Taco iWorx SMZ1 Скачать руководство пользователя страница 18

iWorx® SMZ1

18

 

505-048-2, Effective: March 10, 2015 

© 2015 Taco Electronic Solutions, Inc.

Zone Sense with Idle

This mode operates similar to the Zone Sense mode except it also activates when the zone slab temperature drops 
below the idle temperature setpoint regardless of the state of the Local Snow Sensor. 

Zone Output Operation

The four zone outputs may be used for zone valves or other 24 VAC-actuated heat sources. If not disabled by the out-
door limits, the outputs for each zone are operated to maintain the zone setpoints established above. The outputs are 
hysteretically controlled by comparing each zone temperature (Zone 1/2/3/4 Temperature) with the respective setpoints 
(Zone 1/2/3/4 Setpoint), or by a PI loop modulated output.

The status of each output is displayed on the LCI (Zone 1/2/3/4 Output). 

Primary and Group Circulators

The primary circulator output is an on/off output that energizes whenever any of the four zone outputs are turned on. 
Group Circulator outputs turn on whenever their associated zones are active. See 

Zone X Configuration

 for more info.

Gain Control 

The analog outputs are modulated by a Propor Integral (P+I) control loop based on the heating loop setpoint 
and the space temperature. The P+I control loop modulates the valve to maintain a constant slab temperature. As the 
temperature decreases below the heating loop setpoint, the heating valve is modulated open. The heating valve is 
modulated closed as the temperature increases above the heating loop setpoint.  

To prevent the integral component from becoming too large, there is anti-wind up reset protection. This protection 
clamps the integral value when all of the components add up to more than 100% or less than 0%. 

Demand Outputs & BLM Communication

When any of the zone outputs are turned on, the 

Primary

 output is turned on. This may be used to operate a supply 

pump for the zone circuits or to signal a heat demand to a non-networked boiler control or other heat source. If the 
SMZ1 

Heat Demand

 setting is on, then the status of this output is communicated to the BLM as a primary loop 

demand. 

The greatest of the four zone demands is displayed as the 

Maximum Zone Demand

. If the SMZ1 

Zone Demand

 setting 

is on, this maximum value is communicated to the BLM as a sub-zone demand for the secondary loop. If the outdoor 
temperature is below the OAT heating cutoff of the BLM, the BLM zone pump is operated and the injection output is 
controlled to provide the appropriate outdoor reset temperature in the secondary loop. The boilers and primary pump 
are operated as needed to meet the injection demand.

If the SMZ1 zones are on the secondary loop of the BLM, only the SMZ1 

Zone Demand

 setting needs to be on, since 

the demand for the boiler is dictated by the injection requirements. This method fires the boiler only as needed. How-
ever, both BLM settings, the 

Heat Demand

 and the 

Zone Demand

 may be turned on. The effect of this is to create a 

demand for the boiler whenever a SMZ1 zone is calling. This serves to keep the boiler in a standby mode that could 
reduce cycling as the demand from the secondary loop varies.

Additional Features

Commissioning Switch

In addition to the individual zone commissioning switches, a single switch setting can be adjusted at the LCI. By setting 

Commissioning

 to "On,” all eight digital outputs are turned on simultaneously.

Alarm Monitoring

The controller detects certain conditions and sends them to the LCI as alarms. These alarms are displayed and 
recorded for later access, but do not alter the system operation.

Temperature Sensor Alarm

If the analog input from a thermistor is outside of the expected range of the thermistor (-60 °F to 230 °F [-51 °C to 110 
°C]), this alarm is sent to the LCI. An alarm of this type is most likely due to a wiring fault causing the input to be shorted 
or open. An open sensor results in a reading of -60 °F (-51 °C), while a short appears as 230 °F (110 °C). 

Содержание iWorx SMZ1

Страница 1: ...pecting the Equipment 5 What is Not Included with this Equipment 5 Equipment Location 5 Selecting a Power Source 6 Installation 6 Mounting the Device 6 Routing Cabling to the Device 7 Grounding the Device 7 Wiring Information 8 Connecting Input Devices 13 Connecting Output Devices 14 Other Connections 15 Specifications 15 Electrical 15 Mechanical 16 Application Description 17 Sequence of Operation...

Страница 2: ...iWorx SMZ1 2 505 048 2 Effective March 10 2015 2015 Taco Electronic Solutions Inc THIS PAGE LEFT BLANK INTENTIONALLY ...

Страница 3: ...o a BLM series boiler controller or HPM heat pump master controller Outdoor Air Cutoff temperature Configurable group circulators for assigning different heat sources to different groups of zones Automatic configuration with a Local Control Interface LCI touchscreen Alarm Event Reporting PURPOSE OF THIS GUIDE The iWorx SMZ1 Application Guide provides application information for the SMZ1 Controller...

Страница 4: ...le for 167 F 75 C Part Number Audience Purpose iWorx SMZ1 Application Guide Document No 505 048 2 this doc ument Application Engineers Wholesalers Contractors Provides specific application information about the BLM series including sequence of operation and configuration information iWorx LCI Application Guide Document No 505 002 Application Engineers Installers Service Personnel Start up Technici...

Страница 5: ...ipment and the receiver Connect the equipment to a power source different from that to which the receiver is connected Consult the equipment supplier or an experienced radio TV technician for help You are cautioned that any changes or modifications to this equipment not expressly approved in these instructions could void your authority to operate this equipment in the United States BEFORE INSTALLI...

Страница 6: ...the load s coil To provide necessary RFI and transient protection the controller s ground GND pin T40 must be connected to earth ground or the earth ground of the packaged unit s enclosure ground Failure to properly ground the controller may cause it to exceed FCC limits Excessive noise could also produce inaccurate sensor data The power source must be capable of operating with this connection to ...

Страница 7: ...he control enclosure and wiring conduit Grounding the Device The ground terminal T40 must be securely connected to earth ground Failure to properly ground this equipment will result in improper operation Improper grounding may also increase the risk of electrical shock and may increase the possibility of interference with radio TV reception For best performance connect the power supply common term...

Страница 8: ...Taco Electronic Solutions Inc WIRING INFORMATION WARNING Terminals 12 15 18 and 38 are connected internally on all SMZ1 controllers Disconnect ALL power sources when installing or servicing this equipment to prevent electrical shock or equipment dam age ...

Страница 9: ...iWorx SMZ1 505 048 2 Effective March 10 2015 9 2015 Taco Electronic Solutions Inc Figure 2 SMZ1 Power Sourcing ...

Страница 10: ...iWorx SMZ1 10 505 048 2 Effective March 10 2015 2015 Taco Electronic Solutions Inc Figure 3 SMZ1 Power Isolated ...

Страница 11: ...iWorx SMZ1 505 048 2 Effective March 10 2015 11 2015 Taco Electronic Solutions Inc Figure 4 SMZ1 Global Snow Melt Four Zones Power Sourcing ...

Страница 12: ...iWorx SMZ1 12 505 048 2 Effective March 10 2015 2015 Taco Electronic Solutions Inc Figure 5 SMZ1 Global Snow Melt Four Zones 5 Wire Sensor Power Sourcing ...

Страница 13: ...With Idle To connect the snowmelt sensor attach one wire to the SMS1 T19 and the other to the associated COM T18 Slab 1 Temperature ST1 This input uses a Precon III thermistor in the slab To connect a thermistor attach one wire to the ST1 T17 input and the other the adjacent COM T18 Snow Melt Sensor 2 SMS2 This input uses a snowmelt sensor individual zone snowmelt mode set as Zone Sense or Zone Se...

Страница 14: ...nsor to SHT T3 The sensor s black ground wire should already be connected to COM Outdoor Air Temperature OAT This input uses a Precon III thermistor To connect a thermistor attach one wire to the OAT T7 input and the other the adjacent COM T6 Once connected remove the controller s cover and move the jumper W15 from Stat to UI11 Remember to place the UI11 dip switch in the thermistor positions Righ...

Страница 15: ... T21 Zone 4 Out Z4 The Zone 4 output must be connected to a 24 VAC pilot relay if the load is greater than 1 Amp See preceding figures for details If the load is less than 1 Amp connect it to Z4 T20 and TC78 T21 SMLT Heater SH This output is used to regulate the temperature of the heating element in a five wire SMLT sensor Connect the Red wire from that sensor to SH T3 The sensor s black ground wi...

Страница 16: ...eed 78KBPS 42 4 Volts DC max Cabling Maximum node to node distance 1312 feet 400 meters Maximum total distance 1640 feet 500 meters For detailed specifications refer to the FTT 10A Free Topology Transceiver User s Guide published by Echelon Corpo ration www echelon com support documentation manuals transceivers Mechanical Housing Dimensions 5 55 141mm high 6 54 166 mm wide 1 75 deep 44 mm ABS Weig...

Страница 17: ...te supply temperatures The SML1 may be configured for a secondary loop supply which uses the injection functions of the BLM or it may be set to use only the primary loop as a supply The commissioning switch displayed on the LCI can be set to turn on all outputs simultaneously for test purposes The zone valve outputs are capable of actuating 2 wire zone valves with up to 1 0 A current draw 0 10V mo...

Страница 18: ...supply pump for the zone circuits or to signal a heat demand to a non networked boiler control or other heat source If the SMZ1 Heat Demand setting is on then the status of this output is communicated to the BLM as a primary loop demand The greatest of the four zone demands is displayed as the Maximum Zone Demand If the SMZ1 Zone Demand setting is on this maximum value is communicated to the BLM a...

Страница 19: ... HPM1 Automatic Configuration The SMZ1 and iWorx Local Control Interface LCI use a self configuring network management scheme requiring no external tools binding or LONWORKS knowledge The LCI recognizes and configures the SMZ1 when the controller s service pin is pressed The controller s status light flashes green until the controller is configured and is solid green after the controller is config...

Страница 20: ...hardware input OCC will still be displayed on the LCI based on its configuration nviResetRuntime is a command to reset the fan heating and cooling runtimes If the value sent is 0 then no reset occurs if the value sent is 1 then the runtimes are reset nviSysTime is a time stamp to set the date and time Writing to this variable will change the time on the device and will affect all time related func...

Страница 21: ...ve wire SMLT Sensor Setting Range Description SMLT Heat Off On Status of the pump output Primary Pump Group 1 Pump Group 2 Pump Zone 1 Pump Zone 2 Pump Zone 3 Pump Zone 4 Pump Zone 1 Out 0 00 to 100 00 Status of the zone outputs Zone 2 Out Zone 3 Out Zone 4 Out Zone 1 Setpoint 4 to 42 F 20 to 5 6 C Current setpoint for each zone Zone 2 Setpoint Zone 3 Setpoint Zone 4 Setpoint Runtimes Z1 Z2 Z3 Z4 ...

Страница 22: ...d Structure N A Zone configuration for Modulated Output Zone 4 Mod Structure N A Zone configuration for Modulated Output OAT Snow Melt Cutoff 29 9 to 41 F 34 4 to 5 0 C 0 F 17 8 C Excessive Cold shutdown Zone 1 Name Alpha numeric string max 17 characters Zone 1 Zone naming override This name appears for the individual zone setting in the LCI Zone 2 Name Alpha numeric string max 17 characters Zone ...

Страница 23: ...intains the slab during idling operation For Digital Zones This is the temperature at which the digital zone output turns off during idling operation Slab Low Idle Setp 4 to 42 F 20 to 5 5 C 20 0 F 6 7 C Temperature at which the digital zone output turns on in idling operation Setting Range Default Description Gain 4 to 5 0 Gain for zone response On 0 to 100 30 0 Initial Output when zone activates...

Страница 24: ...larm Trigger Alarm Reset Temperature Sensor Alarm Normal Alarm Any one of the attached Sensors is Open or Short Sensor Reading is within the specified Sensor range or faulty sensor gets replaced Unit Maintenance Alarm Normal Alarm Any of the output runtimes exceeds the specified limit Runtimes are reset ...

Страница 25: ...on Status Solid green when running and configured by an LCI networking Flashing green when running and NOT configured by an LCI stand alone Solid red when a fault condition exists control shut down Blinking Red the controller has a device failure Solid Amber The controller has not received a LCI ping message in over 10 minutes and is part of a network Network Yellow while the controller is transmi...

Страница 26: ...ot relay have been powered with 24 VAC and the output has been correctly wired to the coil of the pilot relay Also ensure that the pilot relay has a 24 VAC coil Ensure that the output jumpers are in the right position for this application isolated group power sourcing or power sink ing The 10K thermistor reading is out of range The input is either shorted or open or the dip switches are not set Ma...

Страница 27: ...iWorx SMZ1 505 048 2 Effective March 10 2015 27 2015 Taco Electronic Solutions Inc ...

Страница 28: ...covered by this warranty TES products are not intended for use to sup port fire suppression systems life support sys tems critical care applications commercial aviation nuclear facilities or any other applica tions where product failure could lead to injury to person loss of life or catastrophic property damage and should not be sold for such pur poses If in doubt as to whether a particular produc...

Отзывы: