FDS-3G…OF
Damper Inspection
The activation mechanism keeps the dampers on stand-by during their entire life cycle in accordance with this manual
issued by the manufacturer. It is not permitted to alter the dampers in any way nor perform any changes to their
structure without the manufacturer’s consent. The operator performs regular checks of the dampers as per established
regulations and standards at least once every 12 months. The check needs to be performed by an employee who has
been specifically trained for this purpose. The current fire damper condition determined during the inspection needs to
be entered into the operating logbook along with the date of the inspection, the legible name, surname and signature
of the employee who performed the inspection. The Operating Journal includes a copy of the employee’s authorization.
If any discrepancies are discovered, these need to be entered in the Operating Journal along with a proposal for their
removal. The Operating Journal can be found in product documents section. Immediately after the installation and
activation of the damper, it needs to be checked under the identical conditions as apply to the above mentioned 12-
month inspections. The visual check ensures that visible damages on the inspected damper parts are seen. On its
external side, the damper housing and the activation mechanism are checked. Due to the need to perform a visual
check of the damper’s internal parts, open the inspection lid. For small sizes there is the possibility of removing the
mechanism to perform the inspection. The removable mechanism always needs to be returned back into the damper
with the damper blade being closed.
The damper’s internal casing, thermal fuse, sealings, foaming substance, the damper blade condition, and accuracy of
its closure during its leaning against the backstop in the closed position must all be checked. There must not be any
strange objects or a layer of impurities from the air distribution systems inside the damper.
Recommended Inspection Steps According to the EN 15 650:
Damper identification
Date of inspection
Inspecting electric connection of the activation mechanism (where applicable)
Inspecting damper for cleanliness and possible need for cleaning (where needed)
Inspecting blade and sealing condition, possible correction and logging (where needed)
Inspecting proper fire damper closure
Inspecting damper functionality – opening and closing using the control system, physical examination of the damper’s
behavior, possible correction and logging (where needed)
Inspecting end switches’ functionality in the open and closed position, possible correction and logging (where needed)
Inspect whether the damper is fulfilling its role as part of the regulation system (where needed)
Inspect whether the damper remains in its standard operating position.
The damper is usually part of a system. In that case the whole system needs to be checked as described in its
operation and requirements published by the builder of the system.
Содержание FDS-3G H0-OF Series
Страница 1: ...FDS 3G OF Overflow Fire Damper FDS 3G ...
Страница 14: ...14 49 FDS 3G OF Free area Dimensions Dimensions FDS 3G OF 200 x 200 up to 1200 x 800 ...
Страница 15: ...15 49 FDS 3G OF Weights Overhangs ...
Страница 18: ...18 49 FDS 3G OF Installation Methods ...
Страница 21: ...21 49 FDS 3G OF ...
Страница 25: ...25 49 FDS 3G OF ...
Страница 29: ...29 49 FDS 3G OF ...
Страница 32: ...32 49 FDS 3G OF ...
Страница 34: ...34 49 FDS 3G OF ...
Страница 49: ...Systemair DESIGN 2020 10 23 HandBook_FDS_3G_OF_en GB 8519DCD0 0720 11EB DCA1 21ABDD8D93BC ...