![TAC Xenta 411 Скачать руководство пользователя страница 25](http://html1.mh-extra.com/html/tac/xenta-411/xenta-411_handbook_3164803025.webp)
TAC AB, 2003-07-01
0-004-7771-2 (GB), 25 (36)
TAC Xenta 400 I/O modules
4 Installation
Connections
When cabinet mounting is used, jumpers may be used between
M (measurement neutral) terminal pairs, as shown in the figure below
and on the next page. All G0 points must be connected to protective
ground.
Basic circuit diagram for cabinet connections of TAC Xenta 451/452 I/O modules
1 2
G G0 U1 M U2 Y1 M Y2 B1 M B2 M U3
G1 G G0
G G0 M X
G G0 MX X1
PU
230
VAC
G
G0
N
1 2
1 2
M S
0 - 10 V
G G0 M S
R =500
Ω
R
min 1.5 mm
2
, max 2 m
Insulated
signal
ground rail
Cabinet
terminals
Cabinet
ground
rail
TAC Xenta 451/452 I/O module
Measuring
device
0–10 V
Measuring
device (with
its own trafo)
Actuator
Thermistor
(2 sensors)
Measuring
device, two-
wire 4–20 mA
Actuator with
differential in-
put (FORTA)
A corresponding diagram for the TAC Xenta 471 is shown on the next
page.
Содержание Xenta 411
Страница 2: ......
Страница 6: ...TAC Xenta 400 I O modules Contents 6 36 0 004 7771 2 GB TAC AB 2003 07 01...
Страница 12: ...12 36 0 004 7771 2 GB TAC AB 2003 07 01 TAC Xenta 400 I O modules 2 I O modules in the TAC Xenta 400 series...
Страница 32: ...32 36 0 004 7771 2 GB TAC AB 2003 07 01 TAC Xenta 400 I O modules Index...
Страница 34: ...TAC AB 2003 07 01 TAC Xenta 400 I O modules Reply form...
Страница 35: ......
Страница 36: ...TAC AB J gershillgatan 18 SE 213 75 MALM SWEDEN 46 40 38 68 50 switchboard www tac com...