background image

 

 

 

2.

 

Wiring  

 

On page 13, there is prepared terminal block for connection of smoke detector type KRM-1 (230V). 

Terminal block 33 and N is for power supply (230V AC) and terminal block 34 and 35 are signal from 

smoke detector which tell controller that we need to shut down the AHU. 

In factory there will be a bridge between terminal block 34 and 35 in case that customer don’t want a 

smoke detector function. 

If there is NO smoke or fire the relay K4 must be activated! 

 

 

Содержание FGT010

Страница 1: ...Systemair FGT Control manual ...

Страница 2: ...ANGING UNIT OPERATION TIME VII TURNING OFF THE UNIT VIII CHANGING TEMPERATURE REGULATION IX CHANGING TEMPERATURE SETPOINTS FOR ROOM EXTRACT TEMPERATURE OR TEMPERATURE FOR SUPPLY AIR X WATER COOLER ACTIVATION XI DX COOLING UNIT ACTIVATION XII DX HEATING COOLING UNIT ACTIVATION XIII ELECTRIC HEATER ACTIVATION XIV SMOKE DETECTOR ...

Страница 3: ...INSTRUCTIONS FOR CHANGING LANGUAGE CORRIGO CONTROLLER Basic FGT010 FGT015 FGT022 ...

Страница 4: ...2 Contents 1 Search for change language menu 3 2 Changing language 4 ...

Страница 5: ...3 1 Search for change language menu Put yourself on the first screen Press RIGHT key button for menu Again press the RIGHT key button Again press the RIGHT key button ...

Страница 6: ...you found language which you like to have press OK Press LEFT 3x to go back to first menu You can choose between English Czech Slovak Swedish Lithuanian Dutch Norwegian Estonian Turkish Danish Hungarian Romanian German Latvian French Slovenian Finnish Spanish Russian Portuguese Polish Italian ...

Страница 7: ...INSTRUCTIONS FOR EXTERNAL DISPLEY ED RU DFO ED TCV CORRIGO CONTROLLER Basic FGT010 FGT015 FGT022 ...

Страница 8: ...2 Contents 1 Search for Admin access 3 2 Search for communication menu 5 3 Wiring diagram of ED TCV 7 4 Wiring diagram of ED RU DFO 9 5 Important note 11 ...

Страница 9: ...ey 4x to access the menu Access rights Press RIGHT key button Press RIGHT key button Press the OK button to position yourself on Enter password Please enter the password 1111 For entering the password Press UP key 2x for value 1 Press RIGHT key for next position and repeat the process for the password 1111 ...

Страница 10: ...4 Press OK button and you will be logged in as Admin ...

Страница 11: ...communication menu Press LEFT key 2x to get to the menu Press UP key button to position yourself on the menu Configuration Press RIGHT key button Press DOWN 31x key button Press RIGHT key button Press DOWN key button ...

Страница 12: ...Wait at least 10s and press RIGHT key Press OK button and press DOWN key depend on which external display you want to connect You have 2 option available in menu If you want to connect ED TCV external display choose ED TCV Or if you want to connect ED RU DFO choose ED RU RUD ...

Страница 13: ...7 3 Wiring diagram of ED TCV ...

Страница 14: ...8 ...

Страница 15: ...9 4 Wiring diagram of ED RU DFO ...

Страница 16: ...10 ...

Страница 17: ...ill activate an external display and start using Port 2 of communication on Corrigo controller you cannot use communication protocol Modbus RTU via RS 485 They only left Modbus TCP IP or BacNet communication protocol for SCADA system ...

Страница 18: ...INSTRUCTIONS FOR EXTERNAL SENSORS CORRIGO CONTROLLER Basic FGT010 FGT015 FGT022 ...

Страница 19: ...3 1 RCO2 W room CO2 sensor 5 3 2 Systemair 2 CO2 duct sensor 6 3 3 RTF1 PT1000 room temperature sensor 7 3 4 QPA2002D room air quality VOC sensor 8 3 5 QPM2102 duct CO2 VOC sensor 9 4 Configuration of system 10 5 Search for UI menu 12 6 Type of sensor 14 7 Watching values 15 ...

Страница 20: ...FGT Basic there is prepared free terminal block for connecting an external sensor like room CO2 room VOC duct CO2 duct VOC room humidity room temperature sensor etc You can see free terminal block on page 8 in wiring diagram ...

Страница 21: ...FGT Basic there are accessories sensors RCO2 W room CO2 sensor 993305 Systemair 2 CO2 duct sensor 14907 RTF1 PT1000 room temperature sensor 993136 QPA2002D room air quality VOC sensor 994027 QPM2102 duct CO2 VOC sensor 993301 ...

Страница 22: ...you must connect Terminal block number 1 from sensor to terminal block 32 or 35 in electric cabinet Terminal block number 2 from sensor to terminal block 30 or 33 in electric cabinet Terminal block number 3 from sensor to terminal block 31 or 34 in electric cabinet ...

Страница 23: ...sor you must connect Red color wire from sensor to terminal block 32 or 35 in electric cabinet Violet color wire from sensor to terminal block 30 or 33 in electric cabinet Black color wire from sensor to terminal block 31 or 34 in electric cabinet ...

Страница 24: ...oom temperature sensor On this sensor you must connect Terminal block number 1 from sensor to terminal block 30 or 33 in electric cabinet Terminal block number 2 from sensor to terminal block 31 or 34 in electric cabinet ...

Страница 25: ...must connect Terminal block number G from sensor to terminal block 32 or 35 in electric cabinet Terminal block number U2 from sensor to terminal block 30 or 33 in electric cabinet Terminal block number G0 from sensor to terminal block 31 or 34 in electric cabinet ...

Страница 26: ... connect Terminal block number G from sensor to terminal block 32 or 35 in electric cabinet Terminal block number U2 from sensor to terminal block 30 or 33 in electric cabinet Terminal block number G0 from sensor to terminal block 31 or 34 in electric cabinet ...

Страница 27: ...key 4x to access the menu Access rights Press RIGHT key button Press RIGHT key button Press the OK button to position yourself on Enter password Please enter the password 1111 For entering the password Press UP key 2x for value 1 Press RIGHT key for next position and repeat the process for the password 1111 ...

Страница 28: ...11 Press OK button and you will be logged in as Admin ...

Страница 29: ... for UI menu Press LEFT key 2x to get to the menu Press UP key button to position yourself on the menu Configuration Press RIGHT key button Press RIGHT key button Press DOWN 4x to get to UI Press RIGHT key button ...

Страница 30: ...13 In this menu you have now chosen UI1 if you press DOWN you will be on UI2 setup Important is that all accessories sensors must be set as AI and not DI ...

Страница 31: ... press 4x DOWN key button For room or duct CO2 sensor you must choose CO2 sensor press 12x DOWN key button For room humidity you must choose Humidity roo press 13x DOWN key button For humidity duct you must choose Humidity duc press 14x DOWN key button Press ENTER 2x to finish selection ...

Страница 32: ...tching values To check a value from specific sensor you must go Put yourself on the first screen Press DOWN key to enter the menu Press RIGHT key Press DOWN key 3x to come on Input Output menu Press RIGHT key ...

Страница 33: ...16 Our external sensor are connected on Universal input so we need to check on UI menu Press DOWN 2x Press RIGHT key In example above we have connected 2 sensors Room Temp1 and Humidity duct ...

Страница 34: ...INSTRUCTIONS FOR CHANGING AIRFLOW CORRIGO CONTROLLER Basic FGT010 FGT015 FGT022 ...

Страница 35: ...2 Contents 1 Search for airflow set point menu 3 2 Airflow set point menu 4 ...

Страница 36: ...3 1 Search for airflow set point menu Put yourself on the first screen Press DOWN key to enter the menu Press DOWN key 2x to access the menu Air control Press RIGHT key button ...

Страница 37: ...e in SAF or EAF menu You will access the menu to change the airflow example for SAF Press OK button and you will need to type in the password Type in the password 3333 with UP key adjust the correct number and with the RIGHT key move to next number to change Press OK button This will grant you OPERATOR rights It will automatically position you in the correct menu after 3s ...

Страница 38: ...ey you move between decimal numbers for required value Confirm with OK button witch will automatically position you to the next menu Setp This value cannot be lower than 800 m3 h Speed 1 1 is normal speed Speed 1 2 is reduced speed which is set when the unit is in startup mode Press LEFT key 2x and UP key 3x You will be in the starting menu ...

Страница 39: ...INSTRUCTIONS FOR CHANGING VENTILATOR REGULATION INTO VAV CORRIGO CONTROLLER Basic FGT010 FGT015 FGT022 ...

Страница 40: ...unting external pressure sensor 3 4 Wiring external pressure sensors 4 5 Search for Admin access 5 6 Search for analog input menu 7 7 Range measurement of VAV external Presigo sensors 11 8 Pressure set point 13 9 Example of change set point of pressure 14 ...

Страница 41: ...sure sensors need to be mounted near supply air duct and extract air duct and must be connected to electric cabinet to external connection terminal block External supply duct sensor A3 pressure hose it s need to be connected in supply duct and is surrounding pressure External extract duct sensor A4 pressure hose it s need to be connected in extract duct and is surrounding pressure Both pressure se...

Страница 42: ...4 Table 1 Symbol description Symbol Description Supply air Extract air 4 Wiring external pressure sensors ...

Страница 43: ... 5 Search for Admin access Put yourself on the first screen Press DOWN key button to enter the menu Press DOWN key button 4x to access the menu Access rights Press RIGHT key button Press RIGHT key button ...

Страница 44: ...rself on Enter password Please enter the password 1111 For entering the password press UP key 2x for value 1 Press RIGHT key for next position and repeat the process for the password 1111 Press OK button and you will be logged in as Admin ...

Страница 45: ...r analog input menu Press LEFT key 2x to get to the menu Press UP key button to position yourself on the menu Configuration Press RIGHT key button Press RIGHT key button Press DOWN key button Press RIGHT key button ...

Страница 46: ...s OK and DOWN 3x to choose SAF extra press and OK 2x Press LEFT key button Press DOWN key button Press RIGHT key button Press DOWN key button Press OK and DOWN key 3x to choose EAF extra press and press OK 2x Press LEFT key button ...

Страница 47: ...utton Press DOWN key button to come on AI2 Press OK and DOWN key 8x to choose SAF pressure and press OK 2x Press DOWN key button to come on menu AI3 Press OK and DOWN key button 9x and OK 2x to choose EAF pressure Press LEFT key button 2x Press DOWN key button 3x ...

Страница 48: ...10 Press RIGHT key button Press OK and UP key button to choose Pressure control and press OK IMPORTANT Shut down AHU for at least 30 seconds so that controller will recognize changes ...

Страница 49: ...ge the value of max range In our case is now set on 2500Pa and we need to change it to the value which you choose with dip settings of Presigo sensor In chapter 4 we set it on 1250Pa so also we need to change it here So in our case you press OK 2x to put yourself on 2500 Change the value to 1250 with UP DOWN button and press OK 4x ...

Страница 50: ...12 And repeat process ...

Страница 51: ...RIGHT key button Now you have menu in which you can change set point of pressure regulation In picture above there is writen SAF this is for supply duct Picture below in marked in red EAF is for extract duct Currently you are position on SAF menu and if you press DOWN button you will come on EAF ...

Страница 52: ...that you put yourself on Setp 1 1 and with buttons UP DOWN change value With RIGHT LEFT button you change decimal place Press OK button and you will be now positioned on Setp 1 2 If you press OK button again then you finish setting for set point of supply SAF pressure regulation The same process is with EAF pressure regulation ...

Страница 53: ...INSTRUCTION FOR CHANGING UNIT OPERATION TIME CORRIGO CONTROLLER Basic FGT010 FGT015 FGT022 ...

Страница 54: ...2 Contents 1 Search for time setting menu 3 2 Time setting menu 4 3 Changing the date of the unit 5 4 Changing the operation time of the unit in normal speed 6 ...

Страница 55: ...3 1 Search for time setting menu Put yourself on the first screen Press DOWN key to enter the menu Press DOWN key 3x to access the menu Time settings Press RIGHT key button ...

Страница 56: ... Timer normal speed you can set the Operation time for normal run mode In the menu Timer reduced speed you can set the Operation time for reduced run mode It s better to only adjust the time for Normal speed The Reduced speed time is only used for special operation times for the unit and start up ...

Страница 57: ...n and you will need to type in the password Press OK button This will grant you OPERATOR rights It will automatically position you in the correct menu after 3s Press OK button to set the time With UP key you can change the value and with RIGHT key you move to the next decimal number Value after are minutes ...

Страница 58: ...r normal speed Press RIGHT key button Press OK button and you will need to type in the password Press OK button This will grant you OPERATOR rights It will automatically position you in the correct menu Press OK button and it will positon the curser over start up time of first period Per 1 ...

Страница 59: ...e minutes When you set the time of start up for second period press OK button and set the time for shut down for Per 2 With UP DOWN key you change the value and with RIGHT key you move to the next decimal number Value after are minutes The time of start up can t be grater then the time of shut down For the unit this means forbidden time and so the unit will not start at that period Also the time d...

Страница 60: ...INSTRUCTION FOR TURNING OFF THE UNIT CORRIGO CONTROLLER Basic FGT010 FGT015 FGT022 ...

Страница 61: ...2 Contents 1 Search of running mode menu 3 2 Running mode menu 4 ...

Страница 62: ...3 1 Search of running mode menu Put yourself on the first screen You press the DOWN key and you come to the menu Now press RIGHT key button Again press RIGHT key button ...

Страница 63: ... Press OK DOWN and again OK The alarm light will be flashing red Now press the red button for alarm and you will have active alarm displayed If you change Running mode from OFF to AUTO the fault will be reset automatically ...

Страница 64: ...INSTURCTIONS FOR CHANGING TEMPERATURE REGULATION CORRIGO CONTROLLER Basic FGT010 FGT015 FGT022 ...

Страница 65: ...2 Contents 1 Search of changing temperature regulation menu 3 2 Temperature regulation menu 5 ...

Страница 66: ...arch of changing temperature regulation menu Put yourself on the first screen Press DOWN key to enter the menu Press DOWN key 4x to access the menu Access rights Press RIGHT key button Press RIGHT key button ...

Страница 67: ...ress OK button and you will be logged in as Admin Press LEFT key 2x to get to the menu Press UP key to position yourself on the menu Configuration Press RIGHT key button Position the curser over Control function press DOWN key 2x and then RIGHT key Now you are in the menu to change temperature regulation Currently there are two regulation available Temperature regulation of constant air supply and...

Страница 68: ...trol If you would like to change to constant air supply do the following Press OK button Press UP key 4x for menu Supply air control Press OK button Now you changed the temperature regulation from extract air to constant supply air Press LEFT key button 2x Press UP key button 7x to return to main screen ...

Страница 69: ...INSTRUCTIONS FOR CHANGING TEMPERATURE SETPOINTS FOR ROOM EXTRACT TEMPERATURE OR TEMPERATURE FOR SUPPLY AIR CORRIGO CONTROLLER Basic FGT010 FGT015 FGT022 ...

Страница 70: ...Contents 1 Search for temperature set point menu 3 2 Temperature set point menu 4 ...

Страница 71: ...1 Search for temperature set point menu Put yourself on the first screen Press DOWN key to enter the menu Press DOWN key for menu Temperature Press RIGHT key button ...

Страница 72: ...key move to next number to change Press OK button This will get you an OPERATOR rights It will automatically position you in the correct menu after 3s Press OK button and set desired value of temperature from room With UP key adjust the value and with RIGHT key move to set the next decimal number Press LEFT key 2x and UP key 3x You will be in the starting menu ...

Страница 73: ...INSTRUCTIONS FOR WATER COOLER ACTIVATION CORRIGO CONTROLLER Basic FGT010 FGT015 FGT022 ...

Страница 74: ... 3 Search for type of cooler menu 7 4 Electric wiring diagram 8 5 In case that your FGT Basic unit will not have any heater element 9 5 1 Deactivating frost protection sensor 10 5 2 Deactivating heating signal AO 12 5 3 Deactivating heating signal DO 13 5 4 Change type of heater element 14 ...

Страница 75: ... 1 Search for Admin access Put yourself on the first screen Press DOWN key button to enter the menu Press DOWN key button 4x to access the menu Access rights Press RIGHT key button Press RIGHT key button ...

Страница 76: ...rself on Enter password Please enter the password 1111 For entering the password press UP key 2x for value 1 Press RIGHT key for next position and repeat the process for the password 1111 Press OK button and you will be logged in as Admin ...

Страница 77: ...ler Press LEFT key 2x to get to the menu Press UP key button to position yourself on the menu Configuration Press RIGHT key button Press RIGHT key button Press DOWN 7x to get to AO Press RIGHT key button In the top left corner the menu will show AO1 ...

Страница 78: ...to change from Not used to Y3 cooling To do that you need to press DOWN key 3x and OK button 3x Now we selected the signal for cooling We need to select what type of water cooler we have After activating the function you must restart the unit ...

Страница 79: ...efore Press LEFT key 2x for menu Inputs Outputs Press DOWN key button 8x for menu Cooling Press RIGHT key button Press OK button and then UP key 2x for Water and again OK button to confirm Configuration for water cooler is completed Press LEFT 2x Press UP key 7x to return to main screen ...

Страница 80: ...8 4 Electric wiring diagram Use terminal 24V SP AGND and 13 and corresponding pins G0 G and Y on the valve to connect Connect G0 to terminal AGND G to terminal 24V SP and Y to terminal 13 ...

Страница 81: ...uest without any heater element it is necessary to deactivate frost protection sensor signal for relay activate and type of heating element Put yourself on the first screen Press DOWN key button to enter the menu Press DOWN key button 4x to access the menu Access rights Press RIGHT key button Press RIGHT key button ...

Страница 82: ...UP key 2x for value 1 Press RIGHT key for next position and repeat the process for the password 1111 Press OK button and you will be logged in as Admin 5 1 Deactivating frost protection sensor Press LEFT key button 2x to get to the menu Press UP key button to position yourself on the menu Configuration Press RIGHT key button ...

Страница 83: ...n 5x to put yourself to menu UI exp3 Press RIGHT key button On the top left of the screen you should have UI1 selected Press DOWN key for UI2 We need to change the Frost prot t to Not used Press OK button and then UP key 11x and again OK button 2x ...

Страница 84: ...12 5 2 Deactivating heating signal AO Press LEFT key button Press DOWN key button 2x Press RIGHT key button Press OK to change value from Y1 heating to Not used Press UP key button Press OK button 3x ...

Страница 85: ... 3 Deactivating heating signal DO Press LEFT key button Press DOWN key for menu DO Press RIGHT key button We need to change from P1 heating to Not used Press OK button and then UP key 5x Press OK button 2x ...

Страница 86: ... top menu shown one step before Press LEFT key 2x for menu Inputs Outputs Press DOWN key 6x for menu Heating Press RIGHT key button Now press OK button and UP key button 2x Menu should be displayed Not connected and press OK button Configuration for Electric heater is complete Press LEFT 2x Press UP key button 7x to return to main screen ...

Страница 87: ...INSTRUCTIONS FOR DX COOLING UNIT ACTIVATION CORRIGO CONTROLLER Basic FGT010 FGT015 FGT022 ...

Страница 88: ... for type of cooler menu 8 5 Electric wiring diagram for DX cooler 9 6 In case that your FGT Basic unit will not have any heater element 10 6 1 Deactivating frost protection sensor 11 6 2 Deactivating heating signal AO 13 6 3 Deactivating heating signal DO 14 6 4 Change type of heater element 15 7 Possible alarms 16 ...

Страница 89: ...ey 4x to access the menu Access rights Press RIGHT key button Press RIGHT key button Press the OK button to position yourself on Enter password Please enter the password 1111 For entering the password Press UP key 2x for value 1 Press RIGHT key for next position and repeat the process for the password 1111 ...

Страница 90: ...4 Press OK button and you will be logged in as Admin ...

Страница 91: ... digital DI menu Press LEFT key 2x to get to the menu Press UP key button to position yourself on the menu Configuration Press RIGHT key button Press RIGHT key button Press DOWN 3x to get to DI Press RIGHT key button ...

Страница 92: ...y 15x for Ext alarm1 NOT Ext alarm10 Press OK button and with UP key change from NO to NC contact Press OK With this setting we will be notified if there is an error with the DX unit If we have the contact on NC position it will be able to detect lost connection or a broken cable between the DX unit and the controller ...

Страница 93: ...y button In the top left corner the menu will show AO1 Press DOWN key button for AO2 Press OK button to change from Not used to Y3 cooling To do that you need to press DOWN key button 3x and OK button 3x Now we selected the signal for cooling We need to select what type of cooler unit we have DX ...

Страница 94: ...or menu Inputs Outputs Press DOWN key 8x for menu Cooling Press RIGHT key button Now press OK button and UP key button Menu should be displayed DX and press OK button Configuration for DX unit is complete Press LEFT 2x Press UP 7x to return to main screen After activating the function you must restart the unit ...

Страница 95: ...9 5 Electric wiring diagram for DX cooler ...

Страница 96: ...quest without any heater element it is necessary to deactivate frost protection sensor signal for relay activate and type of heating element Put yourself on the first screen Press DOWN key button to enter the menu Press DOWN key button 4x to access the menu Access rights Press RIGHT key button Press RIGHT key button ...

Страница 97: ...UP key 2x for value 1 Press RIGHT key for next position and repeat the process for the password 1111 Press OK button and you will be logged in as Admin 6 1 Deactivating frost protection sensor Press LEFT key button 2x to get to the menu Press UP key button to position yourself on the menu Configuration Press RIGHT key button ...

Страница 98: ...n 5x to put yourself to menu UI exp3 Press RIGHT key button On the top left of the screen you should have UI1 selected Press DOWN key for UI2 We need to change the Frost prot t to Not used Press OK button and then UP key 11x and again OK button 2x ...

Страница 99: ...13 6 2 Deactivating heating signal AO Press LEFT key button Press DOWN key button 2x Press RIGHT key button Press OK to change value from Y1 heating to Not used Press UP key button Press OK button 3x ...

Страница 100: ... 3 Deactivating heating signal DO Press LEFT key button Press DOWN key for menu DO Press RIGHT key button We need to change from P1 heating to Not used Press OK button and then UP key 5x Press OK button 2x ...

Страница 101: ... top menu shown one step before Press LEFT key 2x for menu Inputs Outputs Press DOWN key 6x for menu Heating Press RIGHT key button Now press OK button and UP key button 2x Menu should be displayed Not connected and press OK button Configuration for Electric heater is complete Press LEFT 2x Press UP key button 7x to return to main screen ...

Страница 102: ...or with the DX unit Check the instructions from the DX unit manufacturer for alarm list and remove the alarm Also check that the signal cable from the DX unit to the controller is not damaged or broke If the screen shows bellow the alarm Returned this means that the fault was removed but the alarm was not confirmed To confirm an alarm press OK button and enter the password 1111 and Acknowledge DO ...

Страница 103: ...INSTRUCTIONS FOR DX HEATING COOLING UNIT ACTIVATION CORRIGO CONTROLLER Basic FGT010 FGT015 FGT022 ...

Страница 104: ...t AO menu 12 7 Activating extra sequence Y4 14 8 Search for type of cooler menu 15 9 Electric heater as additional heater 16 10 Type of additional heater 18 11 Electric wiring diagram for combined DX unit heating cooling 19 12 Electric wiring diagram of additional electric heater 20 13 Electric wiring diagram of additional water heater 21 14 Possible alarms of DX unit 22 15 Possible alarms of addi...

Страница 105: ...ing defrost cycle In standard FGT unit we prepared in that case 2 options of preventing too much cold supply air additional signal 0 10V and start stop signal for additional heater element signal that AHU will go into reduce mode during defrost cycle lower airflow If you won t use any of suggested options you run a risk of shutting down of the FGT unit and it can also have serious damaged on DX re...

Страница 106: ... 2 Search for Admin access Put yourself on the first screen Press DOWN key button to enter the menu Press DOWN key button 4x to access the menu Access rights Press RIGHT key button Press RIGHT key button ...

Страница 107: ...rself on Enter password Please enter the password 1111 For entering the password Press UP key 2x for value 1 Press RIGHT key for next position and repeat the process for the password 1111 Press OK button and you will be logged in as Admin ...

Страница 108: ...DI menu Press LEFT key button 2x to get to the menu Press UP key button to position yourself on the menu Configuration Press RIGHT key button Again press RIGHT key button Press DOWN key button 3x to get to DI Press RIGHT key button ...

Страница 109: ...DOWN key button 2x for DI7 Press OK button and press UP key button 15x for Ext alarm1 NOT Ext alarm10 Press OK button and with UP key change from NO to NC contact Press OK With this setting we will be notified if there is an error with the DX unit If we have the contact on NC position it will be able to detect lost connection or a broken cable between the DX unit and the controller ...

Страница 110: ... Press OK and DOWN button 10x to choose Ext run Press OK 2x With this we activate reduced speed in case you want to use that type of regulation when DX unit will go into defrost cycle After activating the function you must restart the unit ...

Страница 111: ...3 menu Press LEFT key Press DOWN 2x for UI exp3 Press RIGHT key button On the top left of the screen you should have UI1 selected Press DOWN key for UI2 We need to change the Frost prot t to Not used Press OK button and then UP key 11x and again OK button 2x ...

Страница 112: ... DOWN key button 5x for DO Press RIGHT key button In the top left corner the menu will show DO1 Press OK button and press UP key button 10x for Y4 extra seq Press OK button 2x Press DOWN key button 2x for DO3 Press OK button then DOWN key button 16x and set to Cool start ...

Страница 113: ...11 Press OK button 2x ...

Страница 114: ...key button to return to menu Press UP key button for AO Press RIGHT key button for the menu In the top left corner the menu will show AO1 Press OK key button Press UP button key 4x for Y4 extra sequen and OK button 3x Press DOWN key button 1x for AO2 ...

Страница 115: ...o change from Not used to Y1 heat Y3 cooling To do that you need to press UP key button 4x and OK button 3x Now we selected the signal for heating cooling and additional heater element We need to activate additional heater ...

Страница 116: ... key button 2x for menu Inputs Outputs Press DOWN key button 4x for menu Extra sequence Y4 Press RIGHT key button Press OK button and DOWN key button to choose from Not active to Active Press OK button Now we activate function for additional heater We need to select what type of cooler unit we have DX ...

Страница 117: ...T key button for menu Extra sequence Y4 Press DOWN key button 4x for menu Cooling Press RIGHT key button Now press OK button and UP key button Menu should be displayed DX again press OK button Configuration for DX unit is complete Press LEFT key button 2x Press UP key button 7x to return to main screen ...

Страница 118: ... element in case on defrosting cycle of DX reversible unit you must also change this settings Search for digital input DI menu Press LEFT key 2x to get to the menu Press UP key to position yourself on the menu Configuration Press RIGHT key button Press RIGHT key button Press DOWN 3x to get to DI ...

Страница 119: ...x for DI6 Press OK button and then press DOWN key 17x for Overheat protection Press OK button and with UP key change from NO to NC contact Press OK button With this we set the feedback signal for the alarm in case of a fault in the electric heater After activating the function you must restart the unit ...

Страница 120: ...top menu shown one step before Press LEFT key 2x for menu Inputs Outputs Press DOWN key 6x for menu Heating Press RIGHT key button Now press OK button and UP key button Menu should be displayed Water Electric and press OK button Configuration for Electric heater is complete Press LEFT 2x Press UP key button 7x to return to main screen ...

Страница 121: ...Electric wiring diagram for combined DX unit heating cooling Terminal block C and 17 can be used if you do not have additional heater element in case that DX unit will go into defrosting cycle in winter time ...

Страница 122: ...20 12 Electric wiring diagram of additional electric heater ...

Страница 123: ...21 13 Electric wiring diagram of additional water heater ...

Страница 124: ...n error with the DX unit Check the instructions from the DX unit manufacturer for alarm list and remove the alarm Also check that the signal cable from the DX unit to the controller is not damaged or broke If the screen shows bellow the alarm Returned this means that the fault was removed but the alarm was not confirmed To confirm an alarm press OK button and enter the password 1111 and Acknowledg...

Страница 125: ...r Solution is that you need to increase airflow in case if you have set point under minimum airflow To confirm an alarm press OK button and enter the password 1111 and Acknowledge If the alarm is active and there is no Returned written then is probably still too hot in area of electric heater Wait 15min and if sign Returned appear then use solution from above If there is still alarm active after 1...

Страница 126: ...INSTRUCTIONS FOR ELECTRIC HEATER ACTIVATION CORRIGO CONTROLLER Basic FGT010 FGT015 FGT022 ...

Страница 127: ...sal input UI of Expansion unit 3 Exp3 menu 7 4 Search for digital output DO menu 8 5 Type of heater 9 6 Electric wiring diagram 10 7 2 phase electric heater diagram type MTXL 11 8 3 phase electric heater diagram type MTXL 12 9 Mounting presostat for electric heater safety 13 10 Possible alarms 14 ...

Страница 128: ...3 1 Search for Admin access Put yourself on the first screen Press DOWN key button to enter the menu Press DOWN key 4x to access the menu Access rights Press RIGHT key button Press RIGHT key button ...

Страница 129: ...rself on Enter password Please enter the password 1111 For entering the password press UP key 2x for value 1 Press RIGHT key for next position and repeat the process for the password 1111 Press OK button and you will be logged in as Admin ...

Страница 130: ... digital input DI menu Press LEFT key 2x to get to the menu Press UP key to position yourself on the menu Configuration Press RIGHT key button Press RIGHT key button Press DOWN 3x to get to DI Press RIGHT key button ...

Страница 131: ...Press DOWN key 5x for DI6 Press OK button and then press DOWN key 17x for Overheat protection Press OK button and with UP key change from NO to NC contact Press OK button With this we set the feedback signal for the alarm in case of a fault in the electric heater ...

Страница 132: ...3 menu Press LEFT key Press DOWN 2x for UI exp3 Press RIGHT key button On the top left of the screen you should have UI1 selected Press DOWN key for UI2 We need to change the Frost prot t to Not used Press OK button and then UP key 11x and again OK button 2x ...

Страница 133: ...menu Press LEFT key button Press DOWN key 3x for DO Press RIGHT key button We need to change from P1 heating to Heat start Press OK button and then DOWN key 9x Press OK button 2x After activating the function you must restart the unit ...

Страница 134: ...hown one step before Press LEFT key 2x for menu Inputs Outputs Press DOWN key 6x for menu Heating Press RIGHT key button Now press OK button and DOWN key button Menu should be displayed Electric and press OK button Configuration for Electric heater is complete Press LEFT 2x Press UP key button 7x to return to main screen ...

Страница 135: ...10 6 Electric wiring diagram ...

Страница 136: ...11 7 2 phase electric heater diagram type MTXL ...

Страница 137: ...12 8 3 phase electric heater diagram type MTXL ...

Страница 138: ...ulation elements On FGT010 is minimum air velocity 550 m3 h Presostat must be set on 70 Pa On FGT015 is minimum air velocity 750 m3 h Presostat must be set on 120 Pa On FGT022 is minimum air velocity 1100 m3 h Presostat must be set on 250 Pa You will have place for mounting presostat near electric cabinet marked with red rectangle picture below and connect it with pressure hose from sensor to on p...

Страница 139: ...hat you need to increase airflow in case if you have set point under minimum airflow To confirm an alarm press OK button and enter the password 1111 and Acknowledge If the alarm is active and there is no Returned written then is probably still too hot in area of electric heater Wait 15min and if sign Returned appear then use solution from above If there is still alarm active after 15min then is pr...

Страница 140: ...INSTRUCTIONS FOR SMOKE DETECTOR CORRIGO CONTROLLER Basic FGT010 FGT015 FGT022 ...

Страница 141: ...2 Contents 1 Basic information 3 2 Wiring 4 ...

Страница 142: ...3 1 Basic information On FGT Basic is only allowed to install smoke detector KRM 1 which is power supply over 230V AC ...

Страница 143: ...is for power supply 230V AC and terminal block 34 and 35 are signal from smoke detector which tell controller that we need to shut down the AHU In factory there will be a bridge between terminal block 34 and 35 in case that customer don t want a smoke detector function If there is NO smoke or fire the relay K4 must be activated ...