AC-400R-3T-TH MANUAL
32
Alarm Contents
Alarm setting explanation
Status
Occur cause
Controller operating status at alarm
Drainage check
Auto return
It occurs when there is no change in the
current value even in drainage operation
in the electrode type humidifier.
Humidification operation is stopped. When the
alarm returns, the alarm is canceled and the
controller operates normally.
Over current
check
Auto return
It occurs when the current is about 1.4
times or more than the set current value
in the electrode type humidifier.
Humidification output is stopped and drainage
operation is activated. When the measured
current value is detected normally, the alarm is
canceled and the controller operates normally.
Water supply
check
Auto return
It occurs when the water level is not
checked even if the water output is more
than 20 minutes in the electrode or
heating type humidifier.
When the water level is checked, the alarm is
canceled and the controller operates normally.