iWorx® HPU3

502-035, Effective: February 21, 2012

11 

© 2012 Taco Electronic Solutions, Inc.

Low Pressure Alarm (LP) 

To connect the Low Pressure alarm to the digital input, attach one wire of the contact to LP (T10) and the other wire to 
the adjacent common (T9). This must be a dry contact, normally open switch. 

  High Pressure Alarm (HP) 

To connect the High Pressure alarm to the digital input, attach one wire of the contact to HP(T8) and the other wire to 
the adjacent common (T9). This must be a dry contact, normally open switch. 

  Heat Pump Power Transducer (POW, optional) 

To connect the power transducer to the unit, connect the positive wire from the sensor to POW (T11) and the other wire 
to the adjacent common (T12). The sensor must be provided and configured by Taco. It is required if the HPU3 needs 
to report energy usage to a GHP1 for COP calculations. 

Space Temperature (ST, optional)

To connect a thermistor (Precon II or Precon III) to the analog input, attach one wire of the sensor to ST (T7) and the 
other wire to the adjacent common (T6). The thermistor can be used if no TS300 series thermostat is being used. 

Supply Air Temperature (SAT, optional)

To connect a thermistor (Precon III) to the analog input, attach one wire of the sensor to ST (T13) and the other wire to 
the adjacent common (T12). 

Connecting Output Devices

Stage 1 & Stage 2 (S1, S2)

The outputs for the stages must be connected to 24 VAC pilot relays if the load is greater than 1 Amp for each pump. If 
the load is less than 1 Amp, connect stage 1 to S1 (T28) and adjacent COM (T27), and connect stage 2 to S2 (T26) 
and adjacent COM (T27)

Reversing Valve (RV) 

The output for the reversing valve must be connected to a 24 VAC pilot relays if the load is greater than 1 Amp. If the 
load is less than 1 Amp, connect the reversing valve input to RV (T29) and adjacent COM (T30). 

Fan (FAN) 

The output for the fan must be connected to a 24 VAC pilot relay if the load is greater than 1 Amp. If the load is less 
than 1 Amp, connect the fan input to FAN (T31) and adjacent COM (T30).

Dehumidification (DHUM) 

The dehumidification mode output must be connected to a 24 VAC pilot relays if the load is greater than 1 Amp. If the 
load is less than 1 Amp, connect the fan input to DHUM (T25) and adjacent COM (T24). 

Modulated Fan (MFAN) 

The modulated fan output can be set to 0-10 V max through the control logic. Connect the positive wire from the fan to 
FANM (T35) and the other wire to COM (T36). 

Other Connections

Network (LON)

Network wiring must be twisted pair. One network wire must be connected to terminal NETA (T1) and the other network 
wire must be connected to terminal NETB (T2). Polarity is not an issue since an FTT-10A network is used for commu-
nications.

Содержание iWorX HPU3

Страница 1: ...llation Instructions 4 Precautions 4 General 4 Static Electricity 4 Location 4 FCC Compliance 4 Before Installing 5 About this Document 5 Inspecting the Equipment 5 What is Not Included with this Equipment 5 Equipment Location 5 Selecting a Power Source 5 Installation 5 Mounting the Device 6 Routing Cabling to the Device 7 Grounding the Device 8 Wiring Information 8 Connecting Input Devices 10 Con...

Страница 2: ...occupied heat and cool LONWORKS interface to building automation systems Equipment status input for additional safety interlocks High and Low Pressure Alarm inputs Thermostat with space temperature humidity temperature setpoint adjust fan override occupancy override Fan control energized on call for heating or cooling Automatic heat cool changeover Global unit enable for main plant synchronization...

Страница 3: ... Technicians End user Provides instructions for setting up and using the iWorx HPU3 iWorx LCI2 Application Guide Doc ument No 505 002 Application Engineers Installers Service Personnel Start up Technicians End user Provides instructions for setting up and using the iWorx Local Control Interface iWorx LHP2 Application Guide Doc ument No 505 024 Application Engineers Installers Service Personnel Sta...

Страница 4: ...or welding equipment This equipment is suitable for indoor use only Preferably or as required by National Electrical Code the unit is intended to be installed within an electrical control enclosure Operate where ambient temperatures do not exceed 140 F 60 C or fall below 32 F 0 C and relative humidity does not exceed 90 non condensing FCC Compliance This equipment has been tested and found to comp...

Страница 5: ...in the ranges specified for this equipment The equipment must be installed within 500 feet of all input peripherals smoke detectors sensors etc that are con nected to the equipment Selecting a Power Source This equipment requires a UL recognized Class 2 external power source not supplied to operate The controller power input requires a voltage of 24 Volts AC To calculate power source current requi...

Страница 6: ... Enclosure mounting is recommended 2 Hold the controller on the panel you wish to mount it on With a marker or pencil mark the mounting locations on the panel 3 Using a small drill bit pre drill the mounting holes 4 Using two 6 pan head screws mount the controller to the panel 5 Wire the controller See Routing Cabling to the Device ...

Страница 7: ...012 Taco Electronic Solutions Inc Figure 1 Mounting Dimensions Routing Cabling to the Device Cabling used to connect the power source and cabling used to connect the FTT 10A network must remain separated within the control enclosure and wiring conduit ...

Страница 8: ... the risk of electrical shock and may increase the possibility of interference with radio TV reception For best performance connect the power supply common terminal T38 to the same external point as the ground terminal T40 WIRING INFORMATION WARNING Terminals 6 9 and 12 are connected internally on all HPU3 controllers Disconnect ALL power sources when installing or servicing this equipment to prev...

Страница 9: ...iWorx HPU3 502 035 Effective February 21 2012 9 2012 Taco Electronic Solutions Inc Figure 3 HPU3 Wiring Example Power Sinking ...

Страница 10: ...ch one wire from the thermostat to STAT T3 and the other wire to the adjacent common T4 Equipment Status EQS To connect the equipment switch to the digital input attach one wire of the contact to EQS T5 and the other wire to the adjacent common T6 This must be a dry contact normally open switch which closes when flow is detected If a flow proof switch is not installed the terminals should be conne...

Страница 11: ...nd the other wire to the adjacent common T12 Connecting Output Devices Stage 1 Stage 2 S1 S2 The outputs for the stages must be connected to 24 VAC pilot relays if the load is greater than 1 Amp for each pump If the load is less than 1 Amp connect stage 1 to S1 T28 and adjacent COM T27 and connect stage 2 to S2 T26 and adjacent COM T27 Reversing Valve RV The output for the reversing valve must be ...

Страница 12: ...puts Cabling twisted shielded pair 18 AWG recommended 500 feet max 152 meters Resolution 10 bit Stat Precon Type III 10K thermistor or 12 Volt nominal internally limited to 0 04 A SLink Supply Air Temp Precon Type III 10K thermistor Heat Pump Power Transducer 0 to 10 Volts DC Equipment Status High Pressure Alarm Low Pressure Alarm Dry Contact Normally Open 5 Volts DC Max Outputs Stage 1 Stage 2 Re...

Страница 13: ...high 6 54 166 mm wide 1 75 deep 44 mm ABS Weight Controller Weight 0 70 pounds 0 32 kilograms Shipping Weight 1 0 pounds 0 46 kilograms Electronics Processor 3150 Neuron 10 MHz Flash 48 Kilobytes SRAM 8 Kilobytes Termination 0 197 5 0 mm Pluggable Terminal Blocks 14 22 AWG Environmental Temperature 32 F to 140 F 0 C to 60 C Humidity 0 to 90 non condensing Agency Listings UL Listed for US and Canad...

Страница 14: ...on Status Solid green when running and configured by an LCI networking Flashing green when running and NOT configured by an LCI stand alone Solid red when a fault condition exists control shut down Blinking Red the controller has a device failure Solid Amber The controller has not received a LCI ping message in over 10 minutes and is part of a network Network Yellow while the controller is transmi...

Страница 15: ... before proper operation can be restored The fan and staged pilot relays will not come on even though the LCI indicates it is on Ensure that the controller and output pilot relay have been powered with 24 VAC and the output has been correctly wired to the coil of the pilot relay Also ensure that the pilot relay has a 24 VAC coil The Space Temperature or Supply Air Temperature thermistor reading is...

Страница 16: ...covered by this warranty TES products are not intended for use to sup port fire suppression systems life support sys tems critical care applications commercial aviation nuclear facilities or any other applica tions where product failure could lead to injury to person loss of life or catastrophic property damage and should not be sold for such pur poses If in doubt as to whether a particular produc...

Отзывы: