDS USED.
5.9
OPERATING TEMPERATURE
Ambient temperature (°C)
0
10
20
30
35
40
Liquid temperature
MIN to MAX (°C)
-10 to 110
10 to 110
20 to 110
30 to 110
35 to 90
40 to 70
TAB. 9