A.3
Parameter settings and display values for service personnel
The values without a value range correspond to the
display values of sensors, control signals or software
statuses. Values with value ranges are parameter
settings.
The values marked with * only appear when the log-
in as service personnel has been performed using
HMI text
Description
Value range
Setting Save
Saves changes to the settings to ensure they are not lost in the event of
a power failure. The parameter automatically resets to “Passive”.
Active
Passive
Operating mode
Setting the operating mode:
Automatic: Normal control
Manual: The unit is operated using the manual settings (see section on
Manual control).
Legio: The setpoint of the domestic hot water is raised to a higher tem-
perature for a specific period for thermal disinfection (see DHW parame-
ters section).
Test: Valves and pumps are activated briefly to test that activation is cor-
rect.
(All modes are automatically switched over to Automatic after a specific
time.)
Auto
Man
Legio
Test
HMI text
Description
Value range
Setpoint DHW
Setpoint for the domestic hot water preparation
25 – 90
°C
Setpoint HTG
supply
Setpoint for the supply temperature of the heating water
15 – 70
°C
Setting Save
Saves changes to the settings to ensure they are not lost in the event of
a power failure. The parameter automatically resets to “Passive”.
Active
Passive
Main overview
Main overview
►
Quick setup
Main overview
►
Quick setup
►
Date/
time input
H3000 E
Appendix for service personnel
01/2023
Item no. 215251
EA no. EA-1291
Operating instructions
53