background image

54

9.5.16 Setting parameters

The parameters related to this chapter are shown in the table below.

Order number

Code

State

Default

Minumum Maximum

Setting 

interval

Unit

1.1

DHW MODE

Enable or disable the DHW mode:0=NON,1=YES

1

0

1

1

/

1.2

DISINFECT

Enable or disable the disinfect mode:0=NON,1=YES

1

0

1

1

/

1.3

DHW PRIORITY

Enable or disable the DHW priority mode:0=NON,1=YES

1

0

1

1

/

1.4

DHW PUMP

Enable or disable the DHW pump mode:0=NON,1=YES

0

0

1

1

/

1.5

DHW PRIORITY TIME SET Enable or disable the DHW priority time set:0=NON,1=YES

0

0

1

1

/

1.6

dT5_ON

The temperature difference for starting the heat pump

10

1

30

1

1.7

dT1S5

The correct value to adjust the output of the compressor.

10

5

40

1

1.8

T4DHWMAX

The maximum ambient temperature that the heat pump
can operate at for domestic water heating

43

35

43

1

1.9

T4DHWMIN

The minimum ambient temperature that the heat pump can
operate for domestic water heating

-10

-25

5

1

1.10

t_INTERVAL_DHW

the start time interval of the compressor in DHW mode.

5

5

5

1

MIN

1.11

dT5_TBH_ OFF

the temperature difference between T5 and T5S that
turns the booster heater off.

5

0

10

1

1.12

T4_TBH_ON

the highest outdoor temperature the TBH can operate.

5

-5

20

1

1.13

t_TBH_DELAY

the time that the compressor has run before starting the
booster heater

30

0

240

5

MIN

1.14

T5S_DI

the target temperature of water in the domestic hot water
tank in the DISINFECT function.

65

60

70

1

1.15

t_DI_HIGHTEMP.

the time that the highest temperature of water in the
domestic hot water tank in the DISINFECT function will
last

15

5

60

5

MIN

1.16

t_DI_MAX

the maximum time that disinfection will last

210

90

300

5

MIN

1.17

t_DHWHP_RESTRICT

he operation time for the space heating/cooling operation.

30

10

600

5

MIN

1.18

t_DHWHP_MAX

the maximum continuous working period of the heat pump
in DHW PRIORITY mode.

90

10

600

5

MIN

1.20

PUMP RUNNING TIME

the certain time that the DHW pump will keep running for

5

5

120

1

MIN

1.19

DHW PUMP TIME RUN

Enable or disable the DHW pump run as timed and keeps
running for PUMP RUNNING TIME:0=NON,1=YES

1

0

1

1

/

1.21

DHW PUMP DISINFECT

Enable or disable the DHW pump operate when the unit is
in disinfect mode and T5

T5S_DI-2:0=NON,1=YES

1

0

1

1

/

2.1

COOL MODE

Enable or disable the cooling mode:0=NON,1=YES

1

0

1

1

/

2.2

t_T4_FRESH_C

The refresh time of climate related curves for cooling
mode

0.5

0.5

6

0.5

hours

2.3

T4CMAX

The highest ambient operation temperature for cooling
mode

52

35

52

1

2.4

T4CMIN

the lowest ambient operating temperature for cooling
mode

10

-5

25

1

2.5

dT1SC

the temperature difference for starting the heat pump(T1)

5

2

10

1

2.6

dTSC

the temperature difference for starting the heat pump(Ta)

2

1

10

1

2.7

t_INTERVAL_COOL

 the start time interval of the compressor in COOL mode.

5

5

5

1

MIN

2.8

T1SetC1

The setting temperature 1 of climate related curves for
cooling mode.

10

5

25

1

2.9

T1SetC2

The setting temperature 2 of climate related curves for
cooling mode.

16

5

25

1

2.10

T4C1

The ambient temperature 1 of climate related curves for
cooling mode.

35

-5

46

1

2.11

T4C2

The ambient temperature 2 of climate related curves for
cooling mode.

25

-5

46

1

2.12

ZONE1 C-EMISSION

The type of zone1 end for cooling mode

0=FCU(fan coil

unit)

1=RAD.(radiator)

2=FLH(floor heating)

0

0

2

1

/

2.13

ZONE2 C-EMISSION

The type of zone2 end for cooling mode

0=FCU(fan coil

unit)

1=RAD.(radiator)

2=FLH(floor heating)

0

0

2

1

/

Содержание SYSHP MINI SPLIT

Страница 1: ...tions Thank you very much for purchasing our product Before use please carefully read this manual and keep it for future reference SYSHP MINI SPLIT 06 16 R32 Split Heat Pump Indoor unit Installation and owner s manual ...

Страница 2: ...8 2 8 3 8 4 8 5 8 6 8 7 8 8 Dimensions Installation requirements Servicing space requirements Mounting the indoor unit Refrigerant pipe connection 4 1 4 2 4 3 4 4 4 5 4 SAFETY PRECAUTIONS INSTALLATION SITE BEFORE INSTALLATION INSTALLATION PRECAUTIONS TYPICAL APPLICATIONS OVERVIEW OF THE UNIT START UP AND CONFIGURATION TEST RUN AND FINAL CHECKS 30 30 08 12 13 5 GENERAL INTRODUCTION 14 6 ACCESSORIES...

Страница 3: ... 13 58 58 12 60 62 General guidelines General symptoms Operation parameter Error codes 12 1 12 2 12 3 12 4 MAINTENANCE AND SERVICE TROUBLE SHOOTING TECHNICAL SPECIFICATIONS 67 14 INFORMATION SERVICING 65 58 ...

Страница 4: ...13 3 4 6 20 14 15 17 19 16 21 6 8 9 10 5 4 3 2 1 CN4 CN22 CN5 S3 DIS1 CN24 CN1 CN2 CN6 CN8 CN13 CN15 CN16 CN18 CN28 S2 CN42 CN21 S1 S4 CN11 CN7 CN17 CN19 CN30 CN35 CN14 CN31 CN36 CN25 CN29 CN40 CN41 CL COM HT EVU SG 30 29 32 25 26 27 28 31 7 12 11 10 9 18 8 7 5 23 22 24 1 2 13 3 4 6 20 14 15 17 19 16 21 6 8 9 10 5 4 3 2 1 CN4 CN22 CN5 S3 DIS1 CN24 CN1 CN2 CN6 CN8 CN13 CN15 CN16 CN18 CN28 S2 CN42 C...

Страница 5: ...quate personal protection equipment such as gloves and safety glasses while installing the unit or carrying out maintenance activities 1 SAFETY PRECAUTIONS The precautions listed here are divided into the following types They are quite important so be sure to follow them carefully Read these instructions carefully before installation Keep this manual in a handy for future preference Meanings of DA...

Страница 6: ...damage Installation of pipework shall be kept to a minimum length NOTE If the total refrigerant charge in the system is 1 84 kg i e if the piping length is 20m for 8 10kW there are no additional minimum floor area requiements If the total refrigerant charge in the system is 1 84 kg i e if the piping length is 20m for 8 10kW you need to comply with additional minimum floor area requirements as desc...

Страница 7: ...ur dealer yes no yes no Unit can be installed at room A if 2 ventilation openings permanently open are provided between room A and B 1 at the top and 1 at the bottom Bottom opening The bottom opening must meet the minimum area requirements VAmin It must be as close as possible to the floor If the ventilation opening starts from the floor the height must be 20mm The bottom of the opening must be si...

Страница 8: ...se GG2 For intermediate mc values i e when mc is between two values from the table consider the value that corresponds to the higher mc value from the table If mc 1 87kg consider the value that corresponds to mc 1 87kg Systems with total refrigerant charge lower than 1 84kg are not subjected to any room requirements NOTE Table 3 Minimum venting opening area for natural ventilation indoor unit 2 22...

Страница 9: ...rcuit or improper electrical construction may lead to electric shocks or fire Be sure to install a ground fault circuit interrupter according to local laws and regulations Failure to install a ground fault circuit interrupter may cause electric shocks and fire Make sure all wiring is secure Use the specified wires and ensure that terminal connections or wires are protected from water and other adv...

Страница 10: ...such as in factories In vehicles or vessels Where acidic or alkaline vapors are present This appliance can be used by children 8 years old and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they are supervised or given instruction on using the unit in a safe manner and understand the hazards involved Children should not play with the u...

Страница 11: ...on equipment must be added in accordance with the standard EN378 Be sure to adopt adequate measures to prevent the unit from being used as a shelter by small animals Small animals making contact with electrical parts can cause malfunction smoke or fire Please instruct the customer to keep the area around the unit clean WARNING Select an installation site where the following conditions are satisfie...

Страница 12: ...pping condensate will not result in damage of your furniture and other devices CAUTION The installation surface is a flat and vertical non combustible wall capable of supporting the operation weight of the unit All piping lengths and distance have been taken into consideration Requirement Maximum allowable piping length between the 3 way valve SV1 and the indoor unit only for installations with do...

Страница 13: ...sible to the final installation position in its original package in order to prevent damage The indoor unit weight is approximately 50kg and should be lifted by two persons Dimensions of the wall bracket NO 1 2 3 4 5 NAME Refrigerant gas connection5 8 14UNF Refrigerant liquid connection 1 4 60 or 3 8 100 160 14UNF Drainage 25 Water Inlet R1 Water Outlet R1 Refrigerant gas connection 5 8 14UNF Dime...

Страница 14: ...t the unit WARNING Fig 4 3 unit mm 30 29 32 25 26 27 28 31 7 12 11 10 9 18 8 7 5 23 22 24 1 2 13 3 4 6 20 14 15 17 19 16 21 6 8 9 10 5 4 3 2 1 CN4 CN22 CN5 S3 DIS1 CN24 CN1 CN2 CN6 CN8 CN13 CN15 CN16 CN18 CN28 S2 CN42 CN21 S1 S4 CN11 CN7 CN17 CN19 CN30 CN35 CN14 CN31 CN36 CN25 CN29 CN40 CN41 CL COM HT EVU SG ...

Страница 15: ...ntly tighten the flare nut with fingers and then tighten it with a spanner and torque wrench The protective nut is a one time part it can not be reused In case it is removed it should be replaced with a new one Protective nut Indoor unit tubing Flare nut Pipings Outer diam Tightening torque N cm Additional tightening torque N cm 6 35 16 9 52 1500 153kgf cm 1600 163kgf cm 2500 255kgf cm 2600 265kgf...

Страница 16: ...t for domestic hot water tank field supply An optional solar kit can be connected to the unit Operation range Temperature probe T5 Coil Outlet Tank booster heater TBH Inlet 5 GENERAL INTRODUCTION These units are used for both heating and cooling applications and domestic hot water tanks They can be combined with fan coil units floor heating applications low temperature high efficiency radiators do...

Страница 17: ...with possible limitation and protection In heating mode the water flowing temperature TW_out range in different outdoor temperature T4 is listed below In DHW mode the water flowing temperature TW_out range in different outdoor temperature T4 is listed below Operation manual Wire controller 1 1 1 Thermistor and extension wire for Tbt1 Tw2 Tsolar can be shared if these functions are needed at the sa...

Страница 18: ...ce tank Field supply 14 3 Coil 2 heat exchanger for Solar energy 5 1 Automatic air purge valve 15 Filter Accessory 5 2 Drainage valve 16 Check valve Field supply 5 3 Tbt1 Balance tank upper temperature sensor Optional 17 Shut off valve Field supply 18 Filling valve Field supply 19 Drainage valve Field supply 20 Tap water inlet pipe Field supply 21 Hot water tap Field supply 23 Collector distributo...

Страница 19: ...ion is invalid in DHW mode TBH tank booster heater control The TBH function is set on the user interface See 9 1 DIP switch settings overview 1 When the TBH is set to be valid TBH can be turned on via TANK HEATER function on the user interface In DHW mode TBH will be turned on automatically when the initial domestic water temperature T5 is too low or the target domestic water temperature is too hi...

Страница 20: ...pply 5 1 Automatic air purge valve 25 Thermostat transfer board Optional 5 2 Drainage valve RT 1 7 Low voltage room thermostat Field supply 6 P_o Outside circulation pump Field supply RT8 High voltage room thermostat Field supply 13 Expansion vessel Field supply FHL 1 n Floor heating loop Field supply 15 Filter Accessory Space heating One zone control the unit ON OFF is controlled by the room ther...

Страница 21: ...d supply 15 Filter Accessory FCU 1 n Fan coil unit Field supply Cooling or heating mode is set via the room thermostat water temperature is set on the user interface 1 When any CL of all the thermostats close system will be set at cooling mode 2 When any HL of all the thermostats close and all CL open system will be set at heating mode Space heating The circulation pumps operation 1 When the syste...

Страница 22: ...or unit 15 Filter Accessory 2 Indoor unit 17 Shut off valve Field supply 3 User interface 18 Filling valve Field supply 5 Balance tank Field supply 19 Drainage valve Field supply 5 1 Automatic air purge valve 23 Collector distributor Field supply 5 2 Drainage valve 25 Thermostat transfer board Optional 6 P_o zone 1 circulation pump Field supply RT 1 7 Low voltage room thermostat Field supply 8 Mix...

Страница 23: ...ectly please refer to 8 8 6 2 2 Thermostat wires to the correct terminals and to configure the ROOM THERMOSTAT in the wired controller correctly Wiring of the room thermostat should follow method A B C as described in 8 8 6 Connection for other components 6 For room thermostat CAUTION NOTE 1 Zone 2 can only operate in heating mode When cooling mode is set on user interface and zone 1 is OFF CL in ...

Страница 24: ... 2 screws and unhitching the cover Make sure to fix the cover with the screws and nylon washers when installing the cover screws are delivered as accessory Parts inside the unit can be hot CAUTION Switch off all power supply i e outdoor unit power supply indoor unit power supply electric heater and additional heater power supply before removing the control box service panel CAUTION F 14 1 5 3 5 4 ...

Страница 25: ...n then when the water flow reach 0 66 m3 h the flow switch close The pump circulates the water in the water circuit Heat exchanging between water and refrigerant 13 14 15 Manometer Electrical heating belt 14 1 14 2 Internal backup heater They are for preventing frozen 14 2 is optional The backup heater consists of an electrical heating element that will provide additional heating capacity to the w...

Страница 26: ... S1 S4 CN11 CN7 CN17 CN19 CN30 CN35 CN14 CN31 CN36 CN25 CN29 CN40 CN41 CL COM HT EVU SG CN32 SW9 30 29 32 25 26 27 28 31 7 12 11 10 9 18 8 7 5 23 22 24 1 2 13 3 4 6 20 14 15 17 19 16 21 6 8 9 10 5 4 3 2 1 CN4 CN22 CN5 S3 DIS1 CN24 CN1 CN2 CN6 CN8 CN13 CN15 CN16 CN18 CN28 S2 CN42 CN21 S1 S4 CN11 CN7 CN17 CN19 CN30 CN35 CN14 CN31 CN36 CN25 CN29 CN40 CN41 CL COM HT EVU SG CN32 SW9 The picture is only...

Страница 27: ...f balance tank 12 Port for lower temp sensor of balance tank 13 Port for domestic hot water tank temp sensor 14 Port for zone 2 temp sensor of outlet water Port for solar panel temp sensor Port for variable speed pump communication Control port for room thermostat heating mode Power port for room thermostat Control port for room thermostat cooling mode 18 Port for smart grid photovoltaic signal Po...

Страница 28: ...house gases are contained in hermetically sealed equipment An electrical switchgear has a tested leakage rate of less than 0 1 per year as set out in the technical specification of the manufacturer 8 5 Water piping All piping lengths and distances have been taken into consideration Refer to Table 3 1 NOTE If no glycol is in the system in case of a power supply failure or pump operating failure dra...

Страница 29: ...2 2 1 2 2 2 4 2 9 2 3 2 5 2 6 6 5 5 2 5 1 13 17 15 17 2 7 2 8 2 10 18 19 FHL1 FHL2 FHLn 23 Modbus 24 Indoor Outdoor 1 1 2 Assembly unit Assembly unit Code Code 13 FHL 1 n 15 17 18 19 3 Outdoor unit Indoor unit Filter accessory Balance tank field supply 5 User interface accessory Expansion vessel field supply Shut off valve field supply Filling valve field supply Drainage valve field supply Bypass valv...

Страница 30: ...an expansion vessel of 8L that has a default pre pressure of 1 5 bar To assure proper operation of the unit the pre pressure of the expansion vessel might need to be adjusted 1 Check that the total water volume in the installation excluding the internal water volume of the unit is at least 40L See 13 Technical specifications to find the total internal water volume of the unit The expansion vessel ...

Страница 31: ... withstand the pressures and temperatures of the system When using non copper metallic piping be sure to insulate two kind of materials from each other to prevent galvanic corrosion If air moisture or dust gets in the water circuit problems may occur Therefore always take into account the following when connecting the water circuit As copper is a soft material use appropriate tools for connecting ...

Страница 32: ...he unit might drain off too much water through the pressure relief valve Water quality should be complied with EN 98 83 EC Directives Detailed water quality condition can be found in EN 98 83 EC Directives Connect the water supply to the filling valves and open the valve Make sure all the automatic air purge valves are open at least 2 turns Filling with water until the manometer indicates a pressu...

Страница 33: ... due to high frequency waves Never install a phase advancing capacitor as it could lead to an accident The illustration below gives an overview of the required field wiring between several parts of the installation Refer also to 7 Typical application Secure the electrical wiring with cable ties as shown in figure so that it does not come in contact with the piping particularly on the high pressure...

Страница 34: ...Code I J K L M Contactor Power supply Indoor unit Booster heater SV1 3 way valve for domestic hot water tank field supply SV2 3 way valve field supply P_d DHW pump field supply E C A K K K K J G F I E L L 9 B CN11 CN7 CN30 1 A 2 B 3 X 4 Y 5 E 6 P 7 Q 8 E 9 H1 10 H2 25 HT 29 N 30 R1 31 DFT1 32 DFT2 26 R2 27 AHS1 28 AHS2 1 SL1 2 SL2 3 C 4 TBH 5 N 6 1ON 7 1OFF 8 P_o 9 N 10 11 N 12 24 3OFF 23 N 21 N 2...

Страница 35: ... power supply and backup heater and domestic hot water tank power supply if applicable before removing the switch box service panel WARNING Field wiring guidelines Most field wiring on the unit is to be made on the terminal block inside the switch box To gain access to the terminal block remove the switch box service panel 8 8 3 Precautions on wiring of power supply Fix all cables using cable ties...

Страница 36: ... wire diameters minimum value individually for each unit based on the table below Stated values are maximum values see electrical data for exact values 8 8 5 Specifications of standard wiring components Equipment main Power Supply Wiring INDOOR UNIT POWER SUPPLY L N LPS XT1 Hz Voltage V Min V Max V MCA A MFA A kW FLA A 60 100 160 60 3kW heater 100 3kW heater 160 3kW heater 60 9kW heater 100 9kW he...

Страница 37: ... backup heater is as option 3 for 9kW backup heater If 3kW or 6kW backup heater is needed please ask professional installer to change the Dip switwch S1 to option 1 for 3kW backup heater or option 2 for 6kW backup heater refer to 9 2 1 FUNCTION SETTING NOTE 1 2 3 4 S1 ON OFF 1 2 3 4 S1 ON OFF 1 2 3 4 S1 ON OFF Option 1 Option 2 Option 3 Mode selection of 3 phase 3 6 9KW backup heater Unit Wiring s...

Страница 38: ...oster heater Internal backup heater 1 SV3 3 way valve Outside circulation pump zone1 pump Pumpc zone2 pump CN11 SV2 3 way valve SV1 3 way valve 11 DHW pipe pump 23 N SV1 3 way valve SV1 3 way valve Solar energy pump 20 3OFF 1 SL1 2 SL2 3 H 4 C 5 6 1ON 7 1OFF 8 9 10 11 12 24 23 N 21 N 20 IBH1 19 18 13 14 L1 15 16 17 N 22 25 HT 29 30 31 DFT2 32 DFT1 26 R2 27 AHS1 28 AHS2 1 A 2 B 3 X 4 Y 5 E 6 P 7 Q ...

Страница 39: ...nt A Wiring size mm2 220 240VAC 0 2 0 75 ATCO TCO 1 2 3 4 5 6 7 8 9 10 11 12 24 23 21 20 19 18 13 1415 16 17 CN11 22 30 26 1 2 3 4 5 6 7 8 9 10 CN30 CN7 Type 1 Running Type 2 7 5 3 1 A1 A2 2 4 6 8 Power supply Contactor TBH 13 16 CN11 25 26 1 2 3 4 5 6 7 8 9 10 CN30 CN7 27 29 30 31 32 28 1 2 CN11 25 26 1 2 3 4 5 6 7 8 9 10 CN30 CN7 27 28 29 30 31 32 2 For 3 way value SV1 SV2 and SV3 SV1 5 6 16 5 6...

Страница 40: ... Power supply 7 5 3 1 A1 A2 2 4 6 8 19 2018 SV3 20 19 18 CN11 25 26 1 2 3 4 5 6 7 8 9 10 CN7 CN30 27 28 29 30 31 32 CN11 25 26 1 2 3 4 5 6 7 8 9 10 CN7 CN30 27 28 29 30 31 32 9 21 CN11 25 26 1 2 3 4 5 6 7 8 9 10 CN7 CN30 27 28 29 30 31 32 12 24 30 29 32 25 26 27 28 31 7 12 11 10 9 18 8 7 5 23 22 24 1 2 13 3 4 6 20 14 15 17 19 16 21 6 8 9 10 5 4 3 2 1 CN4 CN22 CN5 S3 DIS1 CN24 CN1 CN2 CN6 CN8 CN13 ...

Страница 41: ...roller for 4 pipe FCU When the indoor unit is connected with the external temperature controller user interface FOR SERVICEMAN set ROOM THERMOSTAT to MODE SET A 1 When unit detect voltage is 230VAC between C and L1 the unit operates in the cooling mode A 2 When unit detect voltage is 230VAC between H and L1 the unit operates in the heating mode A 3 When unit detect voltage is 0VAC for both side C ...

Страница 42: ...in the cooling mode A 2 When unit detect voltage is 12VDC between HT and COM the unit operates in the heating mode A 3 When unit detect voltage is 0VDC for both side CL COM HT COM the unit stop working for space heating or cooling A 4 When unit detect voltage is 12VDC for both side CL COM HT COM the unit working in cooling mode Method B RT provide the switch signal to unit User interface FOR SERVI...

Страница 43: ...icture Fix the cable with cable ties to the cable tie mountings to ensure stress relief C 2 When unit detect voltage is 12VDC between CL and COM zone2 turn on according to climate temp curve When unit detect voltage is 0V between CL and COM zone2 turn off C 3 When HT COM and CL COM are detected as 0VDC unit turn off C 4 when HT COM and CL COM are detected as 12VDC both zone1 and zone2 turn on The ...

Страница 44: ... 2 0 75 10 For outside circulation pump P_o KM2 Power supply 7 5 3 1 A1 A2 2 4 6 8 CN11 25 26 1 2 3 4 5 6 7 8 9 10 CN7 CN30 27 28 29 30 31 32 10 22 KM5 Power supply 7 5 3 1 A1 A2 2 4 6 8 ATCO TCO CN11 25 26 1 2 3 4 5 6 7 8 9 10 CN7 CN30 27 28 29 30 31 32 14 17 12 For smart grid The unit has smart grid function there are two ports on PCB to connect SG signal and EVU signal as following SMART GRID 3...

Страница 45: ...hanged to 70 automatically and the TBH operate as below T5 69 the TBH is on T5 70 the TBH is off The unit operate in cooling heating mode as the normal logic 2 When EVU signal is off and SG signal is on the unit operate normally 3 When EVU signal is off SG signal is off the DHW mode is off and the TBH is invalid disinfect function is invalid The max running time for cooling heating is SG RUNNIN TI...

Страница 46: ...s or the locally installed protection devices are of the size and type specified in 13 Technical specifications Make sure that no fuses or protection devices have been bypassed Backup heater circuit breaker Do not forget to turn on the backup heater circuit breaker in the switchbox it depends on the backup heater type Refer to the wiring diagram Booster heater circuit breaker Do not forget to turn...

Страница 47: ...e indoor unit can provide the head and flow Available external static pressure VS Flow rate 0 10 20 30 40 50 60 70 80 90 0 3 0 6 0 9 1 2 1 5 1 8 2 1 2 4 2 7 3 0 ESP KPa Q m3 h Available external static pressure VS Flow rate Indoor unit 160 0 10 20 30 40 50 60 70 80 90 0 3 0 7 1 1 1 5 1 9 2 3 2 7 3 1 ESP KPa Q m3 h Indoor unit 60 100 CAUTION If the valves are at the incorrect position the circulati...

Страница 48: ... causes can be found in 12 4 Error codes The unit should be configured to match the installation environment outdoor climate installed options etc and user demand A number of field settings are available These settings are accessible and programmable through FOR SERVICEMAN in user interface 9 5 Field settings Procedure To change one or more field settings proceed as follows Temperature values disp...

Страница 49: ... 1 3 7 OTHER HEATING SOURCE 8 HOLIDAY AWAY MODE SETTING 9 SERVICE CALL SETTING 10 RESTORE FACTORY SETTINGS 11 TEST RUN 12 SPECIAL FUNCTION OK ENTER FOR SERVICEMAN DHW domestic hot water Go to MENU FOR SERVICEMAN 1 DHW MODE SETTING Press OK The following pages will be displayed 9 5 1 DHW MODE SETTING 1 DHW MODE SETTING YES YES YES YES NON ADJUST 1 1 DHW MODE 1 2 DISINFECT 1 3 DHW PRIORITY 1 4 DHW P...

Страница 50: ...dT1SC ADJUST 2 C 5MIN 10 C 16 C 35 C 2 3 2 COOL MODE SETTING 2 6 dTSC 2 7 t_INTERVAL_C 2 8 T1SetC1 2 9 T1SetC2 2 10 T4C1 ADJUST 16 C 15 C 5 C 2 0HRS YES 3 HEAT MODE SETTING 3 1 HEAT MODE 3 2 t_T4_FRESH_H 3 3 T4HMAX 3 4 T4HMIN 3 5 dT1SH 9 5 4 AUTO MODE SETTING Go to MENU FOR SERVICEMAN 4 AUTO MODE SETTING Press OK the following page will be displayed 25 C FCU FLH 3 3 2 COOL MODE SETTING 2 11 T4C2 2...

Страница 51: ...S The following pages will be displayed NON NON YES 5 TEMP TYPE SETTING 5 1 WATER FLOW TEMP 5 2 ROOM TEMP 5 3 DOUBLE ZONE ADJUST If you set WATER FLOW TEMP and ROOM TEMP to YES meanwhile set DOUBLE ZONE to NON or YES the following pages will be displayed only WATER FLOW TEMP YES only ROOM TEMP YES Homepage zone 1 2 Addition page zone 2 Double zone is effective If you set DOUBLE ZONE to YES and set...

Страница 52: ... you set DOUBLE ZONE and ROOM TEMP to YES meanwhile set WATER FLOW TEMP to YES or NON the following page will be displayed Homepage zone 1 2 Addition page zone 2 Double zone is effective In this case the setting value of zone 1 is T1S the setting value of zone 2 is T1S2 The corresponding TIS2 is calculated according to the climate related curves In this case the setting value of zone 1 is T1S the ...

Страница 53: ...S 11 TEST RUN Active the settings and active the TEST RUN OK CONFIRM NO YES Please wait 5 10 RESTORE FACTORY SETTINGS If POINT CHECK is selected the following pages will be displayed Press to scroll to the components you want to check and press ON OFF For example when 3 way valve is selected and ON OFF is pressed if the 3 way valve is open close then the operation of 3 way valve is normal and so a...

Страница 54: ...he following page will be displayed During HEAT MODE test running the default target outlet water temperature is 35 C The IBH internal backup heater will turn on after the compressor runs for 10 min After the IBH runs for 3 minutes the IBH will turn off the heat pump will operate until the water temperature increase to a certain value or the next command is received When the DHW MODE RUNNING is se...

Страница 55: ...elected after press OK the following page will be displayed 12 1 PREHEATING FOR FLOOR 30 C 72 HOURS ADJUST T1S t_fristFH ENTER EXIT Use to scroll the cursor to YES and press OK the preheating for floor will turn off The operation of the unit during preheating for floor described in the picture below During preheating for floor all the buttons except OK are invalid If you want to turn off the prehe...

Страница 56: ... 15 4 Tbt1 15 5 Tbt2 12 3 FLOOR DRYING UP The unit will operate floor drying up on 09 00 01 08 2018 OK CONFIRM The AUTO RESTART function is used to select whether the unit reapplies the user interface settings at the time when power returns after a power supply failure 9 5 13 AUTO RESTART During floor drying all the buttons except OK are invalid When the heat pump malfunctions the floor drying mod...

Страница 57: ... time that disinfection will last 210 90 300 5 MIN 1 17 t_DHWHP_RESTRICT he operation time for the space heating cooling operation 30 10 600 5 MIN 1 18 t_DHWHP_MAX the maximum continuous working period of the heat pump in DHW PRIORITY mode 90 10 600 5 MIN 1 20 PUMPRUNNING TIME the certain time that the DHW pump will keep running for 5 5 120 1 MIN 1 19 DHW PUMPTIMERUN Enable or disable the DHW pump...

Страница 58: ...FLOW TEMP 0 NON 1 YES 1 0 1 1 5 2 ROOMTEMP Enable or disable the ROOMTEMP 0 NON 1 YES 0 0 1 1 5 3 DOUBLEZONE Enable or disable the ROOMTHERMOSTAT DOUBLE ZONE 0 NON 1 YES 0 0 1 1 7 1 dT1_IBH_ON The temperature difference betw een T1S and T1 for starting the backup heater 5 2 10 1 7 2 t_IBH_DELAY The time that the compressor has run before the first backup heater turns on 30 15 120 5 MIN 7 3 T4_IBH_...

Страница 59: ...N OFF M1 M2 Define the function of the M1M2 sw itch 0 REMOTE ON OFF 1 TBH ON OFF 2 AHS ON OFF 0 0 2 1 15 2 SMART GRID Enable or disable the SMART GRID 0 NON 1 YES 0 0 1 1 15 3 T1b Tw 2 Enable or disable the T1b Tw 2 0 NON 1 YES 0 0 1 1 15 4 Tbt1 Enable or disable the Tbt1 0 NON 1 YES 0 0 1 1 15 5 Tbt2 Enable or disable the Tbt2 0 NON 1 YES 0 0 1 1 15 6 Ta Enable or disable the Ta 0 NON 1 YES 0 0 1...

Страница 60: ...is done in accordance with relevant local laws and regulations Water pressure Check the water pressure if it is below 1 bar fill water to the system Water filter Clean the water filter Water pressure relief valve Check for correct operation of the pressure relief valve by turning the black knob on the valve counter clockWise If you do not hear a clacking sound contact your local dealer In case the...

Страница 61: ...d on but the compressor is not starting space heating or domestic water heating POSSIBLE CAUSES CORRECTIVE ACTION The unit maybe operate out of its operation range the water temperature is too low In case of low water temperature the system utilizes the backup heater to reach the minimum water temperature first 12 C Check that the backup heater power supply is correct Check that the backup heater ...

Страница 62: ...eps running out of the unit close both the water inlet and outlet shut off valves first and then contact your local dealer POSSIBLE CAUSES CORRECTIVE ACTION Backup heater operation is not activated Too much heat pump capacity is used for heating domestic hot water applies only to installations with a domestic hot water tank Check that the t_DHWHP_MAX and t_DHWHP_RESTRICT are configured appropriate...

Страница 63: ...y in DHW mode POSSIBLE CAUSES CORRECTIVE ACTION Surface of coil in the tank not large enough The same solution for Symptom 7 TBH or AHS not available Heat pump will stay in DHW mode untill t_DHWHP_MAX reached or setpoint is reached Add TBH or AHS for DHW mode TBH and AHS should be controlled by the unit 12 3 Operation parameter This menu is for installer or service engineer reviewing the operation...

Страница 64: ...of deviation is 25 NOTE OPERATION PARAMETER 00 IDU TARGET FREQUENCY 46Hz ADDRESS FREQUENCY LIMITED TYPE 5 FAN SPEED 600R MIN SUPPLY VOLTAGE 230V DC GENERATRIX VOLTAGE 420V DC GENERATRIX CURRENT 18A 7 9 OPERATION PARAMETER 00 TW_I PLATE W INLET TEMP 30 C ADDRESS T2 PLATE F OUT TEMP 35 C TW_O PLATE W OUTLET TEMP 35 C T2B PLATE F IN TEMP 35 C Th COMP SUCTION TEMP 5 C Tp COMP DISCHARGE TEMP 75 C 8 9 O...

Страница 65: ...ult 1 Check the resistance of the sensor 2 The T5 sensor connector is loosen Reconnect it 3 The T5 sensor connector is wet or there is water in remove the water make the connector dry Add waterproof adhesive 4 The T5 sensor failure change a new sensor 5 If you want to close the domestic water heating when T5 sensor do not connected to the system then T5 sensor can not be detected refer to 9 5 1 DH...

Страница 66: ... indoor unit PCB Room temp sensor Ta fault 1 Check the resistance of the sensor 2 The T2 sensor connector is loosen Re connect it 3 The T2 sensor connector is wet or there is water in remove the water make the connector dry Add waterproof adhesive 4 The T2 sensor failure change a new sensor Refrigerant liquid temp sensor T2 fault 1 Check the resistance of the sensor 2 The T2B sensor connector is l...

Страница 67: ...s wet or there is water in remove the water make the connector dry Add waterproof adhesive 4 The Tsolar sensor failure change a new sensor Buffer tank low temp sensor Tbt2 fault Communication error between main board and thermostat transferboard RT Ta PCB is set to be valid on user interface but the thermostat transfer board is not connected or the communication between thermostat transfer board a...

Страница 68: ...l Volume Max operating pressure Pre charge pressure Weight Net weight 37kg 37kg 39kg Gross weight 43kg 43kg 45kg Refrigerant gas liquid side Φ15 9 Φ6 35 Φ15 9 Φ9 52 Φ15 9 Φ9 52 Water inlet outlet Drain connection Operation range Outlet water heating model Outlet water cooling model Domestic hot water Ambient temperature Water pressure 6L min 220 240V 50Hz Refer to the technical data 420x790x270 52...

Страница 69: ...r input Volume Max operating pressure Pre charge pressure Net weight 43kg 43kg 45kg 43kg 43kg 45kg Gross weight 49kg 49kg 51kg 49kg 49kg 51kg Refrigerant gas liquid side Φ15 9 Φ6 35 Φ15 9 Φ9 52 Φ15 9 Φ9 52 Φ15 9 Φ6 35 Φ15 9 Φ9 52 Φ15 9 Φ9 52 Water inlet outlet Drain connection Outlet water heating model Outlet water cooling model Domestic hot water Ambient temperature Water pressure 220 240V 50Hz ...

Страница 70: ... shall be displayed 7 Ventilated area Ensure that the area is in the open or that it it adequately ventilated before breaking into the system or conducting any hot work A degree of ventilation shall continue during the period that the work is carried out The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere 8 Checks to the refrigerat...

Страница 71: ...this task Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved then venting to atmosphere and finally pulling down to a vacuum This process shall be repeated until no refrigerant is within the system When the final OFN charge is used the system shall be vented down to atmospheric pressure to enable work to take place...

Страница 72: ... equipment appliances The storage of equipment should be in accordance with the manufacturer s instructions Storage of packed unsold equipment Storage package protection should be constructed such that mechanical damage to the equipment inside the package will not cause a leak of the refrigerant charge The maximum number of pieces of equipment permitted to be stored together will be determined by ...

Страница 73: ...erant liquid line temperature sensor Refrigerant gas line temperature sensor Water outlet temperature sensor Expansion vessel Circulating pump Manometer Pressure relief valve Internal backup heater Total outlet temperature sensor ANNEX A Refrigerant cycle Water inlet temperature sensor Automatic air purge valve Basic Customized 7 4 ...

Страница 74: ...71 NOTE ...

Страница 75: ...uits peuvent être modifiés sans préavis Photos non contractuelles In dem Bemühen um ständige Verbesserung können unsere Erzeugnisse ohne vorherige Ankündigung geändert werden Fotos nicht vertraglich bindend A causa della politica di continua miglioria posta in atto dal costruttore questi prodotti sono soggetti a modifiche senza alcun obbligo di preavviso Le foto pubblicate non danno luogo ad alcun...

Отзывы: