background image

D690-04-00 

I56-2783-003R

TabLe 1. CUrrenT draW (ma)

dC inpUT

8–17.5 VoLTS

16–33 VoLTS

15

15/75

15

15/75

30

75

95

110

115

1 Second Chime High

131

142

65

76

94

160

185

207

213

1 Second Chime Low

131

142

64

75

92

157

183

203

212

1/4 Second Chime High

129

142

66

75

95

159

184

205

212

1/4 Second Chime Low

129

142

64

74

91

155

181

204

211

Temporal Chime High

125

142

64

74

91

156

181

205

211

Temporal Chime Low

129

141

65

75

92

155

180

200

209

5 Second Whoop High

133

145

70

81

99

165

189

210

217

5 Second Whoop Low

130

143

66

77

95

160

186

206

214

One Time Chime

127

141

64

76

93

156

182

203

210

FWr inpUT

8–17.5 VoLTS

16–33 VoLTS

15

15/75

15

15/75

30

75

95

110

115

1 Second Chime High

128

150

72

82

98

158

183

202

210

1 Second Chime Low

127

150

71

81

97

157

182

202

210

1/4 Second Chime High

129

149

72

82

99

160

183

203

211

1/4 Second Chime Low

128

149

71

81

97

154

179

196

205

Temporal Chime High

128

148

71

81

97

157

179

199

206

Temporal Chime Low

125

147

71

81

97

156

180

200

206

5 Second Whoop High

136

152

84

93

110

170

193

212

220

5 Second Whoop Low

132

150

77

86

102

161

184

203

214

One Time Chime

127

147

72

82

97

157

181

200

210

TabLe 2. horizonTaL pLane LiGhT diSTribUTion 
For WaLL and CeiLinG appLiCaTionS

horizonTaL 

anGLe

% oF raTed LiGhT oUTpUT

0

100

45

75

90

25

TabLe 3. VerTiCaL pLane LiGhT diSTribUTion  
For WaLL appLiCaTionS

horizonTaL anGLe

% oF raTed LiGhT oUTpUT

0

100

45

34

90

12

Содержание SpectrAlert Advance CHSR

Страница 1: ...ls typically supply DC filtered voltage or FWR full wave rectified volt age The system design engineer must calculate the number of units used on a loop based on the type of panel supply Be certain the sum of all the device currents does not exceed the current capability of the panel Calculations are based on using the device current found in the subsequent charts and must be compatible with the c...

Страница 2: ... Input 8 17 5 Volts 16 33 Volts 15 15 75 15 15 75 30 75 95 110 115 1 Second Chime High 128 150 72 82 98 158 183 202 210 1 Second Chime Low 127 150 71 81 97 157 182 202 210 1 4 Second Chime High 129 149 72 82 99 160 183 203 211 1 4 Second Chime Low 128 149 71 81 97 154 179 196 205 Temporal Chime High 128 148 71 81 97 157 179 199 206 Temporal Chime Low 125 147 71 81 97 156 180 200 206 5 Second Whoop...

Страница 3: ...ination of the wiring terminals of the mounting plate 4 To attach product to mounting plate hook tabs on the product housing into the grooves on mounting plate Then swing product into position to engage the pins on the product with the terminals on the mounting plate Make sure that the tabs on the back of the product housing fully engage with the mounting plate 5 Secure product by tightening the s...

Страница 4: ...from date of manufacture System Sensor makes no other express warranty for this product No agent representative dealer or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty The Company s obligation of this Warranty shall be limited to the replacement of any part of the product which is found to be defec tive in materials or workmanship un...

Отзывы: