background image

D900-38-00 

I56-2477-002R

Mounting

Reversible strobe module

Should  the  back  box  be  located  near  an  obstruction  such  as  a 
doorway, the strobe module is field-reversible (Fig. 1).

Figure 4: Surface mount back box – 4

Figure 3: Mounting to irregular surfaces

LOCKING RIB SLOT

DRYWALL SCREWS
(OPTIONAL)

A0168-00

4-INCH BACK BOX

MUD RING

8-32 SCREW

6-32 SCREW

6-32 SCREW

8-32 SCREW

BBS-CHS

A0169-00

Flush mount back box

The chime/strobe can be flush mounted on a 4

″×

4

″×

1

1

2

 back box 

(Fig. 2) as follows:
A. For the 4

″×

4

, mount the mud plate (provided) using the 8-32 

pan  head  screws.  Make  sure  the  mud  ring  is  mounted  verti-
cally, as shown.

B.  Mount the chime/strobe using the 6-32 oval head screws. The 

chime/strobe  shall  be  mounted  on  the  left  side  of  the  mud 
ring. The 6-32 screws shall be inserted into the holes on the 
mud ring that are opposite that of the strobes; i.e., when the 
strobe is on the right, screws into the left side of the mud ring, 
and vice versa. See Figure 1.

NOTE: 

 Two drywall screws (provided) may be used to fasten the 

mounting  plate  to  the  wall.  To  use  the  drywall  screws, 
it will be necessary to first unsnap and hinge the strobe 
module away from the mounting plate. (Fig. 3)

Surface mount back box

The chime/strobe can be surface mounted on a 4

″×

4

″×

1

1

2

 back 

box (Fig. 4) as follows:
A. Mount  the  BBS-CHS  and  the  mud  ring  (provided)  using  the 

8-32 pan head screws. Make sure that the large opening in the 
BBS-CHS lines up with the horn and the mud plate is mounted 
vertically, as shown.

B.  Mount the chime/strobe using the 6-32 oval head screws. The 

chime/strobe  shall  be  mounted  on  the  left  side  of  the  mud 
ring. The 6-32 screws shall be inserted into the holes on the 
mud ring that are opposite that of the strobes; i.e., when the 
strobe is on the right, screws into the left side of the mud ring, 
and vice versa. See Figure 1.

To  reverse  the  strobe  module:  insert  screwdriver,  as  shown  in 
Fig.  3,  to  unlock  snap.  While  pushing  in  the  screwdriver,  pull 
back on the strobe module. Hinge the strobe module, disengage 
the  Locking  Rib  and  lift  the  module  away  from  the  mounting 
plate. Turn the module so that it is upside down from its original 
position,  re-insert  the  module  into  the  mounting  plate  (be  sure 
to  insert  the  Locking  Rib  into  the  slot),  and  press  the  module 
into the mounting plate. The strobe module will make a “click” 
when it has locked into place. Turn the entire assembly so that 
the lens/reflector is on the bottom, as shown. The unit can now 
be mounted.

INSERT
SCREWDRIVER
TO REMOVE

LOCKING RIB

When strobe is on the
right, mount chime/strobe
with 6-32 screws inserted
into the holes on the left
of the mud ring.

LEFT

RIGHT

When strobe is on the
left, mount chime/strobe
with 6-32 screws inserted
into the holes on the right
of the mud ring.

LEFT

RIGHT

A0166-00

Viewing Window

Figure 5: Candela Selections
For strobe candela selection, adjust slide switch 
located on the rear of the product while watching 
the viewing window on the side of the reflector.

A0133-00

Figure 1: Reversible strobe module

4-INCH BACK BOX

MUD RING

8-32 SCREW

6-32 SCREW

A0167-00

Figure 2: Flush mount back box – 4

Содержание SpectrAlert CH24MC Series

Страница 1: ...s are established at Underwriters Laboratories in their reverberant room Always use the sound output specified as UL Reverberant Room when comparing products Listings UL S4011 Private Mode Chime Strobe UL S5512 Strobe Specifications Strobe Voltage Regulated 24 DC FWR Operational Voltage Range 16 33 Volts Synchronous Applications with MDL Module 17 33 Volts Flash Rate 1 flash per second Selectable ...

Страница 2: ... limits Chime Selection Chimes are factory set for high volume 1 0K repeating 1 second chime Tones may be selected by making the appropriate settings on the DIP Switch located on the printed circuit board The set tings required for the available tone options are as follows Table 1 SpectrAlert Chime Switch Settings Switch 1 on 0 off 1 2 3 4 Hz Type 1 1 1 1 1 2k Repeating 1 Second Chime 1 0 1 1 1 0k...

Страница 3: ...d plate is mounted vertically as shown B Mount the chime strobe using the 6 32 oval head screws The chime strobe shall be mounted on the left side of the mud ring The 6 32 screws shall be inserted into the holes on the mud ring that are opposite that of the strobes i e when the strobe is on the right screws into the left side of the mud ring and vice versa See Figure 1 To reverse the strobe module...

Страница 4: ... power supply The chime will not work without power The chime gets its power from the fire security panel monitoring the alarm system If power is cut off for any reason the chime will not provide the desired audio or visual warning The chime may not be heard The loudness of the chime meets or exceeds current installation standards for private mode operation However the chime may not alert a sound ...

Отзывы: