TabLe 4. 2-Wire Horn/STrobe CurrenT draW (     ) For p2 and pC2 STandard CandeLa SerieS:

DC Input

8–17.5 Volts

16–33 Volts

15 cd

15/75 cd

15 cd

15/75 cd

30 cd

75 cd

95 cd

110 cd

115 cd

Temporal High

137

147

79

90

107

176

194

212

218

Temporal Medium

132

144

69

80

97

157

182

201

210

Temporal Low

132

143

66

77

93

154

179

198

207

Non-temporal High

141

152

91

100

116

176

201

221

229

Non-temporal Medium

133

145

75

85

102

163

187

207

216

Non-temporal Low

131

144

68

79

96

156

182

201

210

FWR Input
Temporal High

136

155

88

97

112

168

190

210

218

Temporal Medium

129

152

78

88

103

160

184

202

206

Temporal Low

129

151

76

86

101

160

184

194

201

Non-temporal High

142

161

103

112

126

181

203

221

229

Non-temporal Medium

134

155

85

95

110

166

189

208

216

Non-temporal Low

132

154

80

90

105

161

184

202

211

TabLe 5. 2-Wire Horn/STrobe CurrenT draW (     ) For p2 and pC2 HigH CandeLa range SerieS:

Sound Pattern

16–33 Volts Volts DC

16–33 Volts Volts FWR

135 cd

150 cd

177 cd

185 cd

135 cd

150 cd

177 cd

185 cd

Temporal High

245

259

290

297

215

231

258

265

Temporal Medium

235

253

288

297

209

224

250

258

Temporal Low

232

251

282

292

207

221

248

256

Non-temporal High

255

270

303

309

233

248

275

281

Non-temporal Medium

242

259

293

299

219

232

262

267

Non-temporal Low

238

254

291

295

214

229

256

262

TabLe 6. Horn ouTpuT (  ba) in uL reverberanT room:

Switch 
Position

Sound Pattern

dA

8–17.5 Volts**

16–33 Volts**

24 V Nominal Measurements

Reverberant

Anechoic

DC

FWR

DC

FWR

DC

FWR

DC

FWR

1

Temporal

High

78

78

84

84

88

88

99

98

2

Temporal

Medium

75

75

80

80

86

85

96

96

3

Temporal

Low

71

71

76

76

81

79

94

89

4

Non-temporal

High

82

82

88

88

93

92

100

100

5

Non-temporal

Medium

78

78

85

85

90

89

98

98

6

Non-temporal

Low

75

75

81

81

86

84

96

92

7*

Coded

High

82

82

88

88

93

92

101

101

8*

Coded

Medium

78

78

85

85

90

89

97

98

9*

Coded

Low

74

75

81

81

85

83

96

92

*Horn & 4-wire Horn/Strobe only. ** Minimum dB rating for Operational Voltage Range as per UL 464.

k SerieS mounTing

1.   K Series products may be used indoors or outdoors. They must be in-

stalled using the proper SpectrAlert Advance weatherproof back box (SA-
WBB, SA-WBBW, SA-WBBC or SA-WBBCW). Do not attempt to use boxes 
other than the ones supplied with the product.

2.   The wall mount box (SA-WBB or SA-WBBW) must be mounted with its 

internal post in the lower left corner, as shown in 

Figure 8

.

3.   Threaded holes are provided in the sides of the box for ¾-inch conduit 

adapters. Knockout plugs in the back of the box can be used for ¾-inch 
rear entry. Unused holes must be sealed. Plugs and O-Rings are provided 
with the box for this purpose.

4.   It is the responsibility of the installer to make sure that all openings and 

connections are sealed properly. Outdoor installations that are protected 
from direct exposure to rain are still subject to condensation or leakage 
through hidden areas, such as a soffit.

5.   Water may pool on the back box due to condensation or direct exposure 

to rain or snow. Use watertight fittings for all wiring connections, includ-
ing the knockout plugs on the back of the box. When using plastic plugs 
to fill unused threaded holes, apply teflon tape and/or silicone sealant to 
reduce the chance of leakage. 

6.   Attach the mounting plate to the weatherproof back box using the four 

unpainted screws. 

7.   Follow steps 2 – 6 of the indoor mounting instructions to wire and attach 

the product.

mounTing indoor WaLL or CeiLing produCTS

1.   Attach mounting plate to junction box as shown in 

Figures 4

 and 

5

. The 

mounting plate is compatible with 4-inch square, double gang, and 4-inch 
octagon junction boxes (2-wire products may be used with a single gang 
box). If using a back box skirt, attach the mounting plate to the skirt and 
then attach the entire assembly to the junction box (see 

Figures 6

 and 

7

).

2.  Connect field wiring to terminals, as shown in 

Figures 1

 and 

2

.

3.   If the product is not to be installed at this point, use the paint cover to 

prevent contamination of the mounting plate. (For indoor models only)

4.   To attach product to mounting plate, remove the paint cover, then hook 

tabs on the product housing into the grooves on mounting plate.

5.   Then, swing product into position to engage the pins on the product with 

the terminals on the mounting plate. Make sure that the tabs on the back 
of the product housing fully engage with the mounting plate.

6.   Secure  product  by  tightening  the  single  mounting  screw  in  the  front 

of the product housing. For tamper resistance, the standard captivated 
mounting screw may be replaced with the enclosed Torx screw. 

ma

d

ma  

D690-03-00 

I56-2769-015R

Содержание SpectrAlert Advance Series

Страница 1: ...pplications indoors and outdoors They are designed to be used in 12 or 24 volt DC or FWR full wave rectified systems These products are electrically backward compat ible with the previous generation of SpectrAlert notification appliances Horn strobe products are available in two versions The 2 wire products fit systems where a single NAC controls both horn and strobe The 4 wire products are in ten...

Страница 2: ...for the specific candela selection in Table 1 with the current draw for the specific horn selec tion in Table 3 Table 1 Strobe Current Draw for S SC P4 PC4 Series Candela 8 17 5 Volts 16 33 Volts DC FWR DC FWR Standard Candela Range 15 123 128 66 71 15 75 142 148 77 81 30 NA NA 94 96 75 NA NA 158 153 95 NA NA 181 176 110 NA NA 202 195 115 NA NA 210 205 High Candela Range 135 NA NA 228 207 150 NA N...

Страница 3: ...n the ones supplied with the product 2 The wall mount box SA WBB or SA WBBW must be mounted with its internal post in the lower left corner as shown in Figure 8 3 Threaded holes are provided in the sides of the box for inch conduit adapters Knockout plugs in the back of the box can be used for inch rear entry Unused holes must be sealed Plugs and O Rings are provided with the box for this purpose ...

Страница 4: ... limited to the replacement of any part of the product which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture After phoning System Sensor s toll free number 800 SENSOR2 736 7672 for a Return Authorization number send defective units postage prepaid to System Sensor Returns Department RA __________...

Отзывы: