background image

2

fantech

Note

Warning /

Important 

note

Information

Technical 

information

Practical tip

1.    Use this unit in the manner intended by the 

manufacturer. If you have any questions, 
please contact the manufacturer.

2.    Before servicing or cleaning unit, switch 

power off at service panel and lock the 
service disconnecting means to prevent 
power from being switched on accidentally. 
When the service disconnecting means 
cannot be locked, securely fasten a 
prominent warning device, such as a tag, 
to the service panel.

3.    Installation work and electrical wiring must 

be done by qualified person(s) in 
accordance with all applicable codes and 
standards, including fire-rated 
construction.

4.    Sufficient air is needed for proper 

combustion and exhausting of gases 
through the flue (chimney) of fuel burning 
equipment to prevent back drafting. Follow 
the heating equipment manufacturer’s 
guideline and safety standards such as 
those published by the National Fire 
Protection Association (NFPA), and the 
American Society for Heating, Refrigeration 
and Air Conditioning Engineers (ASHRAE), 
and the local code authorities.

5.    When cutting or drilling into wall or ceiling, 

do not damage electrical wiring and other 
hidden utilities.

6.    Ducted fans must always be vented to the 

outdoors.

7.    If this unit is to be installed over a tub or 

shower, it must be marked as appropriate 
for the application and be connected to a 
GFCI (Ground Fault Circuit Interrupter) – 
protected branch circuit.

8.    NEVER place a switch where it can be 

reached from a tub or shower. 

9.   This fan must be properly grounded.

10.  Do not use in the cooking area (Figure. 1).

11.  Do not block the air intakes or exhaust.

12.   Power supply wiring is to be No. 14 AWG 

wire or larger (suitable for at least 90°C 
(190°F) ).

13.  Not for use outdoors.

14.   The fan must not be installed in a ceiling 

with an “R” rating greater than 40.

15.  The fan is type IC (Inherently Protected).

16.   To reduce the risk of injury, install the fan 

at least 7 feet (2.1m) above the floor.

17.   Acceptable for use over a shower or tub 

when installed in a GFCI protected branch 
circuit.

18.   The fan should not be turned on or off 

rapidly.

19.   Do not clean the fan with corrosive 

chemicals or water in excess of 60° C 
(140° F).

20.   If the fan is not operating properly, shut 

the power off immediately, and have a 
certified installer inspect it and have it 
serviced as required.

21.   Fan must be mounted to structural 

members that are strong enough to 
support the fan’s weight.

22.   Do not allow foreign objects to enter the 

fan; this could result in electric shock or 
fan damage.

Caution:

1.    For general ventilating use only. Do not use 

to exhaust hazardous or explosive 
materials and vapors.

2.    This product is designed for installation in 

flat ceilings only. Do not install it in a 
sloping ceiling or in a wall.

3.    To avoid motor bearing damage and noisy 

unbalanced impellers keep construction 
material / dust from entering the fan.

4.    Please read specification label on the 

product for further information and 
requirements.

Figure 1

Cooking area

Do not install above or 

inside this area

45°

45°

Floor

Cooking 

Equipment

Read and Save these instructions for future reference. 
Before installation, to reduce the risk of fire, electric shock, or injury to persons, observe the following:

Содержание fantech ProPLUS Series

Страница 1: ...imiento y humeda Package includes Fantech Exhaust Fan 1 pc EZ Mounting Bracket 1 pc Mounting screws 7 pcs L ensemble comprend Ventilateur extracteur ou ventilateur à éclairage Fantech 1 pc Supports de fixation 1 pc Vis de fixation 7 pcs El paquete incluye Extractor de aire o un extractor con luces Fantech 1 pc Ménsulas de montaje 1 pc Tornillos de montaje 7 pc Technical Customer Support United Sta...

Страница 2: ...wer 9 This fan must be properly grounded 10 Do not use in the cooking area Figure 1 11 Do not block the air intakes or exhaust 12 Power supply wiring is to be No 14 AWG wire or larger suitable for at least 90 C 190 F 13 Not for use outdoors 14 The fan must not be installed in a ceiling with an R rating greater than 40 15 The fan is type IC Inherently Protected 16 To reduce the risk of injury insta...

Страница 3: ...it être adéquatement mis à la terre 10 Ne pas utiliser dans une aire de préparation de repas Figure 1 11 Ne pas bloquer les entrées ou les évacuations d air 12 Le câblage d alimentation électrique doit être de calibre nº 14 AWG ou plus gros adéquat pour au moins 90 C 190 F 13 Ne doit pas être utilisé à l extérieur 14 Pour les unités à éclairage utiliser uniquement des lampes fluorocompactes de typ...

Страница 4: ...utilizar en el área usada para cocinar figura 1 11 No bloquee las entradas ni la salida de aire 12 Las conexiones de alimentación deben realizarse con cables calibre 14 AWG o más gruesos aptos para al menos 90 C 13 No apto para uso externo 14 En las unidades con luces utilice únicamente una lámpara CFL tipo T4 de 26 W y una lámpara de noche de 4 W como máximo 15 El extractor no debe instalarse en ...

Страница 5: ...ie W Débit d air pi3 min Puissance Moteur ProPLUS 120V 60 Hz 25 80 90 110 140 ProPLUS L 120V 60 Hz 30 80 90 110 140 Especificaciones del extractor Modelo Consumo de energía W Flujo de aire CFM Alimentación Motor ProPLUS 120V 60 Hz 25 80 90 110 140 ProPLUS L 120V 60 Hz 30 80 90 110 140 Spécifications Especificaciones 7 5 8 11 3 8 10 1 2 13 13 3 4 289 mm 267 mm 350 mm 330 mm 194 mm 11 3 8 10 1 2 7 5...

Страница 6: ...d blower assembly before installation EZ mounting frame Housing Duct Assembly Blower Assembly 1 Install EZ Mounting Frame 2 Install Duct And Housing Attach duct assembly to frame using provided 1 1 4 screw Before inserting the housing first pull the locking tab located opposite of the duct collar and push housing into the frame Release the locking tab so that it temporarily holds the housing in pl...

Страница 7: ... can reduce energy loss and inhibit mold growth Fans installed with existing ducts may not achieve their rated air flow Wiring diagram Run 120 Vac house wiring to the location of the fan Use only UL approved connectors not included to attach the field wiring to the wiring plate Refer to the wiring diagram and connect the wires as shown Install the Grille To attach the grille assembly to the fan ho...

Страница 8: ...ERATION The humidity sensing fan uses a sophisticated humidity sensor that responds to a rapid to moderate user adjustable increases in humidity or b humidity above a user adjustable set point 50 100 relative humidity The fan run continuously at a preset lower level set by the low speed control Knob and automatically boost up to high speed when environmental conditions change After delay timer 20 ...

Страница 9: ...existants peuvent ne pas atteindre leur débit d air nominal Retirer l ensemble pour conduit et l ensemble souffleur avant de procéder à l installation Cadre de montage EZ Boîtier Ensemble pour conduit Ensemble souffleur 1 Installer le cadre de montage EZ 2 Installer le conduit et le boîtier Installer le conduit dans le cadre et le fixer avec des vis Tirer la patte dans le boîtier presser le boîtie...

Страница 10: ... réduire la perte d énergie et empêcher la formation de moisissure Les ventilateurs installés avec des conduits existants peuvent ne pas atteindre leur débit d air nominal Schéma de câblage Brancher le câblage du boîtier 120 V c a à l emplacement du ventilateur Utiliser uniquement des connecteurs homologués UL non inclus pour raccorder le câblage in situ à la plaque de câblage Consulter le schéma ...

Страница 11: ... D HUMIDITÉ Le ventilateur à capteur d humidité est doté d un capteur d humidité sophistiqué qui détecte a les augmentations rapides ou modérées réglable par l utilisateur du taux d humidité ou b les taux d humidité inférieurs à une valeur réglable par l utilisateur 50 à 100 d humidité relative Le ventilateur fonctionne en continu à une vitesse inférieure préréglée réglage au moyen du bouton du ca...

Страница 12: ...uctos ya existentes no alcancen su flujo de aire nominal Retire el conjunto del ducto y el del soplador antes de la instalación Bastidor de montaje EZ Carcasa Conjunto del ducto Conjunto del soplador 1 Instalar el bastidor de montaje EZ 2 Instalar el ducto y la carcasa Conecte el ducto al bastidor y fíjelo con tornillos Tire de la lengüeta de la carcasa empuje la carcasa hacia el interior del bast...

Страница 13: ...res instalados con ductos ya existentes no alcancen su flujo de aire nominal Diagrama de cableado Extienda cables para instalaciones domiciliarias de 120 V CA hasta la ubicación del ventilador Utilice solamente conectores aprobados por UL no incluidos para conectar el cableado de campo a la placa de cableado Consulte el diagrama de cableado y conecte los cables tal como se indica Instalar la parri...

Страница 14: ...a un sofisticado sensor de humedad que responde a lo siguiente a incrementos rápidos a moderados lo puede ajustar el usuario en la humedad o b un nivel de humedad que supera el punto de referencia que puede ajustar el usuario entre 50 y 100 de humedad relativa El ventilador funciona continuamente al nivel más bajo predefinido establecido por la perilla del sensor de humedad y pasa automáticamente ...

Страница 15: ...tallation for any breach of warranty WARRANTY VALIDATION The user must keep a copy of the bill of sale to verify purchase date These warranties give you specific legal rights and are subject to an applicable consumer protection legislation You may have additional rights which vary from state to state This warranty does not apply to any Fantech product or part which has failed as a result of faulty...

Страница 16: ... d usine en matière de qualité d exécution ou de matériau Il sera peut être nécessaire de retourner le produit à l usine Fantech accompagné d une copie du contrat de vente et du numéro d autorisation de retour POUR RETOURNER UN PRODUIT À L USINE VOUS DEVEZ Obtenir un numéro d autorisation de retour pour ce faire communiquer avec Fantech aux États Unis au numéro 1 800 747 1762 ou au Canada au numér...

Страница 17: ... instalación o reinstalación por incumplimiento de la garantía VALIDACIÓN DE LA GARANTÍA El usuario debe conservar una copia de la constancia de compraventa para verificar la fecha de compra Estas garantías le otorgan derechos legales específicos y están sujetas a una legislación aplicable para protección del consumidor Usted puede tener derechos adicionales que varían de estado en estado Esta gar...

Страница 18: ...ng Frame Cadre de montage EZ Bastidor de montaje EZ 1 4 Blower assembly Ensemble souffleur Conjunto del soplador 1 5 Housing Boîtier Carcasa 1 6 Duct assembly Ensemble pour conduit Conjunto del ducto 1 7 Power box Boîtier d alimentation Caja de alimentación 1 8 Sensor Capteur Sensor 1 a Screw Vis Tornillo 5 WARNING Ensure that the fan is disconnected before replacing 1 8 2 3 4 5 a a 7 6 1 8 MISE E...

Страница 19: ...Notes Notas ...

Страница 20: ... Fantech Fantech se réserve le droit de faire des changements techniques Pour de la documentation à jour s il vous plaît se référer au www fantech net Fantech se reserva el derecho de hacer modificaciones técnicas en cualquier momento Para obtener la documen tación actualizada por favor consulte www fantech net ...

Отзывы: