10 - Troubleshooting
The table below lists the anomalies of operation of the unit, the relevant causes and the corrective measures. For anomalies of any other type or
not listed, contact one of authorised Service Centre for technical assistance.
Anomaly
Cause
Operation
The unit continues
to work, but without
cooling
Insufficient charge of refrigerant.
Refill.
The dehydrating filter is clogged.
Replace.
Ice on the suction line
Wrong calibration of overheating.
Increase overheating.
Check the charge.
Excessive noise
Vibration of lines.
Check the clamping brackets, if any.
Whistler emitted by the thermostatic expansion
valve.
Refill.
Check the dehydrating filter.
Noisy compressor.
Seized bearings; replace the compressor.
Check that the compressor’s locknuts are tightened.
Low oil level in the
compressor
One or more gas or oil leaks in the circuit.
Identify and remove leaks.
Mechanical failure of the compressor.
Request the intervention of a Service Centre.
Anomaly of the oil heater of the compressor’s
base.
Check the electric circuit and the resistor of the heater of the
motor base, and replace defective components.
One or both
compressors are not
working
Breaking of the electric circuit.
Check the electric circuit and detect any ground dispersions and
short circuits. Check fuses.
Intervention of the HP pressure switch.
Reset the pressure switch and the control panel and restart
the appliance. Identify and remove the cause that enabled the
pressure switch.
The fuse of the control circuit is broken.
Check for ground dispersions and short circuits. Replace fuses.
Loosened terminals.
Check and tighten.
Halt caused by thermal overload of the electric
circuit.
Check the operation of check and safety devices. Identify and
remove the cause.
Wrong wiring.
Check wiring of check and safety devices.
The line voltage is too low.
Check voltage. If problems regard the system, solve them. If
they are caused by the distribution network, inform the Energy
Distributor.
Short-circuit of the compressor’s motor.
Check the continuity of the winding.
Seized compressor.
Replace the compressor.
Activation of the LP
alarm, stop of the unit
Gas leak.
Identify and remove the leak.
Insufficient charge.
Refill.
Activation of the HP
alarm, stop of the unit
Failure of the pressure switch.
Check the operation of the pressure switch, replace it if
defective.
The delivery valve is partially closed.
Open the valve and replace it, if faulty.
Substances with condensable gases in the
circuit.
Drain the circuit.
The fan of the condenser is stopped.
Check cables and motor. If defective, repair or replace.
The liquid line is too hot
Insufficient charge.
Identify and remove the cause of the loss of charge and refill.
Frosting of the liquid
line
The valve of the liquid line is partially closed.
Check that valves are open.
The liquid filter is clogged.
Replace the cartridge or the filter.