7

installation manual 

Main pipe (Please refer to Fig.4-5 and Fig.4-7)
        In  Fig.4-6,  the  main  pipe  L1,  the  outdoor  unit  capacity  is 
16kW,  and  check  the  Fig.4-7  to  get  the  size  of  gas  pipe/liquid 
pipe is 

Φ19.1/Φ9.5, and aslo the total equivalent length of liquid 

side  and  gas  side  pipes  is  >90m,then  check  the  Fig.4-4  to  get 
the size of gas pipe/liquid pipe is Φ22.2/Φ9.5, and according to 
the maximum value principle, it should apply the Φ22.2/Φ9.5. 

 Allowable length and altitude difference of refrigerant pipe

Maximum 
Piping(L)

Indoor Unit to Indoor Unit Drop Heihgt(H)

Equivalent Length

Actual Length

or L1+L3+L5+f(The second  connect method)

or L3+L5+f(The second connect method)

L1+L2+L3+L4+L5+f(The first connect method)

L2+L3+L4+L5+f(The first connect method)

DEFGH

Total Pipe Length(Actual)

Pi

p

e

 L

e

n

g

th

Pipe Length(from the first line branch
 pipe to furhtest indoor unit)(m)

Indoor Unit-Outdoor 
Unit Drop Height(H)

Outdoor Unit up

Outdoor Unit Down

Permitted value

ŏP

ŏPδN:θN:θN:θN:ε

ŏPδN:θN:θN:θN:ε

ŏP

ŏP

ŏP

ŏP

Piping

/////

+a+b+c+d+e+f

ŏP

D

ro

p

 H

EI

G

H

T

 b

e

tw

e

e

n

 i

n

d

o

o

u

n

it

 a

n

d

 u

u

td

o

o

u

n

it

The first cennect method

Indoor Unit

The First Line Branch Pipe

Outdoor unit

D

$

/

/

%

&

'

(

/

/

/

E

F

G

H

I

Fig.4-7

Note: When the total equivalent piping length of  gas side is ≥90m, it must increase the size of air side main pipe. Besides, according 
to the distance of refrigerant pipe and the over matched state of inner unit, when the capacity is decreasing it still can increase the gas side 
main pipe size.

ŏPδN:θN:ε

ŏPδN:θN:ε

Inner branch pipes are a~f, the size selection please refers to 
Table4-6. Note: The max. length of the branch pipe should not 
longer than 15m. 

Indoor unit branch pipe

The main pipes of indoor unit and the indoor unit branch pipe 
components

The downstream inner units of the main pipe L2 are N1, N2, and 
its total capacity is 28×2=56, the

 size of pipe L2 isΦ15.9/Φ9.5,

and the branch pipe B should be FQZHN-01C.  

The downstream inner units of the main pipe L4 are N3, N4, and 
its total capacity is 28×2=56, the size of pipe L4 isΦ15.9/Φ9.5,  
and the branch pipe D should be FQZHN-01C.  

The downstream inner units of the main pipe L5 are N5, N6, and  
its total capacity is 28+22=50, the size of pipe L5 isΦ15.9/Φ9.5, 
and the branch pipe E should be FQZHN-01C. 

The indoor unit below to the main pipe L3 are N3

̚

N6, and its to-

tal capacity is 28×3+22=106, the size of pipe L3 isΦ15.9/Φ9.5, 
and he branch pipe C should be FQZHN-01C.
The indoor unit below to the main pipe  A are N1

̚

N6, and its to-

tal capacity is 28×5+22=162, and the branch pipe should be 
FQZHN-01C, and because the total piping length of air side

is ≥90m, check Table.4-4, and the first branch pipe should apply 
FQZHN-02C, and according to the principle of maximum value, it 
should apply FQZHN-02C.

D

ro

p

 H

e

ig

h

t

Pipe Length(from the nearest branch
 pipe equivalent length(m)

Pipe length(From the nearest branch pipe equivalent length)

Maximum pipe equivalent length

(From the first line branch pipe) Maximum pipe equivalent length 

In

d

o

o

U

n

it

 t

o

 I

n

d

o

o

U

n

it

 D

ro

p

 H

e

ih

g

t

table 4-11

Содержание SYSVRF AIR EVO HP Mini

Страница 1: ...Outdoor unit Mini VRF Heat Pump INSTALLATION MANUAL GB SYSVRF AIR EVO HP Q R ...

Страница 2: ...intain the air conditioner Inappropriate installation may result in water leakage electric shock or fire Turn off the main power supply switch or breaker before attempting any electrical work Make sure all power switches are off Failure to do so may cause electric shock Connect the connecting cable correctly If the connecting cable is connected in a wrong way electric parts may be damaged When mov...

Страница 3: ...se copper pipe with 1 0 mm or more thickness for φ15 9 Use copper pipe with 1 0 mm or more thickness for φ19 0 Flare nut and flare works are also different form those of the conventional refrigerant take out the flare nut attached to the main unit of the air conditioner and use it Before installation Be careful to the following items before installation Air purge For air purge use a vacuum pump Do...

Страница 4: ...ion place Near a private power station or high Frequency equipment The insulation of the metal parts of the building and the air conditioner should comply with the regulation of National Electric Standard Install indoor unit outdoor unit power cord and connecting wire at least 1m away from TV set or radio to prevent noise or picture interference 3 2 Installation space Unit mm 300 600 300 2000 Wall...

Страница 5: ... the bends meet the following requirements 4 1 Refrigerant piping Fig 4 1 Large pipe Four condensed water outlets on the chassis for selection display as the follow figure Please pay attention to avoid the components while connect to the connecting pipes While installing the outdoor unit pay attention to the installation place and the drainage pattern if it s installed at the alpine zone the froze...

Страница 6: ...units Main pipe size mm Iiquid pipe Branch Pipe 4 1 4 1 R410A Indoor unit connecting pipes diameters 1 R410A Indoor unit connecting pipes diameters 4 3DŽ 2 Example 1 In the Fig 4 5 The downstream inner units of the L2 and its total capacity is 28 2 56ˈrefers to the Table 4 4 the air liquid side of L2 is Φ15 9 Φ9 5DŽ 1 1 1 1 1 1 D E F H I G The straight distance between copper pipe turning and the co...

Страница 7: ...door unit will be attenuated When capacity of indoor unit greater than or equal to the sum of 120 in order to ensure the effectiveness of machine and then try to open the indoor units at different time When the capacity of indoor unit is greater than or equal to 16 8kW the caliber of primary gas pipe should be augmented from Φ16 to Φ19 12 7 Flaring nut A 45 R410A A 56 6 4 Flaring nut 15 9 Flaring ...

Страница 8: ...e capacity is decreasing it still can increase the gas side main pipe size ŏ Pδ N θ N ε ŏ Pδ N θ N ε Inner branch pipes are a f the size selection please refers to Table4 6 Note The max length of the branch pipe should not longer than 15m Indoor unit branch pipe The main pipes of indoor unit and the indoor unit branch pipe components The downstream inner units of the main pipe L2 are N1 N2 and its...

Страница 9: ...frigerant Amount to be Added Using vacuum pump to do the vacuum never using refrigerant to expel the air Vacuuming should be done from both liquid side and gas side simultaneously Calculate the added refrigerant according to the diameter and the length of the liquid side pipe of the outdoor unit indoor unit connection NOTE Additional refrigerant volume of divergent pipe is 0 1kg per item Consider ...

Страница 10: ...or unit Indoor unit Indoor unit Signal wire between indoor units 1 3 4 1 4 3 1 1 4 3 4 3 Branch Box Branch Box CCM Branch Box Please use 3 core shielded wire and connect the shielded layer to Grounding Power Supply Power Supply CCM For 8 18kW Fig 5 3 Outdoor Unit Indoor Unit Power wiring indoor Communication Bus Power 220 240V 50Hz 1 Phase 208 230V 60Hz 1 Phase Power 220 240V 50Hz 1 Phase 208 230V...

Страница 11: ...on is indicated in broken line table users can select it when necessary CAUTION Indoor Outdoor Unit Signal Wire Connect the wire according to their numbers For 10 5 18kw Fig 5 4 Outdoor Unit Indoor Unit Power 220 240V 50Hz 1 Phase 220 240V 60Hz 1 Phase 208 230V 60Hz 1 Phase Power wiring indoor Communication Bus Indoor Unit Indoor Unit wire distribution box Switch Circuit breaker Switch Circuit bre...

Страница 12: ...work address of indoor units NOTE Single phase indoor unit Wire controller The reserved wire control function is indicated in broken line table users can purchase the wire controller when necessary In broken line table users can purchase the wire controller when necessary To wire controller Display board WHITE BLUE BLACK P Q X Y E YELLOW GRAY To Outdoor COMM BUS To Central Control Monitor CCM COMM...

Страница 13: ...ition 2 Calculate the indoor cubage B m as the minimum cubage 3 3 Calculate the refrigerant amount İ critical amount Counter measure against high amount 1 Install mechanical ventilator to keep the refrigerant amount under critical level ventilate regularly 2 Install leak alarm facility related to mechanical ventilator if you can not regularly ventilate b Leak alarm related to mechanical ventilator...

Страница 14: ...202000171943 MDV12I 013IW SYSVRF AIR EVO HP Q R_IM April 2014 ...

Отзывы: