Cleaning |
21
Activities cont'd
Check the screwed connections for damages/defects and
check that they are firmly seated.
X
See normal operating
conditions
Check the fan intake is free from contamination.
X
X
Check that the fan and its components are being used
correctly.
X
See normal operating
conditions
Check the current consumption and compare this with the
rated data.
X
X
Check the vibration dampers (if used) are working
correctly and check for visible damage and corrosion.
X
See normal operating
conditions
Check the electrical and mechanical protective equipment
is working correctly.
X
See normal operating
conditions
Check the fan’s rating plate is legible.
X
X
Check the connection clamps and screwed cable
connections for damage/defects, and check that they are
firmly seated.
X
See normal operating
conditions
Check the flexible connectors for damage.
X
See normal operating
conditions
Note:
For all other damage/defects, please contact Systemair.
13.4 Spare parts
♦
Use original spare parts from Systemair only.
♦
When ordering spare parts, please specify the serial number of the fan. This can be found on the name plate.
1
Motor
1
2
3
4
5
6
2
Flange plate
3
Motor disc
4
Impeller
5
Taper bush
6
Housing
14
Cleaning
14.1 Safety information
♦
Cleaning may only be carried out by adequately qualified persons, details see Table 1
♦
Wear protective equipment during all work in the vicinity of the fan, details see 3.2
♦
Observe the 5 rules of electrical safety, see 3.3
♦
The impeller must be at a standstill.
♦
Pay attention to the safety data sheet of the chemical substances transported with the fan.
| 002