background image

TERMINAL BLOCK CONNECTIONS 
CLAMPING PLATE TERMINAL

FIG. 8

LWCO WIRING DIAGRAM USING 
BURNER CIRCUIT POWER SOURCE

FIG. 6

LWCO WIRING DIAGRAM USING POWER 
SOURCE OTHER THAN BURNER CIRCUIT 

FIG. 7

*

*Factory Installed

Wire insulation must be rated at 
167º F (75º C) or greater. Use at 
least 18 AWG copper conductors, 
or as required by code. Use of other 
wire or insulation types could result 
in fire causing property damage or 
serious injury.

NOTE:

 For 24 VAC LTA-2 models, LTA0243S-2, 24 VAC to be 

supplied by an 

EXTERNAL

 Class 2 power source to terminals 

H and N. For 120 VAC LTA-2 models, LTA1203S-2, 120 VAC is 
supplied by an external circuit to terminals H and N.

LWCO Wiring Using the Burner Circuit Power Source

(See Fig. 6):

1.  Connect the hot lead wire from the power source to terminal 

H

.

2.  Connect the neutral lead wire from the power source to terminal 

N

.

3.  Verify that factory installed jumper is present or connect an 18 

AWG (min.) jumper wire from terminal 

H

 to terminal 

COM

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4. Connect the neutral wire of the power source to the neutral 

side of the burner circuit. Connect wire from the hot side of the 
burner circuit to terminal 

NC

.

5.  Connect the neutral wire of the power source to the neutral side 

of a water feeder or alarm. Connect wire from the hot side of 
the water feeder or alarm to terminal 

NO

.

LWCO  Wiring Using a Power Source Other than Burner 
Circuit (See Fig. 7):

1. 

Remove Factory installed jumper.

2.  Connect the hot lead wire from the separate power source to 

terminal 

H

.

3.  Connect the neutral lead wire from the separate power source 

to terminal 

N

.

4.  Connect the hot lead wire from the burner circuit power source 

to terminal 

COM

.

5.  Connect the neutral wire of the burner circuit power source to 

the neutral side of the burner circuit. Connect wire from the hot 
side of the burner circuit to terminal 

NC

.

6.  Connect the neutral wire of the burner circuit power source to 

the neutral side of a water feeder or alarm. Connect wire from 
the hot side of the water feeder or alarm to terminal 

NO

.

Be sure the power source for Control Unit and burner circuit
are the same voltage. Make sure you are not introducing
a second voltage source into the burner circuit via the
jumper. This will bypass other operating limit, and/or safety
controls, which may result in property damage, personal 
injury, or death.

Testing: 

1. DO NOT fill boiler. Set thermostat to lowest possible setting          
    and turn on electric power to the boiler. On initial start-up, the
    LTA-2 will indicate a low water condition, which indicates  
    proper function. The "STATUS" LED on the control unit should  
    illuminate RED. The burner should not operate without water      
    in the system.
2. Fill boiler with water. Once water covers the probe, the "STATUS"  
    LED on the control should turn from RED to GREEN.
3. Set thermostat to call for heat and verify that the burner ignites.
4. With the burner aflame, depress and hold the test switch while       
    observing the burner and the "STATUS" LED on the LTA-2. After   
    the "STATUS" LED illuminates RED, the burner should turn off.
5. Release the test switch and verify that the burner ignites  

   

    (provided water covers the probe). The "STATUS" LED on        
    the control unit should turn from RED to GREEN.
6. If burner fails to cutoff or relight, see the Troubleshooting section  
    for details. Otherwise, set the thermostat to its normal setting.
Once correct operation of the LTA-2 has been tested, test all other   
safety, limit, and control devices before finalizing system operation.

PROBE CLEANING
FIG. 9

TEFLON SLEEVE INSULATOR

(Be careful not to damage during cleaning)

DWG #1108-8

Cleaning, Maintenance, and Replacement:

• Test the operation of the LTA-2 annually, or more frequently,      
   by pressing the “TEST” button. The “STATUS” LED should 
   turn RED and the boiler should shut down.
• Probe must be inspected every 5 years, (or sooner if “SERVICE”  
   LED turns on), for scale build-up or coating. Clean all oils, fluxes,  
   and scale from probe with a clean rag.
• The control unit should be replaced every 15 years. In areas       
   of high humidity, heavy dust, or other airborne contaminants     
   more frequent replacement may be required.

Содержание LTA-2

Страница 1: ...ing NEMA 1 for indoor use only Input Power 2 8 VA 120 VAC 2 8 VA 24 VAC supplied by a Class 2 power source Reset Automatic reset when water level returns to safe level Testing Integrated test switch for testing safety shutdown US Patents 6 904 800 7 243 540 and 7 317 993 Other Patents Pending Installation must be performed by qualified personnel and in accordance with all national and local codes ...

Страница 2: ...robe so that the exposed portion of the stainless steel is a minimum of 1 4 from any grounding surface inside the boiler to prevent the probe from shorting See Fig 2 4 Tighten probe securely with a wrench using bushing flats provided Use pipe thread sealant to seal the probe threads tures Status LED Service LED Test Button Do not tighten by grasping the device enclosure Use wrenching flats on the ...

Страница 3: ... the two mounting screws in the probe bushing are loosened approximately 1 8 from the bushing surface 3 Then remove the first lock washer nut from the probe threads 4 Orient the slotted holes in the control unit over the heads of the mounting screws of the probe and turn control unit counter clockwisesothattheendsoftheslotsarefullyunderthemounting screw heads Tighten mounting screws 5 Replace the ...

Страница 4: ...onnect wire from the hot side of the water feeder or alarm to terminal NO Be sure the power source for Control Unit and burner circuit are the same voltage Make sure you are not introducing a second voltage source into the burner circuit via the jumper This will bypass other operating limit and or safety controls which may result in property damage personal injury or death Testing 1 DO NOT fill bo...

Страница 5: ...dels w Red Green LEDs H N C B W McDonnell Miller Series 750 1 2 3 4 5 McDonnell Miller RB 122 H Black Wire N White Wire C Yellow Wire B Yellow Wire McDonnell Miller RB 120 1 2 3 4 5 McDonnell Miller RB 24 Red Wire White Wire Yellow Wire Yellow Wire Hydrolevel 24 Black Wire White Wire Orange Wire Brown Wire Hydrolevel 170 H GN P1 P2 A Hydrolevel 400 500 600 700 450 550 650 750 1 2 P1 P2 A Honeywell...

Страница 6: ...NTAL COSTS OF REMOVING OR REPLACING DEFECTIVE PRODUCTS This warranty gives the purchaser specific rights and the purchaser may have other rights which vary from state to state Some states do not allow limitations on how long an implied warranty lasts or on the exclusion of incidental or consequential damages so these limitations or exclusions may not apply to you Symptom Possible Cause Remedy Boil...

Отзывы: