WfdeXP explosion Proof 
vane-type Waterflow detectors

insTaLLaTion and mainTenance insTrUcTions

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

imPorTanT

Please Read Carefully And Save

This instruction manual contains important information about the installation 
and operation of waterflow detectors. Purchasers who install waterflow detec-
tors for use by others must leave this manual or a copy of it with the user.

Read  all  instructions  carefully  before  beginning.  Follow  only  those  instruc-
tions that apply to the model you are installing.

CAUTION

Use  vane-type  waterflow  detectors  in  wet-pipe  systems  only.  Do  NOT  use 
them in dry pipe, deluge, or preaction systems. The sudden inrush of water in 
such systems may break the vane or damage the mechanism.

PrinciPLes of oPeraTion

Vane-type waterflow detectors mount to water-filled pipes in sprinkler systems. 
Waterflow  in  the  pipe  deflects  a  vane,  which  produces  a  switched  output–
usually after a specified delay. All waterflow detectors have a pneumatically 
controlled mechanical delay mechanism. Delays do NOT accumulate; they re-
set if the flow of water stops before the entire delay has elapsed. All switches 
actuate when the water flow rate is 10 gallons per minute or greater, but will 
not actuate if the flow rate is less than 4 gallons per minute. This System Sen-
sor installation manual covers the following waterflow detectors for sprinkler/
fire alarm applications.

Model

Pipe Size

(inches)

Pipe

Schedule

Max. Pressure

Rating (psig)

WFD20EXP

2

10 thru 40

450

WFD25EXP

2.5

10 thru 40

450

WFD30-2EXP

3

10 thru 40

450

WFD35EXP

3.5

10 thru 40

450

WFD40EXP

4

10 thru 40

450

WFD50EXP

5

10 thru 40

450

WFD60EXP

6

10 thru 40

450*

WFD80EXP

8

10 thru 40

450*

*Maximum Pressure Rating 400 psig as approved by Factory Mutual Research.

CAUTION

Do NOT use any of the WFD models on copper pipe. The clamping forces of 
the mounting bolts may collapse the pipe sufficiently to prevent the detector 
from functioning properly.

Do  NOT  install  steel  or  iron  pipe  sections  in  copper  piping  for  mounting  a 
waterflow detector. Incompatibility between the dissimilar metals causes bi-
metallic corrosion.

NOTE:

  Not  for  use  in  potable  water  systems,  systems  where  sand  or  other 

material is present or systems employing other than water.

sPecificaTions

Contact Ratings: 

10 A @ 125/250 VAC 

; 2.5 A @ 24 VDC 

Triggering Threshold Bandwidth (Flow Rate):  4 to 10 gpm
Static Pressure Rating: 

See models listed below

Dimensions (Installed): 

4.0 in H × 8.8 in W × 7.0 in D

Operating Temperature Range: 

32°F to 120°F (0°C to 49°C)

Compatible Pipe: 

Steel water pipe, schedule 10 or 40

Shipping Weight: 

According to size

Enclosure Rating: 

NEMA 4 indoor/outdoor use

  Hazardous Atmosphere Classification: 

Class I, Groups B, C, D Div, 1; Class II, Groups E, F, G Div. 1; Class III Div. 1

US Patent Number: 

5,213,205

insTaLLaTion GUideLines

Before installing any waterflow alarm device, be thoroughly familiar with:

NFPA 72: 

National Fire Alarm Code

NFPA 13: 

Installation of Sprinkler Systems, Section 3.17

NFPA 25: 

 Inspection, Testing and Maintenance of Sprinkler Systems, Section 
5.3.3.2

Other  applicable  NFPA  standards,  local  codes,  and  the  requirements  of  the 
authority having jurisdiction

NOTE:

 Installation methods other than those listed in this installation manual 

may prevent the device from reporting the flow of water in the event the asso-
ciated sprinkler system is activated by a fire. System Sensor is not responsible 
for devices that have been improperly installed, tested, or maintained.

1.   Mount the detector where there is adequate clearance for installation and 

removal and a clear view of it for inspections. See 

Figure 1

 for mounting 

dimensions.

2.  Locate to protect from damage – 6 to 7 feet above the floor.
3.   On horizontal runs, position the detector on the top or side of the pipe. 

Do not mount it upside down because condensation may collect in the 
housing and impair the operation of the detector. For vertical flow appli-
cations, mount the detector on pipe through which water flows upward. 
Otherwise, the unit may not operate properly.

4.   Mount the detector at least 6 inches from a fitting that changes the direc-

tion of water flow and no less than 24 inches from a valve or drain.

5.  Be sure the direction-of-flow arrow matches the direction of flow in the pipe.

CAUTION

Contact the appropriate personnel regarding the proper tools and procedures 
when installing this device in a “HAZARDOUS” area. Disconnect supply cir-
cuits before opening the cover, to reduce the chances of ignition of hazardous 
atmospheres. Secure the cover and cover screws prior to activating circuits. 
Tighten cover screws to 40 in. lbs. min.

moUnTinG insTrUcTions

1.  Drain the pipe.
2.   Cut a hole at the desired location. Center the hole in the pipe, as shown 

in 

Figure 2

, and be sure the hole is perpendicular to the center of the 

pipe. Before drilling, use a punch or scribe to mark the drill site to pre-
vent the bit from slipping. If the hole is off center, the vane will bind 
against the inside wall of the pipe. Use a drill or hole saw to cut a hole of 
the proper diameter. See 

Table 1

 for hole size.

CAUTION

When drilling the hole with a hole saw, make certain that the center of the cut 
does not remain in the pipe.

3.   Remove burrs and sharp edges from the hole. Clean and remove all scale 

and foreign matter from the inside of the pipe for one diameter on each 
side of the hole to ensure free movement of the vane. Clean the outside 
of the pipe to remove dirt, metal chips, and cutting lubricant.