Short description of main components in the control system |
11-1
Annex 11 Short description of main components in the control system
11.1 Geniox Core units delivered in several sections
This model of the Geniox Core unit has an integrated control system and depending on the size of the unit, the cabinet
is installed in the unit, on the unit or on the front of the unit. The controller is mounted in the cabinet, and all electrical
connections between cabinet and components in the unit are installed. The control system is configured according to
the customer’s order – confirmed by the order confirmation - to promote easy start-up on the site. The unit is tested at
the factory and all functions are confirmed by a final functional test and test report that is deliverd with the unit. After
the final test the unit is divided in sections to facilitate the transport. After reassembly of the unit on the site, the clearly
marked cables with sockets must be reconnected in the marked terminals. Cable strips are preinstalled for installation
of the cables between the components in the unit-sections and the cabinet. Cables installed on the unit-sections in the
preinstalled strips are protected by metal covers. The covers have been removed before installation of the unit on the
final site and must be replaced after installation of the cables. Cables with the mains power supply must be installed in
the automatic circuit breakers belonging to fans, heat pump unit Geniox Core-HP (if delivered). All external components
must be connected on the site.
11.1.1
External components
External components are Systemair control panel, valves, valve motors, pressure transmitters, supply air temperature
sensor, sensor for water temperature in the heating coil (if water heating coil was requested) and circulation pump
(Systemair does not deliver the pump). Terminals are present in the cabinet for pressure transmitters, if it is a solution
for constant pressure in the ducts, and terminals are present in the cabinet for valve motors, circulation pump, supply
air temperature sensor and sensor for water temperature in the heating coil, but cables are not installed and not
connected to terminals in the cabinet. The Systemair control panel with cable is not connected to the controller in the
cabinet. All external components delivered are packed in a cardboard box delivered together with the unit.
11.2 Geniox Core unit delivered assembled on base frame
This model of the Geniox Core unit has an integrated control system and the cabinet mounted inside the unit. The
cabinet is always mounted in the unit section with the heat exchanger and the cabinet is always placed at the warm
side of the heat exchanger. The intelligent controller is mounted in the cabinet, and all electrical connections between
cabinet and components in the unit are installed. The control system is configured according to the customer’s order –
confirmed by the order confirmation - to promote easy start-up on the site. The unit is tested at the factory and all
functions are confirmed by a final functional test and test report that is deliverd with the unit. The unit is delivered as
one assembled section on base frame. Cables with the mains power supply must be installed in the automatic circuit
breakers belonging to fans, heat pump unit Geniox Core-HP (if delivered). All external components must be connected
on the site.
11.2.1
External components
External components are Systemair control panel, valves, valve motors, pressure transmitters, supply air temperature
sensor, sensor for water temperature in the heating coil (if water heating coil was requested) and circulation pump
(Systemair does not deliver the pump). Terminals are present in the cabinet for pressure transmitters, if it is a solution
for constant pressure in the ducts, and terminals are present in the cabinet for valve motors, circulation pump, supply
air temperature sensor and sensor for water temperature in the heating coil, but cables are not installed and not
connected to terminals in the cabinet. The Systemair control panel with cable is not connected to the controller in the
cabinet. All external components delivered are packed in a cardboard box delivered together with the unit.
output |