Minimum speed cut off
10
Min. Uout = 3.5 V
Max. Uout = 10.0 V
20 °C
Setpoint
7 K
Pband
27 °C
06.05.2010
v_min_luft_abschalt_ctg.vsd
Uout
[V]
Actual Value
[°C]
5
H
Msco. = OFF
Msco. = -2.0 K
8 Start-up
8.1 Procedure
1. You must mount and connect the device in accordance with the operating instruc-
tions.
2. Double check that all connections are correct.
3. The supply voltage must match the information on the rating plate.
4. Set the operating Mode in the
BASE SETUP
(factory settings
2.01
).
5. When saving the Operating Mode, the factory settings are stored.
Therefore the settings you have made, e.g. in
“
SETTING
”
are lost.
Attention, electrostatic sensitive devices!
Be sure to ground the board at a suitable point in order to prevent damage to the
electronic components being caused by electrostatic discharges. Such damage
could occur, e.g., if a metal water pipe or heating line are brie
fl
y touched.
Operating Instructions
TCA 150D
Start-up
L-BAL-E119-GB 1318 Index 002
Part.-No. 00163357-GB
13/17