38
8 - Technical Data (continued)
AQWH STD/HSE/HPF - BLN models
1404
1604
1806
2106
2406
Power supply
V/Ph/Hz
400 (±10%)/3/50
Number of refrigerant circuits
2
2
2
2
2
Refrigerant charge
kg
47 + 47
52 + 52
61 + 61
78 + 61
78 +78
Total capacity steps
%
21-50-71-100
25-50-75-100
17-33-50-67-83-100 15-29-43-62-81-100 17-33-50-67-83-100
COMPRESSORS
Number
4
4
6
6
6
Type
Scroll
Oil type
POE
N° of loading stages
0/100
0/100
0/100
0/100
0/100
EVAPORATOR
Number
1
1
1
1
1
Type
PLATE
PLATE
PLATE
PLATE
PLATE
Water volume
l
33
35
38
38
40
AIR COOLED CONDENSER
Number of coils
4
4
4
4
4
Total coil face area per coil
m²
4.4
4.4
5.6
6.7
6.7
FANS
Number of fans
8
8
10
10
12
Nominal speed
rpm
880
880
880
880
880
Total airflow
m³/h
181000
181000
200000
214500
242000
Total input power
kW
14.4
14.4
18.0
18.0
21.6
Total input power
(*)
kW
13.0
13.0
16.3
16.3
19.6
External static pressure
Pa
0 or 120 Pa
(**)
WEIGHT
Shipping weight
kg
2896
3018
3967
4083
4465
Operating weight
kg
2931
3056
4007
4123
4507
ADDITIONAL WEIGHT
HSE version
kg
0
0
0
0
0
HPF version
kg
0
0
0
0
0
Desuperheater version
kg
Please consult factory
With pump/s
kg
See following table
With pump/s and tank
kg
Copper Fins
kg
Please consult factory
SOUND LEVELS
Sound power level
(1)
dB(A)
97
97
98
98
99
Sound pressure level - (10m)
(2)
dB(A)
65
65
66
66
67
DIMENSIONS
Length
mm
4000
4000
5000
6000
6000
Width
mm
2200
2200
2200
2200
2200
Height
mm
2550
2550
2550
2550
2550
(1)
Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744 and Eurovent 8/1.
(2)
Sound pressure level values refer to ISO standard 3744, parallelepiped shape.
(*)
High efficiency units (HSE) with inverter fans.
(**)
HPF units with high static pressure fans.
Note:
Refrigerant charge data are indicative only. Always refer to data shown on the unit nameplate.