6
,.' Connecting to the Pump:
Go to Internet Explorer, in the address line type http://viridian or
the IP address of the pump.
,.B OvervieW Page:
The overview page allows you to view the current status of the
pump. You may select the intervals (never, every 30 seconds,
every 3 seconds) of which you would like the data refreshed. It dis-
plays pump operation summary information, including:
• Power Consumption • Heatsink Temperature
• Amperage • Operating Hours
• RPM • Number of Restarts
• Estimated Head • Accumulated Power
• Estimated Flow Consumption
• Estimated Efficiency • Digital Inputs
• Motor Status • Relay Status
,.4 Pump Settings:
For more detail or to change any of the pump settings click on the
Pump tab.
Limit head (Hmax)
will set the maximum allowable head.
Hmax proportional to Q
will set the ratio between head
and flow:
Hmax = 0%: Constant pressure is set and should not exhibit
noticeable change until maximum power is reached.
Hmax = X%: Parameter will set the percentage of drop
in head from maximum to closed valve.
Limit rpm to
will limit motor speed.
Limit power to
will set maximum wattage (max power
consumption of the pump).
Limit grid current to
will assign a maximum amp draw.
Limit heatsink temperature to
will set a maximum
temperature at the heatsink (electronics area).
Switch on the relay when
can be set up as:
Standby (operation)
Active (run)
Error detected (error)
Active I2 (i2)
Input I1
is either:
Run
Run the pump (run)
Full power (max)
No function (0)
Overview
Pump
Network
Log
Help
VR 30
Limit head
adjusts the maximum pump head. The pump will try to maintain that head
between its ports.
Hmax proportional to Q
will reduce the head at the low flow. It will drop for a set percentage at zero
flow.
Limit rpm
can provide a head regulation similar to a manual adjustable pump.
Regulation will reduce the pump power until none of the parameters will be
exceeded.
Regulation settings:
Limit head (Hmax) to
feet of head
Hmax proportional to Q
%
Limit rpm to
/min
Limit power to
W
Limit grid current to
A
Limit heatsink temperature to
°F
Switch on the relay when
Input I1 is:
Input I2 is:
23.0
50
3000
1600
8.0
203
error
run
max
Save
™
Overview
Pump
Network
Log
Help
Welcome!
You have reached
VR 30
circulating pump. It is connected to
network with
IP
192.168.0.245 and
MAC
02-1A-6F-EF-FB-BA.
Pump status is available on the right. In order to refresh the view, press
browser's refresh button or choose automatic refresh.
Pump Status:
Refresh the view: never | every 30s | every 3s
Operation:
Power consumption: 251 W (1600 W)
Grid current: 1.09 A (8.0 A)
RPM: 1645/min (3000/min)
Estimated head: 13.1 ft. of head (13.3 ft. of head)
Estimated flow: 30.7 GPM
Estimated efficiency: 30 %
Temperatures:
Motor: OK
Heatsink: 91 °F (203 °F)
Statistics:
Operating hours: 4 h
Number of restarts: 13
Energy consumed: 1 kWh
Control:
Digital inputs: 1 (run), 0 (max)
Relay status: 0 (error)
Twin pump mode: N/A (-4)
™