Maintenance and Examination
Frequent examination and maintenance is not required for the inverter.
To maintain appropriate reliability, please proceed with following periodical examination. Remember to
turn off power supply and wait till the Power LED goes off before proceed. (Due to the large amount of
remaining charges in the internal capacitors.)
(1) Clean out internal dust and dirt.
(2) Check out mounting screws on every terminal and parts. Tighten loose screws.
(3) Dielectric
strength
test
(a) Remove all conducting wires between Drive and outside world. Power must be turned OFF.
(b) The dielectric strength test inside Drive should be carried out only for T-VERTER major circuitry. Use
DC 500V: high resistance meter. Measured resistance should be higher than 100M ohm.
CAUTION: Do not perform dielectric strength test to the control circuit.
Connection for dielectric strength test
Input power source
DC-500V
high-resistance
meter
Grounding terminal
Motor
L1 (R)
T1 (U)
L2 (S)
Drive
T2 (V)
T3 (W)