30 (36), 0-004-7771-2 (GB)
TAC AB, 2003-07-01
TAC Xenta 400 I/O modules
4 Installation
TAC Xenta 400 I/O modules
Terminals type X:
Min. cross-sectional area ...................................................0.25 mm²
Max. cable length .................................................................... 200 m
Terminals type U, connected as
a) digital inputs,
b) measurement devices using voltage signals that are
not
powered via the same transformer as the I/O module or
c) measurement devices using current signal
Min. cross-sectional area ...................................................0.25 mm²
Max. cable length .................................................................... 200 m
Terminals type U, connecting measurement devices, using voltage
signals that are powered via the
same
transformer as the I/O
module:
Min. cross-sectional area ...................................................0.75 mm²
Max. cable length ...................................................................... 20 m
Terminals type B or U, as thermistor inputs:
Min. cross-sectional area ...................................................0.75 mm²
Max. cable length,
up to 75 °C, cross-sectional area 0.75 mm² .............................. 75 m
up to 75 °C, cross-sectional area 1.5 mm² .............................. 150 m
up to 150 °C, cross-sectional area 1.5 mm² .............................. 75 m
Terminals type K (relay outputs):
Cross-sectional area ................................................. 0.75 – 1.5 mm²
Max. cable length .................................................................... 200 m
Terminals type Y (for actuators powered via
the
same
transformer as the I/O module):
Min. cross-sectional area ...................................................0.75 mm²
Max. cable length
1
................................................................... 20 m
Terminals type Y (for actuators power supplied via
their
own
transformer, external or internal;
or when the outputs have isolated converters):
Min. cross-sectional area ...................................................0.25 mm²
Max. cable length .................................................................... 200 m
1
Some actuators allow greater cable lengths, for example:
EM52
0.5 mm²
80 m
three wires
EM15LBB
0.75 mm²
80 m
three wires
EM42
0.75 mm²
80 m
four wires
TAC Forta
0.75 mm²
80 m
four wires
TAC Forta
1.5 mm²
100 m
three wires
(part nos. xxxx-
010
)
4.3
Commissioning
Commissioning of the I/O modules is always carried out together with
the base units (TAC Xenta controllers) that they belong to.
The procedure is therefore described in the TAC Xenta 300 and 401
manuals.
Содержание Xenta 411
Страница 2: ......
Страница 6: ...TAC Xenta 400 I O modules Contents 6 36 0 004 7771 2 GB TAC AB 2003 07 01...
Страница 12: ...12 36 0 004 7771 2 GB TAC AB 2003 07 01 TAC Xenta 400 I O modules 2 I O modules in the TAC Xenta 400 series...
Страница 32: ...32 36 0 004 7771 2 GB TAC AB 2003 07 01 TAC Xenta 400 I O modules Index...
Страница 34: ...TAC AB 2003 07 01 TAC Xenta 400 I O modules Reply form...
Страница 35: ......
Страница 36: ...TAC AB J gershillgatan 18 SE 213 75 MALM SWEDEN 46 40 38 68 50 switchboard www tac com...