37/49 |
F-R60
Type of Activation BST0
• The actuator and the control module are factory wired.
• Connect the supply voltage to the connecting cable (approx. 1 m, with ferrules).
• Switch off the power supply before working on any electrical equipment.
• Only qualified electricians are permitted to work on the electrical system.
• This type of activation comes with a Belimo communication and power supply unit BKN230-24 (other communication
units on demand).
• Actuator power supply: AC (50/60 Hz)/DC 24 V
Two LEDs in the device indicate the function status
LED / Status / Function
Yellow / Flashing / Damper moves OPEN
Yellow / On / Damper OPEN
Green / Flashing / Damper moves CLOSED
Green / On / Damper CLOSED
Yellow and Green / Flashing at double frequency / Fault
Yellow and Green / Off / Power failure
Notes:
• Caution! Main power supply voltage!
• Parallel connection of several actuators possible.
• Power consumption and switching thresholds must be observed!
• Combination of power supply voltage and safety extra-low voltage not permitted at both auxiliary switches.
Legend
1)
- Jumper factory-fitted. Can be removed if necessary to be replaced by a thermoalectric trip (the safety function will
be triggered if terminals 1 and 2 are not linked).
2)
- Jumper only used for commissioning purposes and without BKS24-..!
3)
- 2-wire conductor to BKS24-...