TROUBLESHOOTING

Problem

Causes

Solutions

Air is too dry

Dehumidistat control is set too low

Increase the desired level of humidity. Change ventilation mode from 
continuous mode to standby.

HRV out of balance

Have contractor balance HRV airflows

Air is too humid

Dehumidistat control is set too high

Reduce the desired level of humidity. Combine this with the use of continuous 
exchange mode.

Sudden change in temperature

Wait until outside temperature stabilizes (winter). Heating will also improve 
situation.

Storing too much wood for heating

Store a majority of your wood outside. Even dried, a cord of wood contains 
more than 20 gallons of water.

Dryer vent exhaust is inside home

Make sure the dryer vent is exhausting outside.

Poor air circulation near windows

Open curtains or blinds.

HRV out of balance

Have contractor balance HRV airflows

Well sealed basement door is closed

Open the door or install a grill on the door.

Failed damper system may be stuck in recirculation 

mode

Check defrost damper. If damper is always blocking incoming fresh air, have 
contractor verify damper system.

Persistent condensation
on window

Improper adjustment of dehumidistat control

Reduce the desired level of humidity. Combine this step with use of continuous 
exchange mode.

HRV out of balance

Have contractor balance HRV

Poor air circulation near windows

Open curtains or blinds.

Poor Air Flows

1/4" (6mm) mesh on the outside hoods is plugged

Clean exterior hoods or vents

Filters plugged

Remove and clean filter

Core obstructed

Remove and clean core

Indoor grilles closed or blocked

Check and open grilles

Inadequate power supply at site

Have electrician check supply voltage

Ductwork is restricting airflow

Check duct installation

Improper speed control setting

Increase the speed of the HRV (i.e. change unit control from REDUCED to NORMAL 

speed)

HRV airflow improperly balanced

Have contractor balance HRV airflows

Ducting has fallen down or been disconnected from HRV

Have contractor reconnect ducting

Supply air feels cold

Poor location of supply grilles, the airflow may irritate 

the occupant

Locate the grilles high on the walls or under the baseboards, install ceiling
mounted diffuser or grilles so as not to directly spill the supply air on the 
occupant (eg. Over a sofa) 
Turn down the HRV supply speed. A small duct heater (1kw) could be used to 
temper the supply air
Placement of furniture or closed doors is restricting the movement of air in 
the home

Outdoor temperature extremely cold

If supply air is ducted into furnace return, the furnace fan may need to run 
continuously to distribute ventilation air comfortably

HRV and/or Ducts frosting up

HRV air flows are improperly balanced

Have HVAC contractor balance the HRV airflows

Malfunction of the HRV defrost system

Note: minimal frost build-up is expected on the core before unit initiates 

defrost cycle functions

Condensation or Ice Build Up in 
Insulated Duct to the Outside

Incomplete vapor barrier around insulated duct

Tape and seal all joints

A hole or tear in outer duct covering

Tape any holes or tears made in the outer duct covering 
Ensure that the vapor barrier is completely sealed.

LED is flashing

Everything is in good operations

LED is not flashing

No Power is being transmitted to the Control Board

Make sure unit is plugged.
Transformer may need replacing.

Note:

 It is best to get the unit checked by a certified HVAC Contractor/Technician.

Содержание 427212

Страница 1: ...ght to modify at any time and without notice any or all of its products features designs components and specifications to maintain their technological leadership position Please visit our website www...

Страница 2: ...combustion equipment i e Gas Furnaces Oil Furnaces Wood Stoves etc Products are designed and manufactured to provide reliable performance but they are not guaranteed to be 100 free of defects Even rel...

Страница 3: ...on 8 Installing the ducting to the weatherhood 8 INTERIOR DUCTING INSTALLATION General Tips 9 Installing duct to HRV 9 Supply Exhaust Air Grilles Location 9 HRV INSTALLATION 10 AIRFLOW ADJUSTMENT BALA...

Страница 4: ...53 25 60 28 501 1000 47 93 45 21 53 24 60 28 68 31 75 35 1001 1500 94 139 60 28 68 31 75 35 83 38 90 42 1501 2000 140 186 75 35 83 38 90 42 98 45 105 49 2001 2500 187 232 90 42 98 45 105 49 113 52 120...

Страница 5: ...eas of the home requiring local exhaust bathroom kitchen laundry room 2 Fresh air is distributed directly to habitable rooms in the house bedrooms living room 3 The HRV s airflow must be balanced afte...

Страница 6: ...ly or interconnected with HRV See furnace electrical connection on page 16 2 Stale air is drawn from key areas of the home bathroom kitchen laundry room 3 Fresh air is supplied to the return air plenu...

Страница 7: ...r to prevent exhausting any fresh air the HRV s exhaust air connection should be upstream of the HRV s supply air connection when ducting to the furnace s cold air return 4 Due to the difference in pr...

Страница 8: ...iner which acts as a vapor barrier must be completely sealed to the outer wall and the HRV using tape and or caulking A good bead of high quality caulking preferably acoustical sealant will seal the i...

Страница 9: ...e duct to prevent leakage between the ducting and the duct connection In the case of solid ducting slide duct over duct connection screw in place and seal SUPPLY AIR GRILLES LOCATION In homes without...

Страница 10: ...fan Central vacuum system Bathroom exhaust fans unless they are specifically designed for this purpose These appliances may cause lint dust or grease to collect in the HRV damaging the unit Connecting...

Страница 11: ...int A P trap should be made in the drain line This will prevent odors from being drawn back up into the unit 2 Invert the drain nipple Make sure to place gasket between the unit and the drain nipple i...

Страница 12: ...perating at normal speed during the balancing sequence When reading with a mechanical type manometer Magnehelic make sure the manometer is placed on a level surface For optimal performance HRV unit sh...

Страница 13: ...w may affect the other airflow as well It is recommended to check each airflow again to make sure the value did not change dramatically during the balancing procedure Make adjustments as necessary The...

Страница 14: ...idity range and ventilation mode for day and night conditions No battery to replace all programmed settings are retained during power outage Maintenance reminder indicator Error code messages reduce t...

Страница 15: ...GRAM VHR150R HIGH SPEEDS LOW V 5 5 JP5 JP3 V 5 7 120V 90V LOW JP3 JP5 HIGH 120V 90V 75V 55V SPEEDS Wiring diagram of complete unit inside of access panel Observe polarity on all accessory controls whe...

Страница 16: ...CTION TO A COOLING SYSTEM On some newer furnaces and older thermostats energizing the R and G terminal at the furnace has the effect of energizing the Y at the thermostat and thereby turning on the co...

Страница 17: ...power supply at site Have electrician check supply voltage Ductwork is restricting airflow Check duct installation Improper speed control setting Increase the speed of the HRV i e change unit control...

Страница 18: ...al damages incurred in the use of the ventilation system Fantech is not responsible for providing an authorized service centre near the purchaser or in the general area Fantech reserves the right to s...

Страница 19: ...nt ou enti rement en tout moment et sans pr avis les caract ristiques la conception les composants et les sp cifications de ses produits afin de conserver sa position de leader de technologie S il vou...

Страница 20: ...auffage vacuation fournaise gaz fournaise mazout po le bois etc Les produits sont con us et fabriqu s pour fournir une performance fiable mais ils ne sont pas garantis 100 sans d faut M me les produit...

Страница 21: ...de l ensemble des conduits avec hottes 26 INSTALLATION DES CONDUITS INT RIEURS Conseils pratiques 27 Installation des conduits sur le VRC 27 Emplacement des grilles d approvisionnement et d vacuation...

Страница 22: ...n L s Pi3 min L s 500 47 30 128 38 18 45 21 53 25 60 28 501 1000 47 93 45 21 53 24 60 28 68 31 75 35 1001 1500 94 139 60 28 68 31 75 35 83 38 90 42 1501 2000 140 186 75 35 83 38 90 42 98 45 105 49 200...

Страница 23: ...st aspir partir des endroits cl s de la maison salle de bains cuisine buanderie 2 L air frais est distribu parmi les pi ces habitables chambres coucher salon 3 Le d bit d air du VRC doit tre confirm s...

Страница 24: ...n lectrique de la fournaise la page 34 2 Air vici est aspir des endroits cl s de la maison salle de bain cuisine buanderie 3 L air frais est fourni au pl num de retour d air de la fournaise 4 En raiso...

Страница 25: ...ation d air frais la connexion d vacuation du VRC devrait tre situ e en amont de la connexion d approvisionnement du VRC lorsqu on les branche la bouche de reprise d air de la fournaise 4 En raison de...

Страница 26: ...pl tement scell sur le mur ext rieur et le VRC l aide de ruban ou de produit de calfeutrage D posez un cordon de produit de calfeutrage de premi re qualit du mastic d isolation acoustique de pr f renc...

Страница 27: ...des crochets Ensuite installez un attache c ble par dessus le conduit flexible afin de pr venir des fuites entre le conduit et le collet Dans le cas d un conduit galvanis faites le glisser sur le col...

Страница 28: ...lateur de cuisini re Syst me d aspirateur central Ces lectrom nagers peuvent entra ner l accumulation de charpie de poussi re ou de graisse dans le VRC et l endommager Assurez vous d avoir une source...

Страница 29: ...s un siphon en P dans un tuyau d coulement Ce siphon emp che le retour des odeurs vers l appareil 2 Inverser le raccord de vidange Assurez vous de placer le joint entre l unit et le raccord de vidange...

Страница 30: ...anom tre analogique Magnehelic assurez vous que le manom tre est plac sur une surface plane Afin d assurer une performance optimal le VRC devrait tre r quilibr apr s toute r novation majeure ou apr s...

Страница 31: ...age d un d bit d air peut affecter le d bit d autres aussi Il est donc recommand de v rifier chaque d bit d air nouveau pour s assurer que la valeur n a pas changer consid rablement Faites les ajustem...

Страница 32: ...ment pr c dent EDF1 EDF1R Appuyez le bouton pour une vitesse r duite continuelle Appuyez le bouton une seconde fois l appareil fera un cycle de 20 minutes ON 40 minutes OFF et r p ter EDF1 Appuyez le...

Страница 33: ...P3 V 5 7 120V 90V LOW JP3 JP5 HIGH 120V 90V 75V 55V SPEEDS Sch ma lectrique de l appareil au complet situ l int rieur du paneau d acc s Respectez la polarit sur tous les accessoires de contr les Le ca...

Страница 34: ...ion de la borne Y du thermostat et cons quemment la mise sous tension du syst me de refroidissement Si votre syst me est muni d un tel type de thermostat vous devez respecter le c blage de verrouillag...

Страница 35: ...cacit du VRC V rifiez le r seau de conduits Mauvais r glage de la commande de vitesse Augmentez la vitesse du VRC i e changez la vitesse de l appareil de vitesse R DUITE vitesse NORMALE avec le contr...

Страница 36: ...nu de respecter tous les codes en vigueur dans sa r gion Les pi ces y compris les pi ces de rechange pos es ult rieurement sont garanties pendant 5 ans partir de la date d achat de l appareil Les mote...

Страница 37: ...val w Stop 413893 11 Collar 6 Oval wo Stop 413894 13 Damper Motor Assy Repl 426467 14 Damper Door Defrost Repl Kit 445199 Temperature Probe 40286 Door Assembly 445100 Kit Chain 404261 Kit Wall Bracket...

Страница 38: ...38 NOTES...

Страница 39: ...39 NOTES...

Страница 40: ...make technical changes For updated documentation please refer to www fantech net Fantech Fantech se r serve le droit de faire des changements tech niques Pour de la documentation jour s il vous pla t...

Отзывы: