6.1.2
To start the configuration wizard
A configuration wizard is available from software version 4.1.
By using the wizard, the following steps in
6.1.3 To activate the pressure control function
and
6.1.4 To allocate differential pres-
can be omitted.
Configuration > Configuration wizard
2022-08-29
Set up Pressure control
>
Configuration > Configuration wizard > Setup pressure control
2022-08-29
Analog outputs
Sensor range
Device
Position
Pressure supply air
0-500
1
Controller
AI4
Pressure extract air
0-500 Pa
Controller
AI5
Confirm In-/Outputs and complete setup >
1.
The set pressure range in the pressure transmitter.
1.
Select Configuration from navigation icons
2.
Select Configuration wizard
3.
Select Set up pressure control
4.
Set sensor range
5.
Select In-/Outputs
6.
Select Confirm In-/Outputs and complete setup
7.
Confirm and activate the selected configuration with Yes complete setup.
6.1.3
To activate the pressure control function
Configuration > Functions > Function activation
2022-08-29
Fan control type
Pressure
1.
Select Configuration from the navigation icons
2.
Select Functions
3.
Select Function activation
4.
Select Pressure as Fan control type.
6.1.4
To allocate differential pressure sensors
Note:
Observe the different IO settings for different Topvex units
Configuration > I/O allocation settings > Analog inputs
2022-08-29
Analog inputs
Device
Position
6