background image

2 of 8 

Reset Ratio

 

Operation of a hot water heating system can generally be improved by modulating the 
supply water temperature as the outdoor temperature changes. Using this approach, the 
heat lost from the building is matched by the heat input to the building. The PC702-1 Boiler 
Reset Control utilizes a reset ratio to set the relationship between outdoor temperature 
and supply water temperature. The reset ratio determines the amount the supply water 
temperature is raised for every 1

°

 drop in outdoor air temperature, and it is determined 

from the starting point and the system design conditions. In order for the control to 
automatically determine the reset ratio, a starting point and design conditions must be 
established. These two points are set by the following 4 adjustments: 

• Boiler starting temperature 
• Outdoor starting temperature 
• Boiler design supply water temperature 
• Outdoor Design Temperature 

See 

Settings - Step Four

 for a complete description of each setting. 

Reset Ratio Starting Point

 

The first point used to establish the reset ratio calculation is the starting point. It is a combination of an adjustable boiler starting water 
temperature setting and an adjustable outdoor starting temperature setting. 

Design Conditions

 

The second point to establish the reset ratio calculation is the design conditions. This point represents the required water temperature 
during the coldest day of the year. 

Warm Weather Shut Down (WWSD)

 

When the outdoor air temperature is warmer than the Warm Weather Shut Down setting, no additional heat is required in the building; 
therefore, the heating system can be shut down. This setting has no effect on the reset ratio calculation. 

BOILER OPERATION

 

The supply water temperature from the boiler(s) can be controlled by cycling the boiler(s) on and off. Modulation of the operating 
temperature in hot water heating systems not only provides more comfort but also offers significant energy savings. The cooler the 
boiler(s) runs, the more efficient it is due to less heat losses up the flue and reduced boiler jacket losses. 

Differential

 

An on / off boiler must be operated with a differential in order to prevent 
short cycling. When the supply water temperature drops below the 
bottom rail of the differential, the boiler is turned on. The boiler is then 
kept on until the supply water temperature rises above the top rail of 
the differential. If the differential is too wide, there can be large supply 
water temperature swings; however, if the differential is too narrow, the 
boiler short cycles and operates inefficiently. This control can auto-
matically calculate the boiler differential in order to achieve an appro-
priate balance between temperature swings and boiler efficiency. This 
also permits the control to adapt to changing loads and conditions. 

Minimum Boiler Supply

 

Most boilers require a minimum supply water temperature in order to prevent corrosion 
from flue gas condensation. The control should therefore only modulate the boiler supply 
water temperature down to the boiler manufacturer’s minimum recommended operating 
temperature. Some boilers are designed to condense and should be operated at low 
water temperatures as much as possible for maximum efficiency. 

Domestic Hot Water (DHW) Boiler Supply

 

Most indirect DHW tanks require a relatively high supply water temperature in order to 
produce adequate amounts of DHW. The control should therefore override the reset ratio 
when there is a demand for DHW and raise the system supply temperature to a 
temperature that is suitable for DHW generation. 

Sequence of Operation

POWERING UP THE CONTROL

 

After the PC702-1 is powered up, all the LCD segments are turned on for 2 seconds, followed by a software version number. The control 
then displays the outdoor temperature. 

Outdoor air  temperature

50

(10)

30

(-1)

10

(-12)

-10

(-23)

70

(21)

90

(32)

Reset

Ratio

Starting

Point

°

F

(

°

C)

Supply water temperature

110

(43)

70

(21)

90

(32)

210

(99)

170

(77)

150

(65)

130

(54)

190

(88)

Design

Conditions

Supply W

ater 

T

emperature

Time

Differential = 10

°

F (5

°

C)

165

°

F(74

°

C)

B

o

ile

r

o

ff

B

o

ile

r

o

n

155

°

F (68

°

C)

160

°

F (71

°

C)

B

o

ile

r

o

ff

B

o

ile

r

o

n

Outdoor air  temperature

50

(10)

30

(-1)

10

(-12)

-10

(-23)

70

(21)

90

(32)

WWSD

Temperature

°

F

(

°

C)

Supply water temperature

110

(43)

70

(21)

90

(32)

210

(99)

170

(77)

150

(65)

130

(54)

190

(88)

Reset

Ratio

Minimum

Содержание PC702–1

Страница 1: ...portional to the temperature of the supplywaterandthesurfaceareaoftheheatingelement Asmallsurface area such as baseboard radiators requires a higher water temperature than a larger surface area such as radiant floors The heat lost from a building is dependent on the outdoor temperature as well as other factors As the outdoor temperature drops the building heat loss increases InstructionSheet PC702...

Страница 2: ...iler jacket losses Differential An on off boiler must be operated with a differential in order to prevent short cycling When the supply water temperature drops below the bottom rail of the differential the boiler is turned on The boiler is then kept on until the supply water temperature rises above the top rail of the differential If the differential is too wide there can be large supply watertemp...

Страница 3: ...iler setting This pro grammed function has an OFF setting for condensing and electric boilers When operating at the minimum setting the control displays the MIN segment in the LCD when either that boiler supply or boiler target temperature are being viewed ROTATION The PC702 1 has an optional boiler rotation function that is selected using the DIP switch located next to terminal 1 in the wiring ch...

Страница 4: ...the sensor cover off by sliding it upward relative to the sensor base Use one round or pan head screw to attach the base of the sensor to the wall The sensor is wall mounted and the wiring enters through the bottom of the enclosure The hole for the cable entry must face downward in order to prevent water from entering and filling the enclosure The sensor should be mounted on a wall which best repr...

Страница 5: ... be adjusted from 35 to 150 F 2 to 66 C This setting is typically set to the desired building temperature In applications where fan coils are used the BOIL Start may need to be set higher to prevent cold drafts during mild outdoor conditions If the building feels cool during mild outdoor conditions the BOIL Start setting should be increased Outdoor Starting Temperature OUTDR Start The OUTDR Start ...

Страница 6: ...esign __________________________________ WWSD ______________________________________ Differential Example 10 F 6 C Btu hr input 100 000 Btu hr System US GPM x 500 20 US GPM x 500 ADJUST MENU To enter the adjustment mode Press and Hold simultaneously the Item and Buttons The ADJUST element will turn on Start Interstage Delay DHW Demand Boiler Demand BOIL F ADJUST Start Interstage Delay DHW Demand B...

Страница 7: ... not be connected to the control while the test is performed Using the chart below estimate the temperature measured by the sensor The sensor and thermometer readings should be close If the test meter reads a very high resistance there may be a broken wire a poor wiring connection or a defective sensor If the resistance is very low the wiring may be shorted theremaybemoistureinthesensororthesensor...

Страница 8: ...or Design 60 to 32 F 51 to 0 C 10 F 12 C Boiler Minimum Off 80 to 180 F Off 27 to 82 C 140 F 60 C Differential Auto 2 to 42 F Auto 1 to 24 C Auto Interstage Delay 0 30 to 4 00 minutes 2 00 min WWSD 35 to 100 F Off 2 to 38 C Off 70 F 21 C Units F C F Do It Once Do It Right TACO INC 1160 Cranston Street Cranston RI 02920 Telephone 401 942 8000 FAX 401 942 2360 TACO Canada Ltd 6180 Ordan Drive Missis...

Отзывы: