Alarm settings
Preset
value
Set
value
Alarm settings
Preset
value
Set
value
18. High room temp
39. Manual Exhaust Air Fan freq control
Class
B
Class
C
Delay 30 min
Delay
0 s
Stop ventilation unit if alarm active
No
Stop ventilation unit if alarm active
No
High room temp 30 °C
19. Low room temp
40. Manual heater control
Class
B
Class
C
Delay 30 min
Delay
0 s
Stop ventilation unit if alarm active
No
Stop ventilation unit if alarm active
No
Low room temp 10 °C
20. High exhaust air temp
41. Manual cooler control
Class
B
Class
C
Delay 30 min
Delay
0 s
Stop ventilation unit if alarm active
No
Stop ventilation unit if alarm active
No
High exhaust temp 30 °C
21. Low exhaust air temp
42. Manual exchanger control
Class
B
Class
C
Delay 30 min
Delay
0 s
Stop ventilation unit if alarm active
No
Stop ventilation unit if alarm active
No
Low exhaust temp 10 °C
22. Electric heating is overheated
43. Manual P1-Heater
(Set to Off on HW units)
Class
A
(Applies to HW units)
Class
C
Delay
0 s
Delay
0 s
Stop ventilation unit if alarm active
Yes
Stop ventilation unit if alarm active
No
23. Frost risk
44. Manual P1-Cooler
(Set to Off on EL units)
Class
B
Class
C
Delay
60 s
Delay
0 s
Stop ventilation unit if alarm active
No
Stop ventilation unit if alarm active
No
24. Low frost guard temp
46. Manual fire damper
(Applies to HW units) Class
A
Class
B
Delay
0 s
Delay
0 s
Stop ventilation unit if alarm active
Yes
Stop ventilation unit if alarm active
No
Frost limit
7 °C
25. Low efficiency
47. Internal battery error
Class
Off
Class
A
Delay 30 min
Delay
0 s
Stop ventilation unit if alarm active
No
Stop ventilation unit if alarm active
No
Low efficiency
50 %
In/Output Configurations.
Possible choices of
Analogue input signal
Preset
Configuration
Set
Configuration
Outdoor temperature sensor
UAI 1
Supply air temperature sensor
AI 4
Exhaust air temperature sensor
AI 3
Extract temperature sensor
Room temperature sensor 1
Room temperature sensor 2
CO2 / VOC sensor 0…10V DC
Extra sensor / Set point potentiometer
Pressure transmitter, supply air 0…10V DC
AI 1
Pressure transmitter, exhaust air 0…10V DC
AI 2
De-icing sensor, heat exchanger
Frost protection sensor, Hot water heater.
UAI 4
(HW units)
Room Humidity sensor
Duct Humidity sensor