F-26159-5
©
Copyright 2008 TAC All Rights Reserved.
3
TYPICAL APPLICATIONS (wiring diagram)
Figure-1 CP-8551 Typical Wiring.
Figure-2 CP-8552 Typical Wiring for Voltage Input.
Figure-3 CP-8552 Typical Wiring for Current Input.
INSTALLATION
Inspection
Inspect the package for damage. If damaged, notify the appropriate carrier immediately.
If undamaged, open the package and inspect the device for obvious damage. Return
damaged products.
Requirements
•
Wiring diagrams.
•
Tools (not provided):
– Screwdriver for mounting screws.
– Drill and drill bit for mounting screws.
•
Appropriate accessories.
•
Two (2) # 6 mounting screws (not provided).
•
M-636 4 in. T and B wire tie (not provided).
•
Training: Installer must be a qualified, experienced technician.
CP-8551
M
B
M
3 to 15 psig
(21 to 103 kPa
to controlled device
(direct acting)
+
—
+4 to 20 mA Current Input Signal
Signal Common
CP-8552
M
B
M
3 to 15 psig
(21 to 103 kPa
to controlled device
(direct acting)
+IV1
Signal Common
Voltage Input Signal
Power Common
COM
24 Vac/dc
24H
1
1
When multiple CP-8552s or other devices are powered
by a common source, uniform wiring polarity must be
maintained between all 24H and COM terminals. Check
to ensure that the controller’s COM terminal is not
connected to any other ground reference.
1
2
3
CP-8552
M
B
M
3 to 15 psig
(21 to 103 kPa
to controlled device
(direct acting)
COM
+IV1
Signal Common
+4 to 20 mA Current Input Signal
1
2
3