General Setting
Backlight setting explanation
Item
Setting range Initial value
Contents
Backlight
ON / OFF /
1 ~ 360 sec
ON
This function sets the backlight ON time of the LCD screen of the monitor.
ON : The backlight of the monitor is always ON when the controller is stopped
or operating.
OFF : The backlight of the monitor is always OFF when the controller is stopped
or operating.
Language
Korean /
English
Korean
This function set the language to be displayed on the monitor.
Monitor
setting
Main /
Remote
Main
This function set the communication mode of monitor
Main : Mode used by connecting to the main monitor port (L1) of the main unit.
Remote : Mode used by connecting to the communication port (L3) of the main unit.
General setting description
Item
Setting range Initial value
Contents
Temp
setting
-20.0℃ ~
80.0℃
25.0℃
This function sets the desired temperature to control the room temperature.
Humidity
setting
0.0% ~
100%
50.0%
This function sets the desired humidity to control the room humidity.
Cooling
deviation
0.1℃ ~
5.0℃
1.0℃
Set the operation and stop point of each step in cooling operation by
the cooling deviation temperature for set temperature.
Cooling 1step operation run : Current temp. ≥ Set. temp. + Cooling deviation × 1
Cooling 2step operation run : Current temp. ≥ Set. temp. + Cooling deviation × 2
Heating
deviation
0.1℃ ~
5.0℃
1.0℃
Set the operation and stop point of each step in heating operation by the
heating deviation temperature for set temperature.
Heating 1step operation run : Current temp. ≤ Set. temp.
–
Heating deviation × 1
Heating 2setp operation run : Current temp. ≤ Set. temp.
–
Heating deviation × 2
Humidi-
fication
deviation
0.1% ~
9.9%
3.0%
Set the operation and stop point of each step in humidification operation
by the humidification deviation for set humidity.
Humidification 1step operation run : Current humi. ≤ Set. humi.
–
Humidification
deviation × 1
Humidification 2step operation run : Current humi. ≤ Set. humi.
–
Humidification
deviation × 2
Dehumi-
dification
deviation
0.1% ~
9.9%
3.0%
Set the operation and stop point of each step in dehumidification operation
by the dehumidification deviation for set humidity.
Dehumidification 1step operation run : Current humi.≥ Set. humi. + Dehumidification
deviation × 1
Dehumidification 2step operation run : Current humi.≥ Set. humi. + Dehumidification
deviation × 2