English

Fan High
Fan Med

Fan Low

Fan Stage

8 TControl EASY 3S

12. COMMISSIONING

 

²

By pressing the “   ” and “   ” key at the same time for more than 3 s, the units °C or °F can be 

selected. Temperature display range is 0..+50 °C or +32..+99 °F. Factory default is °C.

 

²

Select 2-pipe or 4-pipe systems (Parameter 8). In both modes the control sequences, Cooling – 

Ventilating – Heating can be selected.

 

²

 Using Parameter No.1. the temperature offset can be adjusted.  This feature should be used if the 

temperature at the mounting place of the Room Thermostat is not accurate compared to the average 

room temperature.

 

²

Key lock selection (Parameter 2), LCD backlight (Parameter 6) and set point ranges (Parameter 

4 and 5) can be parameterized. Under Fan operation “INDEPENDENT” (parameter 7) the fan runs 

permanently according to the selected or automatic selected fan stage; under Fan operation 

“DEPENDENT” the fan is tuned off (cyclically) when the valve is closed. If the valve is open, the fan 

will run according to the selected or automatic selected fan stage. When the fan stages are changed, 

the fan remains in a no-current switcheover pause (0.5 s).

13. HANDLING

 

²

By pressing “   ” or “   ” button the room temperature set point can be adjusted b16..+30 °C 

(+60..+86 °F). See also parameter 4 and 5.

 

²

If an external temperature sensor is used in 2-pipe system to measure the temperature in the pipes, 

no change of mode is possible via MODE button. The system recognizes automatically, whether 

current mode is cooling or heating. When temperature is <=19 °C cooling is active, when the 

temperature is >=30 °C heating is active. The other mode is not available. A time delay between 

cooling/heating mode changes is implemented to ensure safe operation and ensures eco-friendly 

operation.

 

²

If no external sensor is used, the functions (heating-ventilation-cooling) can be selected using MODE 

button. In heating mode the valve will be opened, if temperature is below set point, in cooling mode 

it will be opened, if the temperature is above set point.

 

²

When using a 4-pipe system no sensor is necessary. Both functions (heating and cooling) are 

available. The function can be selected via MODE button.

 

²

If the NTC room temperature sensor is out of range, thermostat will switch off the fan and close the 

valve, fault code “E01” will be shown.

14. FAN STAGE SELECTION

For cooling or heating modes

Low 

 Med 

 Hi 

 Auto

For ventilation mode

Low 

 Med 

 Hi

Auto mode:

Содержание TControl EASY 3S

Страница 1: ...Controller for Fan Coil Units Installation and maintenance manual TControl EASY 3S...

Страница 2: ......

Страница 3: ...INSTALLATION INSTRUCTION NOTICE D INSTALLATION INSTALLATIONSHANDBUCH ISTRUZIONI INSTALLAZIONE INSTRUCCIONES DE INSTALACI N English Fran ais Espa ol Deutsch Italiano...

Страница 4: ...IBILITY AND RESIDUAL RISKS 4 4 SECURITY ADVICE CAUTION 4 5 REMARKS TO ROOM SENSORS 5 6 SURFACE AND FLUSH MOUNTING 5 7 DIMENSIONS 5 8 MOUNTING 5 9 MAINTENANCE INSTRUCTIONS 6 10 TERMINAL CONNECTION PLAN...

Страница 5: ...EC fan motor if there is an ECOSPEED card 2 TECHNICAL DATA Measuring values temperature Output switch contact 5x contact NO 2x heating cooling 3x fan stages 250 V max load 3 A fan stages switchover p...

Страница 6: ...ion with any equipment that in case of a failure may threaten directly or indirectly human health or life or result in danger to human beings animals or assets Ensure all power is disconnected before...

Страница 7: ...E AND FLUSH MOUNTING The measuring result is influenced by the thermal characteristics of the wall A solid concrete wall responds to thermal fluctuations within a room in a much slower than a light we...

Страница 8: ...lation Heating On off key Mode key Fan speed key Valve open Fahrenheit Setting parameter Celsius 6 TControl EASY 3S 9 MAINTENANCE INSTRUCTIONS It is recommended to clean the touch surface with a damp...

Страница 9: ...ck on off 2 lock Mode 3 lock fan speed 4 lock temp setting 5 lock all the keystrokes 0 3 not used 4 Temp upper limit Range 1 50 C 30 C 5 Temp lower limit Range 1 50 C 16 C 6 LCD backlight 0 without ba...

Страница 10: ...tcheover pause 0 5 s 13 HANDLING By pressing or button the room temperature set point can be adjusted between 16 30 C 60 86 F See also parameter 4 and 5 If an external temperature sensor is used in 2...

Страница 11: ......

Страница 12: ...T CONTROL EASY 01 N 1GB As part of our ongoing product improvement programme our products are subject to change without prior notice Non contractual photos Systemair AC SAS Route de Verneuil 27570 Ti...

Отзывы: