When the clock contacts are closed, the system will regulate according to the comfort setpoint, when 
they are open the regulation will be performed according to the 3°C reduced setpoint. 
 
Note that if you do not connect any clock, the inputs 6 and 7 are always open, so this will make the 
system perform the reduced setpoint regulation, however in the thermostat can always be manually 
selected the comfort setpoint. 
 
In this case there will not be a programmed reduction, but you will be able to manually select the 
comfort or reduced setpoint from the thermostat panel selector (in the DTP A80 BC the sun or moon 
position, see thermostat documentation for more information).  
 
If you desire the receiving unit never work with any reduction, just wire terminals 6 and 7 together. In 
case the receiver is used in conjunction with either a thermostat without 3°C reduction or a 
chronostat, it will never regulate with any reduction regardless the state of the clock input.

 

 

 

 

Maintenance 

No particular maintenance is required for this product. Periodically check for the good quality of the 
received signals. In case the signal from the thermostat is too weak or absent, the red side led (1) 
blinks. This could happen if the transmitter battery is flat.

 

 

 

 

Troubleshooting 

TROUBLE SHOOTING

 

SYMPTOM

 

PROBABLE REASON

 

REMEDY

 

The receiver seems to be 
completely ‘dead’. 

230V~ power supply is not 
present. 

Check for the correct supply 
of the device. Normally the led 
(1) remains turned-off, but 
at the start-up it flashes in a 
sequence “green-red-green-
red” to show the correct 
working of the appliance. 

The red side of the led (1) Fig. 
1 in the frontal panel blinks. 

The output is in “alarm status” 
because its relevant 
transmitter does not work well 
or the signal is too weak. 

Check the battery of the 
relevant transmitter. See its 
documentation for more 
information. 

When the transmitter is 
working in “Test mode” the 
receiver does not activate the 
relay. The green side of the 
led (1) quickly flashes three 
times. 

Signals issued by the 
transmitter are correctly 
received but the address set 
on the dip-switch of the 
transmitter does not match 
the address memorized in the 
receiver. 

Execute the “self-learning” as 
explained in the “System set-
up” section. 

When the transmitter is  
working in “Test mode” the 
receiver does not activate the 
relay. The green side of the 
led (1) remains always turned-
off. 

Signals received are too weak 
for the receiver to correctly 
decode the command. 

Reposition the transmitters 
and/or the receiver. Take care 
of avoiding positioning them 
close to metal screens or 
electrical disturbances 
sources. Spend some time to 
find the best orientation. 

 

 

 
WARNING ! 
- To determine the right position ensure that the radio signals transmitted are correctly 
received by the receiving unit. 
- To adjust properly room temperature, install the thermostats far from heat sources, 
airstreams or particularly cold walls (thermal bridges). 
- The appliance must be wired to the electric mains through a switch capable of 
disconnecting all poles compliant to the current safety standards and with a contact 
separation of at least 3 mm in all poles. 
- Installation and electrical wirings of this appliance must be made by qualified technicians 
and in compliance with the current standards. 
- Before wiring the appliance be sure to turn the mains power off.

 

 

 

 

 

 

Notes: In the view of a constant development of their products, 
the manufacturer reserves the right for changing technical data 
and features without prior notice. The consumer is guaranteed 
against any lack of conformity for 24 months from the time of 
delivery, according to the European Directive 1999/44/EC. The 
full text of guarantee is available on request from the seller.

Содержание DRPA83M01

Страница 1: ...n rooms or offices It features one SPDT relay output which is driven from radio commands received from a thermostat or a chronostat transmitter This system is definitely the best solution in all those buildings where no wires can be laid between the thermostat and the heating cooling room The thermostat transmitter issues some radio commands directed to the receiver unit DRP A83 M01 according to t...

Страница 2: ...lash a command has been received and the signal is strong the communication is reliable Two flashes a command has been received the signal is still sufficient but the communication might be corrupted by occasional disturbances Three flashes a command has been received from a transmitter in which is set an address different from the one memorized in the receiver and so the command has been ignored ...

Страница 3: ...se to the receiver in order to easy the address self learning procedure Step 3 After opening the case of the DRP A83 M01 wire it to the 230V power supply At the start up the led 1 will perform the sequence green red green red Step 4 Execute the self learning procedure by pressing the button 3 Fig 3 for one second until the led 1 turns on green Now the receiver waits for a command and as soon as it...

Страница 4: ...alarm status because its relevant transmitter does not work well or the signal is too weak Check the battery of the relevant transmitter See its documentation for more information When the transmitter is working in Test mode the receiver does not activate the relay The green side of the led 1 quickly flashes three times Signals issued by the transmitter are correctly received but the address set o...