7

Input I2

has the functions the same as 

I1

.

SAVE

will write settings in permanent non-volitile memory.

,., NetWor3 Settings:

This  page  provides  a  way  to  change  network  configurations.

Buttons operate in a similar manner as on previous pages.

,.k Log:

This page will display possible errors.

,.k.1 Errors:

By clicking on either 

current error

or 

last error

you are brought to

a page detailing the errors, the probable cause and possible solu-

tion. Also, errors can be viewed without having to connect to the

pump through an Ethernet cable or the internet. A control light on

the front panel provides fast overview of pump operation. The blue

color signifies correct operation while the sequence of a blinking

red indicates an error.

,.9 yelp:

This page will redirect you to www.taco-hvac.com. Possible soft-

ware upgrades and manuals will be available.

k. DIAbNOSTIC AND OPERATINb LIbyTS:

A control light on the front panel provides fast overview of pump

operation. The blue color signifies correct operation while red indi-

cates an error.

k.1 Red Light:

A red light blinks to indicate an error code. The sequence of the

blinks is interrupted by a pause. The number of blinks between

pauses is the error code.

k.- Overload Effects and Reset:

Overload is indicated by the blue power light changing to red. The

red  overload  light  flashes  in  accordance  to  the  failure.  The  last

overload is saved in memory.

9. SEARCy FOR A  LOST PUMP<:

If you have forgotten the IP address or NetBIOS name or if you

accidently set it to an incorrect value, a pump can still be found

with  network  analyzers.  Freeware  tools  like  “WireShark”  or

“EtherDetect” can help you to trace the pump as it periodically tries

to contact its twin. This is true even in the case of a single pump.

You can trace out the device that sends out requests and contact

it directly.

qLUE LIbyT

Blinking

Pump is in standby mode and not pumping water.

Solid On

Pump is operating as set

RED LIbyT

ERROR

CODE

DESCRIPTION

1

Motor is operating under very low load conditions. This indi-

cates that the pump is probably running dry. System may

need filling or air purged.

2

Pump cannot start. Rotor might be blocked. Remove head

of pump and check if the impeller turns freely.

3

Motor has overheated. Too hot of a medium, over estimat-

ed head of pump requirements or nonfunctioning motor.

4

Frequency converter error.

5

Stator or rotor faulty.

Overview

Pump

Network

Log

Help

ERROR CODE

DESCRIPTION

PROBABLE CAUSE AND SOLUTION

(*)1

Low load detected

The pump might be running dry. Make 

sure the system is filled with fluid to 

prevent bearing damage.

(**)2

Overload trip, protective shutdown

Overcurrent, line surge or locked rotor 

caused the pump to restart. If the issue 

persists, check if the rotor is spinning freely

(***)3

Motor too hot

Motor has exceeded allowed temperature 

and is now stopped to cool down. 

Extremely hot medium or hardware failure 

might have caused that.

(****)4

Frequency converter error

Converter has detected an internal fault. 

The pump might still be operating, but 

needs repair.

(*****)5

5 Motor/stator faulty

Motor does not behave as expected. 

Internal winding or wiring error might have 

caused that.

Content ©copyright 2011 Taco Inc., 1160 Cranston, RI USA 02920 • www.taco-hvac.com

Overview

Pump

Network

Log

Help

VR 30

IP address

is a pump network address. The pump is seen as http server on this address.

Subnet mask

sets subnet address range that is on the same subnet and can be reached 

directly. The rest of communication goes over the gateway.

Default gateway

provides connection route to larger networks. This is usually a router 

address.

NetBIOS name

is a local network name server. Instead of '192.168.0.245' you can for 

example use 'http://VIRIDIAN'.

Twin mode IP

will connect two pumps for alternating operation. When two pumps are 

configured for twin mode, they will switch about once per day. Setting this 

field to unexistent IP will disable this option. Set it so the first pump 

references the second and vice versa. 

(!)Use 'Save' carefully. Incorrect settings might render pump unreachable. If 

you change the IP address, you will need to manually enter it into browser 

window.

Network connection settings:

Pump IP address:

Subnet mask:

Default gateway:

NetBIOS name:

Twin mode with IP:

Content ©copyright 2011 Taco Inc., 1160 Cranston, RI USA 02920 • www.taco-hvac.com

192.168.0.245

255.255.0.0

192.168.0.1

VIRIDIAN

0.0.0.1

Save

Overview

Pump

Network

Log

Help

Log:

For operation statistics, to go 

Overview

 page.

Current error

: 0(See error description) 

Last error

: 1(See error description) 

Startup diagnosis: 0000000000000000

Content ©copyright 2011 Taco Inc., 1160 Cranston, RI USA 02920 • www.taco-hvac.com

O ERLOAD EFFECTS AND RESET

DESCRIPTION

O ERLOAD

EFFECT

RESET

REàUIREMENT

Low Load

(dry run)

Pump runs at

reduced speed after

approx 60 seconds.

Runs at normal speed once

motor load is increased (water in

volute).

Overload

(locked rotor)

Pump shuts off.

Manual (turn main power supply

off/on). Clear obstructions if nec-

essary.

Motor Overheat

Pump runs at

reduced power until

motor cools down.

Cool motor.

VFD Failure

Pump shuts off.

Manual (turn main power off/on).

If unable to reset, replace pump

(powerhead).

Motor/Stator

Failure

Pump shuts off.

Manual (turn main power off/on).

If unable to reset, replace pump

(powerhead).

Содержание Viridian 15

Страница 1: ...t O rings use part number 975 001RP See detailed Motor Rotation Procedure 4 1 below Instruction Sheet Viridian 15 30 1 and 2 Models 302 364 SUPERSEDES October 24 2013 EFFECTIVE November 2 2015 A Taco resource saving product CAUTION Use supplG Wires suitaVle for x6XC ATTENTION EmploGer des fils d alimentation ade2auts pour x6XC HARNINb Do not use in sWimming pool or spa areas Pump has not Veen inve...

Страница 2: ...ck up the motor with the terminals properly orientated and carefully start to slide the motor over the rotor can The resis tance of the sliding will keep the rotor and rotor can assembly in place and the screwdriver can be moved Note Do not alloW the motor to droop or the OYring might get out of position 10 Line up the bolt holes reinstall the bolts and tighten in a cross pattern 11 Carefully open...

Страница 3: ...neficial when the Viridian is installed in a system where there is a much lower resis tance friction loss in the main distribution loop compared to the resistance in the transfer part of the system i e baseboard radia tion radiant floors terminal units For example this characteristic of generally lower head loss can be found in converted gravity sys tems systems operating with large temperature sp...

Страница 4: ... CLOSED CLOSED CLOSED OFF RUN OPEN MAX NF 0 OPEN OPEN MAX RUN CLOSED OPEN CLOSED MAX RUN CLOSED CLOSED OPEN RUN RUN CLOSED CLOSED CLOSED RUN RUN CLOSED NF 0 MAX OPEN OPEN RUN RUN CLOSED OPEN CLOSED MAX RUN CLOSED CLOSED OPEN RUN RUN CLOSED CLOSED CLOSED MAX RUN CLOSED RUN Default MAX Default OPEN OPEN RUN RUN CLOSED OPEN CLOSED MAX RUN CLOSED CLOSED OPEN OFF RUN OPEN CLOSED CLOSED OFF RUN OPEN MAX...

Страница 5: ... one pump will be connected into network each indi vidual pump should have its IP address and NetBIOS name changed and noted That will prevent network confusion and pro vide naming service in relation to pump function 1 HeV Interface Settings When the Viridian is connected to a network or another computer it can be reached by typing its IP address or NetBIOS name into the internet explorer s addre...

Страница 6: ...tion Active run Error detected error Active I2 i2 Input I1 is either Run Run the pump run Full power max No function 0 Overview Pump Network Log Help VR 30 Limit head adjusts the maximum pump head The pump will try to maintain that head between its ports Hmax proportional to Q will reduce the head at the low flow It will drop for a set percentage at zero flow Limit rpm can provide a head regulatio...

Страница 7: ...e the system is filled with fluid to prevent bearing damage 2 Overload trip protective shutdown Overcurrent line surge or locked rotor caused the pump to restart If the issue persists check if the rotor is spinning freely 3 Motor too hot Motor has exceeded allowed temperature and is now stopped to cool down Extremely hot medium or hardware failure might have caused that 4 Frequency converter error...

Страница 8: ...le device NOR Will it ma3e the iridian accessiVle over the internet 16 1 Hireless Setting This is where it is possible to personalize the name of the wireless network The example below illustrates a network called Viridian Wireless Regardless of the wireless network name once set up the wireless device iPhone iPad PC Mac or Android device is directed to connect to that network Viridian Wireless as...

Страница 9: ...uniquement a l interieur 11 Electrical Data Pump Ratings 1 phase 110 240V 47 63Hz VR15 VR20 1 phase 200 240V 47 63Hz VR25 VR30 Power Consumption HP VR15 0 027 0 680 HP VR20 0 035 1 088 HP VR25 0 054 1 496 HP VR30 0 054 2 175 HP Power Consumption W VR15 20 500 W VR20 26 800 W VR25 46 1100 W VR30 40 1600 W Rated Current 1 phase 115 230V VR15 2 2 A 6 0 A VR20 3 5 A 6 0 A Rated Current 1 phase 230V VR...

Страница 10: ...0 75 100 125 150 175 200 225 250 275 300 325 350 375 400 HEAD FT 0 5 10 15 20 25 30 35 40 45 50 Flow liter min 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 Head m 0 2 4 6 8 10 12 14 Performance 3 4 1 VR15 3 VR25 4 VR30 2 VR20 1 2 ...

Страница 11: ...11 NOTES ...

Страница 12: ...a Taco product or part or for any application restrictions consult the applicable Taco instruction sheets or contact Taco at 401 942 8000 Taco reserves the right to provide replacement products and parts which are substantially similar in design and functionally equivalent to the defec tive product or part Taco reserves the right to make changes in details of design construction or arrangement of ...

Отзывы: