6.Press 

Setpoints

.

7.The 

Setpoints

 menu opens.

a.Select 

Setpoint

.

b.Select 

Cooling Offset

c. Select 

Heating Offset

.

d.Select USER setpoint adjustable limits (

SP Adjust 

Limit

). Setting is +- setpoint.

e.Select unoccupied cooling setpoint (

Unocc Cool

).

f. Select unoccupied heating setpoint (

Unocc Heat

).

g.Press 

Save

.

8.Press 

Comp. Stages

.

9.The 

Comp. Stages

 menu opens.

a.Select number of 

Stages

 of equipment (1 or 2).

b.Select the stage 

Control Band 

in degrees. Cannot 

be set to 0.

c. Select the 

Stage Time 

in minutes. Cannot be set to 

0.

d.Press 

Save

.

10.Press 

Fan Type

.

11.The 

Fan Type

 menu opens. Select:

a.“ON” = On in Occupied mode, cycles with Heat/

Cool call in Unoccupied.

b.“Auto” = cycles with Heat/Cool call always.
c. Press 

Save

.

12.Press 

Rev. Valve Action

.

13.The 

Rev Valve Action

 menu opens.

a.Select “Energize on Heat” or “Energize on Cool.” 

NOTE:

 Consult Heat Pump Equipment Installation 

Instructions to determine correct selection.

b.Press 

Save

.

Содержание iWorx HPU2

Страница 1: ...internally limited to 0 04 A TS300 Series Electrical Outputs Modulated Fan HPU3 only Analog 0 10 Vdc 2K Ohm minimum load 8 bit resolution Stage 1 Stage 2 Reversing Valve Fan Dehumidification HPU3 only...

Страница 2: ...lass 2 external power source not supplied to operate The controller power input requires a voltage of 24 Volts AC To calculate power source current requirements add the power consumption of all periph...

Страница 3: ...onnect the equipment to a power source different from that to which the receiver is connected Consult the equipment supplier or an experienced radio TV technician for help You are cautioned that any c...

Страница 4: ...iWorx HPU Series 4 502 025 Effective April 17 2013 2013 Taco Electronic Solutions Inc...

Страница 5: ...iWorx HPU Series 502 025 Effective April 17 2013 5 2013 Taco Electronic Solutions Inc...

Страница 6: ...be shorted Setup Instructions 1 Press Controllers from main screen 2 Select required HPU from controller list and press appropriate controller 3 Press All Settings 4 Press Thermostat 5 The Thermostat...

Страница 7: ...p Stages 9 The Comp Stages menu opens a Select number of Stages of equipment 1 or 2 b Select the stage Control Band in degrees Cannot be set to 0 c Select the Stage Time in minutes Cannot be set to 0...

Страница 8: ...iWorx HPU Series 8 502 025 Effective April 17 2013 2013 Taco Electronic Solutions Inc...

Страница 9: ...iWorx HPU Series 502 025 Effective April 17 2013 9 2013 Taco Electronic Solutions Inc...

Страница 10: ...shorted Setup Instructions 1 Press Controllers from main screen 2 Select required HPU3 from controller list and press appropriate controller 3 Press All Settings 4 Press Dehumidification 5 The Dehumid...

Страница 11: ...s 1 Press Controllers from main screen 2 Select required HPU3 from controller list and press appropriate controller 3 Press All Settings 4 Press Next 3 5 Press Mod Fan Settings 6 The Mod Fan Settings...

Страница 12: ...lot relay have been pow ered with 24 VAC and the output has been correctly wired to the coil of the pilot relay Also ensure that the pilot relay has a 24 VAC coil The 10K thermistor reading is at its...

Страница 13: ...ormation please refer to the last page of this Document for the company s Limited Warranty Statement which is also issued with the product or available at www taco hvac com Notes Description Audience...

Страница 14: ...iWorx HPU Series 14 502 025 Effective April 17 2013 2013 Taco Electronic Solutions Inc...

Страница 15: ...iWorx HPU Series 502 025 Effective April 17 2013 15 2013 Taco Electronic Solutions Inc...

Страница 16: ...be covered by this warranty TES products are not intended for use to support fire suppression systems life support systems critical care applications commercial aviation nuclear facilities or any othe...

Отзывы: