background image

D900-37-00 

I56-2257-005R 

 

 

© 2005 System Sensor

The horn and/or strobe will not work without power.

 The horn/strobe 

gets its power from the fire/security panel monitoring the alarm system. 
If  power  is  cut  off  for  any  reason,  the  horn/strobe  will  not  provide  the 
desired audio or visual warning.

The  horn  may  not  be  heard.

  The  loudness  of  the  horn  meets  (or  ex-

ceeds)  current  Underwriters  Laboratories’  standards.  However,  the  horn 
may not alert a sound sleeper or one who has recently used drugs or has 
been  drinking  alcoholic  beverages.  The  horn  may  not  be  heard  if  it  is 
placed on a different floor from the person in hazard or if placed too far 
away to be heard over the ambient noise such as traffic, air conditioners, 
machinery or music appliances that may prevent alert persons from hear-
ing the alarm. The horn may not be heard by persons who are hearing 
impaired.

NOTE:

 Strobes must be powered continuously for horn operation.

The signal strobe may not be seen.

 The electronic visual warning signal 

uses an extremely reliable xenon flash tube. It flashes at least once every 
second. The strobe must not be installed in direct sunlight or areas of high 
light intensity (over 60 foot candles) where the visual flash might be disre-
garded or not seen. The strobe may not be seen by the visually impaired.

The  signal  strobe  may  cause  seizures.

  Individuals  who  have  positive 

photoic response to visual stimuli with seizures, such as persons with epi-
lepsy, should avoid prolonged exposure to environments in which strobe 
signals, including this strobe, are activated.

The  signal  strobe  cannot  operate  from  coded  power  supplies.  Coded

 

power supplies produce interrupted power. The strobe must have an un-
interrupted source of power in order to operate correctly. System Sensor 
recommends that the horn and signal strobe always be used in combina-
tion so that the risks from any of the above limitations are minimized.

WARNING

The Limitations of Horn/Strobes

Three-Year Limited Warranty

System  Sensor  warrants  its  enclosed  horn.  strobe,  or  horn/strobe  to  be  free  from 

defects  in  materials  and  workmanship  under  normal  use  and  service  for  a  period 

of  three  years  from  date  of  manufacture.  System  Sensor  makes  no  other  express 

warranty for this horn, strobe, or horn/strobe. No agent, representative, dealer, or 

employee of the Company has the authority to increase or alter the obligations or 

limitations  of  this  Warranty.  The  Company’s  obligation  of  this  Warranty  shall  be 

limited to the repair or replacement of any part of the horn, strobe, or horn/strobe 

which is found to be defective in materials or workmanship under normal use and 

service during the three year period commencing with the date of manufacture. After 

phoning  System  Sensor’s  toll  free  number  800-SENSOR2  (736-7672)  for  a  Return 

Authorization  number,  send  defective  units  postage  prepaid  to:  System  Sensor, 

Returns  Department,  RA  #__________,  3825  Ohio  Avenue,  St.  Charles,  IL  60174. 

Please include a note describing the malfunction and suspected cause of failure. The 

Company shall not be obligated to repair or replace units which are found to be de-

fective because of damage, unreasonable use, modifications, or alterations occurring 

after the date of manufacture. In no case shall the Company be liable for any conse-

quential or incidental damages for breach of this or any other Warranty, expressed 

or implied whatsoever, even if the loss or damage is caused by the Company’s neg-

ligence or fault. Some states do not allow the exclusion or limitation of incidental or 

consequential damages, so the above limitation or exclusion may not apply to you. 

This  Warranty  gives  you  specific  legal  rights,  and  you  may  also  have  other  rights 

which vary from state to state.

FCC Statement

SpectrAlert Strobes and Horn/Strobes have  been  tested  and  found  to  comply  with 

the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These 

limits  are  designed  to  provide  reasonable  protection  against  harmful  interference 

when  the  equipment  is  operated  in  a  commercial  environment.  This  equipment 

generates,  uses,  and  can  radiate  radio  frequency  energy  and,  if  not  installed  and 

used  in  accordance  with  the  instruction  manual,  may  cause  harmful  interference 

to radio communications. Operation of this equipment in a residential area is likely 

to cause harmful interference in which case the user will be required to correct the 

interference at his own expense.

Please refer to insert for the Limitations of Fire Alarm Systems

7""

'ASKET

0LATE

X

q

&LAT(EAD

3CREWTOTAL 

0APER,INER
&OR0LATE
'ASKET

#ONDUIT
%NTRANCE

3LOT

,OCKING2IB

Typical outdoor mounting with universal plate:

1.  Mount WBB in desired location.
2.  For SpectrAlert models, mount plate to back box using 4 #8-

32  

1

/

2

˝ screws.

3.  Complete field wiring.
4.  Remove  paper  liner  on  gasket  - 

NOTE:  Perform  electrical 

tests  first,  then  remove  liner.  Paper  liner  must  be  re-
moved from gasket before final installation.

5.  Insert locking rib into slot on plate.
6.  Press  into  plate,  the  SpectrAlert  model  will  make  a  “click” 

when it has locked into place.

NOTE:

  The  outdoor  notification  appliance  must  be  used  with  a 

WBB back box when installed in applications requiring the appli-
ance to be outdoor-listed. In such applications, using a back box 
other than the WBB will void the UL designation.

A0120-00

Figure 8: Removal of horns and strobes from 
mounting plates:

To  remove  units  from  mounting  plates,  insert  Quick  Click  Re-
moval Tool as shown to unlock snap. While pushing in Removal 
Tool to release the snap, pull back on the horn/strobe. Hinge the 
horn/strobe module, disengage the Locking Rib, and lift the horn/
strobe away from the mounting plate.

PLASTIC SNAP LEVER

TAB SLOT

TAB

INSERT REMOVAL TOOL

A0115-00

firealarmresources.com