DWG# 3576-1

LTA-2 Features:

Item

Description

Status LED

Bi-color LED status indicator.  See "LED States" 
table for details.

Service LED

Amber LED indicator that service is needed on 
LTA-2 or system.

Test Button

Push button switch for testing safety shutdown 
of boiler controls.

Status LED

Service LED

Contacts

Meaning

Green

Off

Closed

Normal

Green

Amber

Closed

Safe water level, weak probe signal - Service soon.

Red

Off

Open

Low water condition, (LW)

Red

Amber

Open

Probe signal too weak, LW condition - Service 

now

.

Blinking

Red

Open

Control failure. Lockout in LW condition.

Off

Off

Open

No power to LWCO.

LED States:

Installation: 

1. Install the probe above the minimum safe water level, as determined from the boiler manufacturer's literature. (See Fig. 1)

NOTE:

 This may be in a tapping on the boiler or in the boiler supply or return piping. 

2. Install the probe to extend into the boiler cavity or piping to make contact with the water.
3. Install the probe so that the exposed portion of the stainless steel is a minimum of 1/4" from any grounding surface inside the 

boiler (to prevent the probe from shorting). (See Fig. 2)

4. Tighten probe securely with a wrench, using bushing flats provided. Use pipe thread sealant to seal the probe threads.

tures:

Status LED

Service LED

Test 

Button

• Do not tighten by grasping the device enclosure. Use         
  wrenching flats on the probe bushing only. Failure to install   
  properly could damage the device and cause improper    
  operation resulting in damage to equipment and property.

• Do not use manual reset low water cutoffs with automatic  
  water feeders. Flooding, equipment damage, and         
  property damage can result. Only use automatic water   
  feeders with automatic reset low water cutoffs.

• Do not mount device with probe angled upward or      
  deposits can accumulate on the probe. 

• Mount only with probe facing horizontally or vertically  
  downward and maintain 1/4" minimum clearance from  
  electrode and pipe wall. 

• Failure to install probe as directed can cause improper  
  operation and damage to equipment and property.

PROBE SPACING REQUIREMENTS

FIG. 2

MINIMUM SAFE WATER LEVEL

FIG. 1

Содержание LTA-2

Страница 1: ...ing NEMA 1 for indoor use only Input Power 2 8 VA 120 VAC 2 8 VA 24 VAC supplied by a Class 2 power source Reset Automatic reset when water level returns to safe level Testing Integrated test switch for testing safety shutdown US Patents 6 904 800 7 243 540 and 7 317 993 Other Patents Pending Installation must be performed by qualified personnel and in accordance with all national and local codes ...

Страница 2: ...robe so that the exposed portion of the stainless steel is a minimum of 1 4 from any grounding surface inside the boiler to prevent the probe from shorting See Fig 2 4 Tighten probe securely with a wrench using bushing flats provided Use pipe thread sealant to seal the probe threads tures Status LED Service LED Test Button Do not tighten by grasping the device enclosure Use wrenching flats on the ...

Страница 3: ... the two mounting screws in the probe bushing are loosened approximately 1 8 from the bushing surface 3 Then remove the first lock washer nut from the probe threads 4 Orient the slotted holes in the control unit over the heads of the mounting screws of the probe and turn control unit counter clockwisesothattheendsoftheslotsarefullyunderthemounting screw heads Tighten mounting screws 5 Replace the ...

Страница 4: ...onnect wire from the hot side of the water feeder or alarm to terminal NO Be sure the power source for Control Unit and burner circuit are the same voltage Make sure you are not introducing a second voltage source into the burner circuit via the jumper This will bypass other operating limit and or safety controls which may result in property damage personal injury or death Testing 1 DO NOT fill bo...

Страница 5: ...dels w Red Green LEDs H N C B W McDonnell Miller Series 750 1 2 3 4 5 McDonnell Miller RB 122 H Black Wire N White Wire C Yellow Wire B Yellow Wire McDonnell Miller RB 120 1 2 3 4 5 McDonnell Miller RB 24 Red Wire White Wire Yellow Wire Yellow Wire Hydrolevel 24 Black Wire White Wire Orange Wire Brown Wire Hydrolevel 170 H GN P1 P2 A Hydrolevel 400 500 600 700 450 550 650 750 1 2 P1 P2 A Honeywell...

Страница 6: ...NTAL COSTS OF REMOVING OR REPLACING DEFECTIVE PRODUCTS This warranty gives the purchaser specific rights and the purchaser may have other rights which vary from state to state Some states do not allow limitations on how long an implied warranty lasts or on the exclusion of incidental or consequential damages so these limitations or exclusions may not apply to you Symptom Possible Cause Remedy Boil...

Отзывы: