Controller Output Scaling

In order to properly control the actuator, the output of the controller must be scaled 
appropriately. Table-2 below illustrates the correct output which corresponds to the 
electronic input of the transducer.

* Applies only to CP-8552.

CHECKOUT

4 to 20 mA Range 
(CP-8551 and 
CP-8552)

Note: The CP-8551 and CP-8552 4 to 20 mA span and start point potentiometers are not 
field adjustable.

To check transducer operation:

1. Check for foreign material such as dirt or oil in the air supply. Also check for clogged filters. 

Supply air contamination by dirt or oil is the most likely cause of malfunction.

2. Verify that the unit is mounted upright and wired correctly.

3. Verify that 20 psig (138 kPa) main air is present.

4. Verify with a digital multimeter that a 4 to 20 mAdc signal is present and of correct 

polarity. 

5. Adjust the input signal to 4 mA. Branch pressure should be 3 psig ± 1.0 (21 kPa). 

6. Adjust the input signal to 20 mA. Branch pressure (direct acting) should be 15 psig 

± 1.0 (103 kPa).

7. Unit is functional if correct pressures are indicated. Replace an inoperative transducer 

with a functional unit.

Table-2  Electronic/Pneumatic Transducer Conversion Chart.

Electronic Input

Output 

(PSI)

4-20 

mA 

6-9

Volts*

0-10

Volts*

3

4.00

6.00

0.00

4

5.33

6.25

0.83

5

6.67

6.50

1.67

6

8.00

6.75

2.50

7

9.33

7.00

3.33

8

10.67

7.25

4.17

9

12.00

7.50

5.00

10

13.33

7.75

5.83

11

14.67

8.00

6.67

12

16.00

8.25

7.50

13

17.33

8.50

8.33

14

18.67

8.75

9.17

15

20.00

9.00

10.00

Содержание CP-8551

Страница 1: ...il mounting for quick snap on installation Two wire loop powered or three wire voltage input High accuracy with low hysteresis Long term driftless operation with high repeatability Low air consumption...

Страница 2: ...Acting Maximum Pneumatic Output 1 to 18 psig 7 to 124 kPa Output Air Capacity Pressure 515 scim 141 ml s maximum with a 20 psig 138 kPa supply Operating Characteristics Linearity 1 of span 75 F 24 C...

Страница 3: ...screws not provided M 636 4 in T and B wire tie not provided Training Installer must be a qualified experienced technician CP 8551 M B M 3 to 15 psig 21 to 103 kPa to controlled device direct acting...

Страница 4: ...marily to provide a degree of protection against contact with the enclosed equipment Do not locate unit in areas subject to incidental contact vibration severe mechanical shock excessive moisture or c...

Страница 5: ...per selection as follows 1 Choose input range 2 Consult Table 1 for jumper position 3 Place jumper over square posts on appropriate lettered block Figure 4 4 Calibrate by performing appropriate CHECKO...

Страница 6: ...unction 2 Verify that the unit is mounted upright and wired correctly 3 Verify that 20 psig 138 kPa main air is present 4 Verify with a digital multimeter that a 4 to 20 mAdc signal is present and of...

Страница 7: ...gnal to bottom of range 0 or 6 V 7 Branch pressure should be 3 psig 21 kPa If not adjust start point potentiometer Figure 4 to obtain a 3 psig 21 kPa output 8 Adjust input to top of range 9 or 10 V 9...

Страница 8: ...marks and registered trademarks are the property of their respective owners Information contained within this document is subject to change without notice F 26159 5 www tac com TAC 1354 Clifford Avenu...

Отзывы: