6.Press
Setpoints
.
7.The
Setpoints
menu opens.
a.Select
Setpoint
.
b.Select
Cooling Offset
.
c. Select
Heating Offset
.
d.Select USER setpoint adjustable limits (
SP Adjust
Limit
). Setting is +- setpoint.
e.Select unoccupied cooling setpoint (
Unocc Cool
).
f. Select unoccupied heating setpoint (
Unocc Heat
).
g.Press
Save
.
8.Press
Comp. Stages
.
9.The
Comp. Stages
menu opens.
a.Select number of
Stages
of equipment (1 or 2).
b.Select the stage
Control Band
in degrees. Cannot
be set to 0.
c. Select the
Stage Time
in minutes. Cannot be set to
0.
d.Press
Save
.
10.Press
Fan Type
.
11.The
Fan Type
menu opens. Select:
a.“ON” = On in Occupied mode, cycles with Heat/
Cool call in Unoccupied.
b.“Auto” = cycles with Heat/Cool call always.
c. Press
Save
.
12.Press
Rev. Valve Action
.
13.The
Rev Valve Action
menu opens.
a.Select “Energize on Heat” or “Energize on Cool.”
NOTE:
Consult Heat Pump Equipment Installation
Instructions to determine correct selection.
b.Press
Save
.
Содержание iWorx HPU2
Страница 4: ...iWorx HPU Series 4 502 025 Effective April 17 2013 2013 Taco Electronic Solutions Inc...
Страница 5: ...iWorx HPU Series 502 025 Effective April 17 2013 5 2013 Taco Electronic Solutions Inc...
Страница 8: ...iWorx HPU Series 8 502 025 Effective April 17 2013 2013 Taco Electronic Solutions Inc...
Страница 9: ...iWorx HPU Series 502 025 Effective April 17 2013 9 2013 Taco Electronic Solutions Inc...
Страница 14: ...iWorx HPU Series 14 502 025 Effective April 17 2013 2013 Taco Electronic Solutions Inc...
Страница 15: ...iWorx HPU Series 502 025 Effective April 17 2013 15 2013 Taco Electronic Solutions Inc...