TabLe 4. 2-Wire Horn/STrobe CurrenT draW ( ) For p2 and pC2 STandard CandeLa SerieS:
DC Input
8–17.5 Volts
16–33 Volts
15 cd
15/75 cd
15 cd
15/75 cd
30 cd
75 cd
95 cd
110 cd
115 cd
Temporal High
137
147
79
90
107
176
194
212
218
Temporal Medium
132
144
69
80
97
157
182
201
210
Temporal Low
132
143
66
77
93
154
179
198
207
Non-temporal High
141
152
91
100
116
176
201
221
229
Non-temporal Medium
133
145
75
85
102
163
187
207
216
Non-temporal Low
131
144
68
79
96
156
182
201
210
FWR Input
Temporal High
136
155
88
97
112
168
190
210
218
Temporal Medium
129
152
78
88
103
160
184
202
206
Temporal Low
129
151
76
86
101
160
184
194
201
Non-temporal High
142
161
103
112
126
181
203
221
229
Non-temporal Medium
134
155
85
95
110
166
189
208
216
Non-temporal Low
132
154
80
90
105
161
184
202
211
TabLe 5. 2-Wire Horn/STrobe CurrenT draW ( ) For p2 and pC2 HigH CandeLa range SerieS:
Sound Pattern
16–33 Volts Volts DC
16–33 Volts Volts FWR
135 cd
150 cd
177 cd
185 cd
135 cd
150 cd
177 cd
185 cd
Temporal High
245
259
290
297
215
231
258
265
Temporal Medium
235
253
288
297
209
224
250
258
Temporal Low
232
251
282
292
207
221
248
256
Non-temporal High
255
270
303
309
233
248
275
281
Non-temporal Medium
242
259
293
299
219
232
262
267
Non-temporal Low
238
254
291
295
214
229
256
262
TabLe 6. Horn ouTpuT ( ba) in uL reverberanT room:
Switch
Position
Sound Pattern
dA
8–17.5 Volts**
16–33 Volts**
24 V Nominal Measurements
Reverberant
Anechoic
DC
FWR
DC
FWR
DC
FWR
DC
FWR
1
Temporal
High
78
78
84
84
88
88
99
98
2
Temporal
Medium
75
75
80
80
86
85
96
96
3
Temporal
Low
71
71
76
76
81
79
94
89
4
Non-temporal
High
82
82
88
88
93
92
100
100
5
Non-temporal
Medium
78
78
85
85
90
89
98
98
6
Non-temporal
Low
75
75
81
81
86
84
96
92
7*
Coded
High
82
82
88
88
93
92
101
101
8*
Coded
Medium
78
78
85
85
90
89
97
98
9*
Coded
Low
74
75
81
81
85
83
96
92
*Horn & 4-wire Horn/Strobe only. ** Minimum dB rating for Operational Voltage Range as per UL 464.
k SerieS mounTing
1. K Series products may be used indoors or outdoors. They must be in-
stalled using the proper SpectrAlert Advance weatherproof back box (SA-
WBB, SA-WBBW, SA-WBBC or SA-WBBCW). Do not attempt to use boxes
other than the ones supplied with the product.
2. The wall mount box (SA-WBB or SA-WBBW) must be mounted with its
internal post in the lower left corner, as shown in
Figure 8
.
3. Threaded holes are provided in the sides of the box for ¾-inch conduit
adapters. Knockout plugs in the back of the box can be used for ¾-inch
rear entry. Unused holes must be sealed. Plugs and O-Rings are provided
with the box for this purpose.
4. It is the responsibility of the installer to make sure that all openings and
connections are sealed properly. Outdoor installations that are protected
from direct exposure to rain are still subject to condensation or leakage
through hidden areas, such as a soffit.
5. Water may pool on the back box due to condensation or direct exposure
to rain or snow. Use watertight fittings for all wiring connections, includ-
ing the knockout plugs on the back of the box. When using plastic plugs
to fill unused threaded holes, apply teflon tape and/or silicone sealant to
reduce the chance of leakage.
6. Attach the mounting plate to the weatherproof back box using the four
unpainted screws.
7. Follow steps 2 – 6 of the indoor mounting instructions to wire and attach
the product.
mounTing indoor WaLL or CeiLing produCTS
1. Attach mounting plate to junction box as shown in
Figures 4
and
5
. The
mounting plate is compatible with 4-inch square, double gang, and 4-inch
octagon junction boxes (2-wire products may be used with a single gang
box). If using a back box skirt, attach the mounting plate to the skirt and
then attach the entire assembly to the junction box (see
Figures 6
and
7
).
2. Connect field wiring to terminals, as shown in
Figures 1
and
2
.
3. If the product is not to be installed at this point, use the paint cover to
prevent contamination of the mounting plate. (For indoor models only)
4. To attach product to mounting plate, remove the paint cover, then hook
tabs on the product housing into the grooves on mounting plate.
5. Then, swing product into position to engage the pins on the product with
the terminals on the mounting plate. Make sure that the tabs on the back
of the product housing fully engage with the mounting plate.
6. Secure product by tightening the single mounting screw in the front
of the product housing. For tamper resistance, the standard captivated
mounting screw may be replaced with the enclosed Torx screw.
ma
d
ma
D690-03-00
3