Transport and storage
Topvex SX is delivered in one piece standing on a pallet for easy transportation using a forklift. The unit
should be stored and transported in such a way that it is protected against physical damage that can harm
panels, handles, display etc. It should be covered so that dust, rain and snow cannot enter and damage
the unit and its components. The appliance is delivered complete with all necessary components, wrapped
in plastic on a pallet for easy transportation.
NB! Necessary parts like control panel, supply air sensor, handles, mounting feet, drainage pipe
with drain trap and electrical safety switch are placed loosely inside the unit. The unit must not be
put into operation before the enclosed parts are removed and installed properly.
Where/how to install
Topvex SX is meant for indoor installation placed on a
horizontal flat surface
. The unit can be leveled by
the use of mounting feet, which are delivered with the unit
(fig.4)
. It’s important that the unit is completely
leveled before it is put into operation.
Fig.4
Place the unit preferably in a separate room (e.g. storage room, laundry room, attic or similar). The
electronic components should not be exposed to lower temperature than 0°C or higher than +50°C.
When choosing the location it should be kept in mind that the unit requires maintenance regularly and that
the inspection doors should be easily accessible. Leave free space for opening the doors and for taking
out the main components (
fig. 3
).
Avoid placing the appliance against a wall, as low frequency noise can cause vibrations in the wall even if
the fan noise-level is acceptable. If this is not possible it is recommended to carefully insulate the wall.
The outdoor air intake of the building should if possible be put in the northern or eastern side of the
building and away from other exhaust outlets like kitchen fan- or laundry room outlets. The extract air
should ideally be led out via a roof cowl away from any outdoor air intakes, windows, balconies etc.
Safety notice
In order for the unit to be considered safely installed the doors if equipped with handles have
to be locked with a key to prevent unauthorized or accidental opening
All inlets and outlets have to be duct connected before starting the unit to prevent the
possibility to come in contact with moving parts.
Handle and hinges are removable. Inspection doors can be opened without handles by using a
16mm cap key