Topvex SX03, SX04, SX06 

 

Installation description 

 
205871  

 

Systemair AB 

10

External connections 

See

 

also the enclosed wiring diagram how to connect the electrical cables. 

 

Topvex SX03/SX04/SX06 EL 

Terminal block 

 

Description

 

Remark

 

PE 

Ground 

 

Earthed neutral (supply voltage) 

 

L1 L1 

Phase 

(supply 

voltage) 

 

L2 

L2 

Phase (supply voltage) 

400V 3~/230V 3~ 

L3 L3 

Phase 

(supply 

voltage) 

 

DO ref  Outdoor/Exhaust air damper 

 

DO1 

Outdoor/Exhaust air damper 

24V AC 
Max. 2,0 A continuous load 

*3 DI3 

Extended/Forced 

running 

*4 

DI ref 

Extended running/Fire alarm 

 

*5 DI5 

Fire 

alarm 

Supply voltage valve actuator, Cooling 

24V AC 

G0 

Supply voltage valve actuator, Cooling 

Neutral 

AO2 

Control signal cooling 

0-10V DC 

DO ref  Alarm signal reference 

 

10 

DO5 

Alarm output, for all alarms 

24V AC  
Max. 2,0 A continuous load 

11 

AI Ref  Sensor supply air reference 

 

12 

AI 1 

Sensor supply air 

 

* These inputs may only be wired to voltage free contacts. 

 
Topvex SX03 HW 

Terminal block 

 

Description

 

Remark 

 

PE Ground 

 

Earthed neutral (supply voltage) 

 

L1 

L1 

Phase (supply voltage) 

230V 1~ 

1  

DO ref  Outdoor/Exhaust air damper 

 

2  

DO1 

Outdoor/Exhaust air damper 

24V AC  
Max. 2,0 A continuous load 

*3 DI3 

Extended/Forced 

running 

*4 

DI ref 

Extended running / Fire alarm 

 

*5 DI5 

Fire 

alarm 

Supply voltage valve actuator, Cooling 

24V AC 

G0 

Supply voltage valve actuator, Cooling 

Neutral 

AO2 

Control signal Cooling 

0-10V DC 

DO ref  Alarm signal reference 

 

10 

DO5 

Alarm output, for all alarms 

24V AC  
Max. 2,0 A continuous load 

11 

AI Ref 

Sensor supply air reference 

 

12 

AI 1 

Sensor supply air 

 

13 

G0 

Supply voltage valve actuator, Heating 

Neutral 

14 

Supply voltage valve actuator, Heating 

24V AC 

15 

AO1 

Control signal  water heating 

0-10V DC 

* These inputs may only be wired to voltage free contacts. 
 
 
 
 
 

 
 

Содержание Topvex SX03 EL

Страница 1: ...Corrigo ver no 1 2 1 00 Topvex SX03 SX04 SX06 Compact Air Handling Unit Installation description GB GB...

Страница 2: ...f machinery Basic concepts general principles for design Part 1 Basic terminology methodology EN ISO 12100 2 Safety of machinery Basic concepts general principles for design Part 2 Technical principle...

Страница 3: ...ments Table of contents Declaration of Conformity 2 Introduction 3 Table of contents 3 Dimensions and weight 4 Topvex SX03 4 Topvex SX04 SX06 5 Component description Topvex SX 6 Transport and storage...

Страница 4: ..._______________________________________________________________ Topvex SX03 SX04 SX06 Installation description Original 205871 4 Systemair AB Dimensions and weight 62 375 470 106 1320 750 1600 43 43 1...

Страница 5: ...4 mm Topvex SX06 mm A 800 800 B 500 600 C 250 300 D 187 180 E 167 167 F 150 100 G 1041 1127 H 171 164 I 183 183 J 30 30 K 1747 2000 L 520 520 X 355 410 Y 212 204 Z 106 106 Topvex SX04 SX06 Topvex SX04...

Страница 6: ...9 10 11 12 3 4 5 6 11 10 8 13 Fig 3 Model M N mm Topvex SX03 500 630 Topvex SX04 500 698 Topvex SX06 550 824 Description 1 Connection supply air 2 Connection extract air 3 Connection outdoor air 4 Con...

Страница 7: ...into operation Fig 4 Place the unit preferably in a separate room e g storage room laundry room attic or similar The electronic components should not be exposed to lower temperature than 0 C or highe...

Страница 8: ...stalled in a non heated place the drain pipe and trap needs to be insulated well to prevent the water from freezing L 32 mm Fig 5 Fig 6 H mm Max negative pressure Pa 85 500 110 750 135 1000 Table 1 No...

Страница 9: ...t must not be put into operation before all the electrical safety precautions have been read and understood See fig 3 where to find the electrical connection box See page 10 and 11 and the enclosed wi...

Страница 10: ...reference 10 DO5 Alarm output for all alarms 24V AC Max 2 0 A continuous load 11 AI Ref Sensor supply air reference 12 AI 1 Sensor supply air These inputs may only be wired to voltage free contacts To...

Страница 11: ...he unit from factory The supply air sensor is enclosed in the package upon delivery Timer extended forced running When the unit is in shut down mode or running on low or medium speed it can be forced...

Страница 12: ...or B alarm Function sketch Accessories dashed components Designation Component description DO Damper outdoor air DEH Damper exhaust air WCB Water cooling battery WVA Water valve actuator Fig 7 The im...

Страница 13: ...et in the control panel The electric heating coil has both automatic and manual overheating protection The manual overheating protection which is controlled by the emergency thermostat is reset by pre...

Страница 14: ...mary circuit Fig 9 Control panel The SCP control panel is delivered with a 10m cable that is pre connected to the panel and with a fast coupling ISDN contact pre connected to the Topvex unit The ISDN...

Страница 15: ...n is at the root of the menu tree Pressing DOWN will move you through the menu choices at this the lowest level UP will move you back through the choices To enter a higher menu level use UP or DOWN to...

Страница 16: ...he right to make changes and improvements to the contents of this manual without prior notice Systemair AB Industriv gen 3 SE 739 30 Skinnskatteberg Sweden Phone 46 222 440 00 Fax 46 222 440 99 www sy...

Отзывы: