iWorx® SMZ1
505-048-2, Effective: March 10, 2015
21
© 2015 Taco Electronic Solutions, Inc.
Outputs
This screen list all the outputs of the SMZ1. These values cannot be changed.
Global SML Sense
Off, On
Status of the global snow melt sensor
Outdoor Temp (Local)
-29 to 230
°F (-33 to 110
°C)
OAT as reported from the controller
SMLT Heater Temp
-29 to 230
°F (-33 to 110
°C)
Temperature of heating element in five-wire SMLT
Sensor
Setting
Range
Description
SMLT Heat
Off, On
Status of the pump output.
Primary Pump
Group 1 Pump
Group 2 Pump
Zone 1 Pump
Zone 2 Pump
Zone 3 Pump
Zone 4 Pump
Zone 1 Out
0.00% to 100.00%
Status of the zone outputs.
Zone 2 Out
Zone 3 Out
Zone 4 Out
Zone 1 Setpoint
-4 to 42
°F (-20 to 5.6
°C)
Current setpoint for each zone.
Zone 2 Setpoint
Zone 3 Setpoint
Zone 4 Setpoint
Runtimes
Z1, Z2, Z3, Z4, G1, G2, P
0 to 65535 hours
Actual number of run hours for the output
Setting
Range
Description
Outside Temp
-29 to 230
°F (-33 to 110
°C)
OAT as reported from the ASM2 controller on the net-
work