2 (4)

0FL-3485-001, 1994.01

The TA 239W controller is part of the C80 system and is
designed for the control of domestic hot water systems.

TA 239W should be used in combination with the EGWS type
fast temperature sensor and the EM5 type actuator. However,
also the EGW type sensor can be used.

The power supply can be 16 V DC or 24 V AC.

The connection of TA 239W is identical with the TA 219W and
TA 229W. Therefore it can directly replace a TA 219W or
TA 229W, without alteration of the connections.

MOUNTING

Controller TA 239W: The controller occupies one module on
the terminal board. Mount in accordance with the
0FL-3139-000 instruction.

Temperature sensor EGWS: Sensor for mounting in pipe
systems without separate pocket. Mount as close to the heat ex-
changer as possible. If a mixing valve is included in the system:
mount 300 mm after the valve.

Actuator EM5: Instruction is enclosed with the actuator.

ADJUSTMENTS

On the front panel:
SP
:

Set point
Range: 20-120 °C.

Under the cover:
Pb
:

P band
Range: 17-200 °C
Factory setting: 50 °C

T

i

:

Integral time
Range: 5-60 seconds
Factory setting: 10 seconds

HL:

High load changeover limit
Range: 6-10 V control output signal (OFF:no low load)
Factory setting: 9 V

DZ:

Low load dead zone
Jumper closed: 5 °C;
Jumper open: 2 °C
Factory setting: 5 °C

SPC: Set point displacement

Jumper in the upper position: SPC = 32;
Jumper in the lower position: SPC = 6,7
Factory setting: SPC = 6,7

ST:

Actuator stroke time
Jumper in the upper position: 60 seconds;
Jumper in the lower position: 15 seconds
Factory setting: 60 seconds

SC:

Sequence control
Jumper open: 3 steps;
Jumper in the upper position: 2 steps;
Jumper in the lower position: 1 step
Factory setting: 1 step

PS:

Power supply
Jumper in the upper position: 16 V DC;
Jumper in the lower position: 24 V AC
Factory setting: 16 V DC

OR: Y Output range

Jumper in the upper position: 2-10 V;
Jumper in the lower position: 0-10 V
Factory setting: 2-10 V

For TAC service personnel only:
P2:

Connection of flat cable to TM2.

TP1: Connection of test wire (6 V) to TM2.

TA 239W Installation instruction

Adjustments on
the circuit board

SPC

DZ

Pb

SC

PS

HL

OR

ST

Ti

P2

TP1

SP

ELECTRICAL INSTALLATION

Connections of the terminal block

M/G0 24 V AC neutral/External 16 V DC neutral
G1/G 24 V AC input/External 16 V DC input
M

Measuring ground (Sensor signal ground)

Y

Output 2-10 V/0-10 V. Connect signal ground to M/G0

B

Sensor. Connect signal ground to M

Z1

SPC input. Connect signal ground to M/G0

Note: If TA 239W is 24 V AC supplied, the actuator must be of
half-wave rectified type e.g. EM5, or else the controller and
the actuator must have separate transformers.

Length of cables

Max. 100 m (300 ft) of 1,5 mm

(AWG 16) cable for power

supply.
Max. 200 m (600 ft) of 0,5 mm

(AWG 20) for other connections.

TECHNICAL DATA

Part number, TA 239W with °C scale:

with cassette and terminal block ................. 239-1010-800
with transformer TR mounted in a case ...... 239-1010-0TR

Ambient temperature:

Operation ......................................................... 0 to +50 °C
Storage .......................................................... -40 to +50 °C

Ambient  humidity ............................................. max. 90% RH
Supply  voltage .............................................. 16 V DC ±0,4 V

24 V AC ±20%, 50-60 Hz

Power  consumption ............................................ max. 25 mA
Control output Y:

Output voltage .................... 2-10 V or 0-10 V, direct acting
Load ............................ max. 2 mA, max. 10 control inputs,

 short circuit proof

Control input Z1:

Permitted  voltage ......................................... max. 16 V DC
Input current .................................................... max. 0,1 mA

G

TA 239W

1

2

EGWS

X1

G

EM

X2 G2

G0

B M

G0

24V AC

0V

Y

Example: 16 V DC supply.

Example: 24 V AC supply.

G1

TA 239W

1

2

EGWS

X1

G

EM

X2 G2

G0

B M

G0

0V

Y

G1

24V AC