20/49 |
FDS-3G…OF
Installation 1 - Wet
Using Plaster/Mortar/Concrete Filling
Important: Use support inside the damper when adding filling. The weight of the filling can damage or bend the
damper casing.
The supporting construction opening must be prepared as depicted. Opening surfaces must be even and cleaned off.
The flexible wall opening must be reinforced as per the standards for plasterboard walls. The opening dimensions are
driven by the nominal dimensions of the damper with added clearance. For rectangular dampers, the opening will be
with the dimensions of W1 and H1.
Insert the closed damper into the middle of the opening so that the damper blade is in the wall. Use the bendable
hanger (2; or hangers) to secure the damper against the wall using a suitable screw (F1; recommended screw diameter
5,5; e.g. DIN7981).
For damper widths greater than 800 mm, it is recommended to use a duct support inside the damper to avoid any
damage, bend to the damper housing from the weight of the filling.
Fill in the area between the wall and the damper with plaster or mortar or concrete filling (2), while paying attention to
prevent the fouling of the damper’s functional parts, which could limit its correct functionality. The best way is to cover
the functional parts during installation. The seepage of the filling material can be prevented by using boards. However,
these are not required for wet installation.
First let the plaster or mortar or concrete filling harden and then perform the next steps!
After the filling hardens, remove the duct support from inside of the damper.
If needed, uncover and clean the damper after installation.
Check the damper’s functionality
Installation - Standard Distances
According to the standard EN 1366-2, the minimum distance from the wall or ceiling to the damper body is 75 mm. For
multiple crossings through a fire resistive wall the minimum distance between two damper bodies is 200 mm. This
applies for distances between the damper and a nearby foreign object crossing the fire resistive wall.
Installation - Smaller Distances, Maximum resistivity reduced to EI90S
The distance between individual fire dampers can be reduced to 60 mm, measured from surface to surface of the
housing and the distance between the surface of the damper installed in the duct and the adjacent supporting
construction (wall/floor) can be reduced to 40 mm, provided that the fire resistance classification will be reduced as
follows: EI90 (ve i <-> o) S.
Installation in a Wall thinner than tested
Installation in a thinner wall is allowed under the condition that an additional layer/layers of fire protective board are
fixed to the surface of the wall in order to achieve the same length of damper penetration seal as was tested. The
minimum width of added boards around the damper is 200 mm. In addition, the alternative thinner wall should be
classified in accordance with EN 13501-2:2007 + A1: 2009 for fire resistance required for product application. For a
protruding wall, the additional layers must be fixed on the steel supporting construction of the wall.
Содержание FDS-3G H0-OF Series
Страница 1: ...FDS 3G OF Overflow Fire Damper FDS 3G ...
Страница 14: ...14 49 FDS 3G OF Free area Dimensions Dimensions FDS 3G OF 200 x 200 up to 1200 x 800 ...
Страница 15: ...15 49 FDS 3G OF Weights Overhangs ...
Страница 18: ...18 49 FDS 3G OF Installation Methods ...
Страница 21: ...21 49 FDS 3G OF ...
Страница 25: ...25 49 FDS 3G OF ...
Страница 29: ...29 49 FDS 3G OF ...
Страница 32: ...32 49 FDS 3G OF ...
Страница 34: ...34 49 FDS 3G OF ...
Страница 49: ...Systemair DESIGN 2020 10 23 HandBook_FDS_3G_OF_en GB 8519DCD0 0720 11EB DCA1 21ABDD8D93BC ...