Version
Document
Preliminary 003
Access V4.X Configuration manual
22 (33)
2019-05-13
Data & Settings > Demand Control > Free cooling > Time to block heat output after free cooling
>
Pretreatment
Configuration > Functions > Function Activation > Pretreatment > “Yes”
Pretreatment activation during free cooling
Configuration > Functions > Pretreatment >
Control of dampers and pump for preheated or pre-cooled outdoor air via an underground intake
chan
nel. The digital output ”Pretreatment” is set to preheating when the unit is started and the outdoor
temperature is below the set heating start limit (default 8°C) or to precooling when the outdoor
temperature is above the set cooling start limit (default 19°C).
If the outdoor temperature exceeds the set heating start limit by more than 1°C (fixed), preheating will
be aborted, as well as if the outdoor temperature falls below the cooling start limit by 1°C.
If a sensor is configured in the intake duct (”intaketemp”) this temperature will be compared with the
outdoor temperature. If the temperature in the intake duct does not exceed the outdoor temperature
by more than 1°C (adjustable) 5 minutes (adjustable) after start-up when using preheating, preheating
will be aborted. The same conditions apply to precooling, i.e. if the intake temperature is not more than
1°C (adjustable) cooler than the outdoor temperature, precooling will be aborted.
Pretreatment always starts at start-up of the unit, if the outdoor temperature so permits. If
pretreatment is aborted due to a small difference between the intake temperature and the outdoor
temperature, pretreatment will be blocked for 6 hours. Then pretreatment will start (if the outdoor
temperature so permits) and run for at least 5 minutes (adjustable)
Data & Settings > Temperature control > Pretreatment>
Summer/winter mode
In addition to normal temperature setpoint, the additional setpoint for summer time can be activated
Configuration > Functions > Temperature control >
Summer/Winter mode > “Yes”
Options for switching the modes include schedule, changeover, digital input or outdoor temperature
setpoint.
Configuration > Functions > Temperature control > Summer/Winter mode > Type of switch
summer/winter
The second Supply, Extract or Room temperature setpoint then will be available (depends on
temperature control type.
Supply: Data & Settings > Temperature control > Supply air controller > Setpoint summer supply
air >
Extract: Data & Settings > Temperature control > Extract air controller > Setpoint summer
extract air >
Room: Data & Settings > Temperature control > Room controller > Setpoint summer room >