TIC-4M MANUAL
11
Setting Menu
Setting menu Explanation
Category
Display
Set.value
Start value
Contents
Setting
Temp.
Min. ~
Max. Temp.
20.0℃
The ability to set the desired temperature when operating the controller.
Cooling
Deviation
0.1~9.9℃
2.0℃
Temperature variation in cooling operation and cooling point.
(Temperature of current climate setting tempe cooling deviation)
Set temperature : 20℃ for 20℃ at 2℃. If the current temperature is at 22℃, the
cooling output will be kept at the temperature of 22℃.
Stop cooling output at the current temperature of 20℃ or below.
Heating
Deviation
OFF /
0.1~9.9℃
OFF
The function of setting up the heater while operating the controller while
operating the controller.
OFF : Without auxiliary heater output.
Deviation setting : In each mode the current temperature is outputted to the set
temperature, if the temperature is lower than the heater deviation.
Setting menu Flow Chart
Run or stop display
Setting temperature
Deviation setting
Cooling deviation
Heating deviation
Change cooling deviation
Change Heating deviation
Change completed
Change completed
Change completed
Change setting temperature
Change Cancel
If you want to cancel the data change
In the menu, press the
MENU key
to
go to The previous menu.