Version
Document
Preliminary 003
Access V4.X Configuration manual
6 (33)
2019-05-13
28k8 bps
28800bps
38k4 bps
38400bps
57k6 bps
57600bps
76k8 bps
76800bps
115k2 bps
115200bps
Cloud
Cloud function must be enabled if the controller shall access “Systemair
Connect” cloud service. The
provided serial number is unique identification of the controller and must be entered upon request
while registering at “Systemair Connect”.
Configuration > System settings > Communication > Cloud >
BACnet
BACnet/IP shall be enabled if controller is connected to BMS via this protocol. The following entries
include device name and BACnet communication related settings.
Communication devices
Configuration > System settings > Communication devices >
The Access controller supports up to 20 devices connected via communication BUS (Modbus and
EXOline).
Only limited number of predefined device models is supported.
List of supported brands and models:
Device
type
Fan / FC
(Modbus)
Rotary
exchanger
(Modbus)
Pressure transmitter
(Modbus / EXOline)
Actuator
(Modbus)
Expansion unit
(EXOline)
Model Vacon
RHC200
PDTxxC (Modbus)
Belimo
E8
Lenze
IBC VariMax
PDTxxC-2 (Modbus)
Emerson
HK DPT-Dual-MOD-
2500 (Modbus)
LS iG5A
PDTxxC (EXOline)
E15
LS iS7
PDTxxC-2 (EXOline)
E28
EBM-PAPST
DANFOSS FC101
ABB ACSxxx
Ziehl blue
Configuration > System Settings > Communication devices > Device (n) > Address >
Modbus devices on the bus must have unique address assigned. The address shall be the same as set in
the device. The device shall also hold the same message format and baud rate settings as the port it is
connected to (see
port function
).
Function