Before Starting the System |

9

Follow the ventilation drawing when connecting the unit to the duct system.

6.1

Ventilation Duct Connection and Insulation

Important

• Always cover the ventilation ducts during construction period.

• Make sure there are no loose objects or impurities inside the ducts.

Install the ducts, supply air diffusers and air intake grilles as shown in the ventilation drawing.

• Supply air and extract air ducts must be insulated if located in cold places.

• Outdoor air and exhaust air ducts with cold air must be insulated if located in warm places (inside building’s vapour

barrier).

It is very important to insulate cold ducts and joints tightly without any gaps, otherwise there is a risk of condensation
which may result in moisture damage.

Do not install the ducts directly against structural building elements to avoid sound propagation. Use acoustic insulation
and sound attenuators.

Note:

The type of ventilation ducts and insulation differ for each building and climate zone. If the ventilation
drawing is not provided, please contact your installer or place of purchase for recommendations.

6.2

Installation and Configuration of Accessories

Please follow instructions included with the accessory or consult “Service and Accessories Installation” manual which
can be found in our online catalogue.

7

Before Starting the System

When the installation is completed, check that:

• The unit is installed in accordance with the instructions

• Outdoor and exhaust air dampers and silencers are installed and that the duct system is correctly connected to the

unit

• All ducts are sufficiently insulated and installed according to local rules and regulations

• Outdoor air intake is positioned with sufficient distance to pollution sources (kitchen ventilator exhaust, central vac-

uum system exhaust or similar)

• All external equipment is connected

229391 | v02

Содержание SAVE VTR 300/B

Страница 1: ...Document in original language 229391 v02 SAVE VTR 300 B Installation instructions GB...

Страница 2: ...s the rights to alter their products without notice This also applies to products already ordered as long as it does not affect the previously agreed specifications Systemair is not liable or bound by...

Страница 3: ...it 5 3 4 2 Condensation outside of the unit 6 4 Delivery Transport Storage 6 4 1 Transport and storage 6 4 2 Delivery Unloading 6 5 Prerequisites for Installation 6 5 1 Location and Space Requirements...

Страница 4: ......

Страница 5: ...ve make a note of the specification and production number from the type label which can be found next to the external connections and inside of the unit Fig 1 Type label Position Description 1 Product...

Страница 6: ...Admonitions Danger Make sure that the mains supply to the unit is disconnected before performing any maintenance or electrical work All electrical connections and maintenance work must be carried out...

Страница 7: ...Technical Data 3 3 2 Dimensions and Weight Fig 2 Dimensions of left hand unit 229391 v02...

Страница 8: ...4 Technical Data Fig 3 Dimensions of right hand unit Water coil connections Drainage Height with mounting bracket The unit weight is 56 kg 229391 v02...

Страница 9: ...unit is in tended to be stopped by the user manually or due to calendar function we recommend to install air tight dampers at ex tract and supply air ducts The dampers will ensure that no air circulat...

Страница 10: ...d be stored and transported in such a way that it is protected against physical damage It should be covered so dust rain and snow cannot enter and damage the unit and its components Important Use the...

Страница 11: ...es delivery Note The drainage connection is plugged in the bottom of the unit at delivery To use the drainage remove the rubber seal and connect the drainage pipe Connect the drainage pipe to the sewe...

Страница 12: ...8 Installation C concrete bricks W wood block G gypsum M mineral wool X adaptable height according to needs Make sure the mounting bracket is completely level 229391 v02...

Страница 13: ...o avoid sound propagation Use acoustic insulation and sound attenuators Note The type of ventilation ducts and insulation differ for each building and climate zone If the ventilation drawing is not pr...

Страница 14: ...s It is possible to go back to previous menus and make modifications Finally choose heating type or none Finish startup wizard with OK button All additional changes post startup wizard must be recorde...

Страница 15: ...l appliances Part 2 40 Particular requirements for electrical heat pumps air conditioners and dehumidifiers EN 50106 Safety of household and similar appliances Particular rules for routine tests refer...

Страница 16: ...SAVE VTR 300 B Installation instructions 229391 en_GB 2021 02 05 v02 Systemair UAB Lin st 101 LT 20174 Ukmerg LITHUANIA Phone 370 340 60165 Fax 370 340 60166 www systemair com...

Отзывы: