Commissioning record
Company
Responsible
Customer
Date
Installation
Object / Unit
Item no.
Installation address
Model / size
Series no.
Present time and date set.
Week schedule set.
External connections such as sensors, dampers, external alarms etc. done.
Function
Preset value
Set value
Temperature (°C).
Control function Temp.
Set point
Outdoor compensating
(supply air controlling)
Outdoor / supply temp.
Point 1,2 and 3
Point 4,5 and 6
Point 7 and 8
Min. supply set point
Max. supply set point
Switching point, between
supply and cascade
regulating
Supply
Exhaust
Room
18,0 °C
-30,0 / 22,0 -20,0 / 21,0 -11,0 / 20,5
-4,0 / 20,0 5,0 / 19,5 12,5 / 19,0
21,0 / 18,5 30,0 / 18,0
12,0 °C
30,0 °C
13,0 °C
Supply
Exhaust
Room
°C
/
/
/
/
/
/
/
/
°C
°C
°C
Air flow
Fan regulation
Airflow (m3/h)
Pressure (Pa)
CO2 (ppm)
Airflow (m3/h)
Pressure (Pa)
CO2 (ppm)
Set point Normal
Supply fan
* .
Extract fan
** .
Supply fan
Extract fan
Set point Reduced
Supply fan
***.
Extract fan
****.
Supply fan
Extract fan
Outdoor compensation
Lower point -20.°C 0 .m3/h, Pa
Upper point 10.°C 0 .m3/h, Pa
Lower point °C m3/h, Pa
Upper point °C m3/h, Pa
Only reduced fan speed
when outdoor is below.
-20 °C
°C
Rotovex 2400
* 2300 m3/h or 250Pa
** 2300 m3/h or 250Pa *** 1500 m3/h or 100Pa
**** 1500 m3/h or 100Pa
Rotovex 3800
* 3500 m3/h or 250Pa
** 3500 m3/h or 250Pa *** 2000 m3/h or 100Pa
**** 2000 m3/h or 100Pa
Rotovex 4800
* 4500 m3/h or 250Pa
** 4500 m3/h or 250Pa *** 2500 m3/h or 100Pa
**** 2500 m3/h or 100Pa