background image

D900-06-00

1

I56-750-57

SS24ADAS Series Strobes and

MASS24ADAS Series Synchronized

Horn/Strobes for Fire Protective

Signaling Systems

INSTALLATION AND MAINTENANCE INSTRUCTIONS

A Division of Pittway

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

General Description

The National Fire Protection Association has published
standards and recommended practices for the installation
and use of the listed appliances. It is recommended that the
installer be familiar with these requirements, with local
codes, and any special requirements of the local fire au-
thority having jurisdiction.

The Multi-Alert sounder and signaling strobe are intended
to be connected to the alarm indicating circuit of a UL-
listed fire alarm control panel  and  is compatible with DC
line supervision. The electronic sounder can be connected
to either 12 or 24 VDC panels. Models SS2415ADAS,
SS241575ADAS, and combination models incorporating
these strobes, require 24 volt panels.  Panels may have full-
wave rectified, unfiltered power supplies. The strobes are
synchronized and flash at a rate of one flash per second
with continuous voltage applied. SS24ADAS, SS24ADA,
MASS24ADAS, and MASS24ADA series devices may be
combined in the same zone.

Model

Supply

Operating Current from

Operating Current from Full-Wave

Voltage

Regulated Supply

Rectified Unfiltered Supply

Range

SS2415ADAS

20-30V

106

200

5.0/7.0

125

250

5.0/7.0

SS241575ADAS

20-30V

195

350

5.0/7.0

180

395

5.0/7.0

Average

Peak

Inrush

Average

Peak

Inrush

Operating Current

Current

Operating

Current

Current

Current

(mA)

(Amps)

Current

(mA)

(Amps)

(mA)

20/30

(mArms)

20/30

Vrms

Vrms

NOTE:

In-rush current du-
ration is less than 20
m i c r o s e c o n d s
(.00002 seconds).

Table 2. Sound output and current ratings for the MA12/24D:

Sound (Hz)

Clips on

Current (mA)

Output (dBA)

UL (dBA)

Tabs

DC Regulated/

(Note 3)

Ratings

(Note 1)

FWR Unfiltered

(Note 4)

12V

24V

30V

12V

24V

12V

24V

Slow Whoop

ABC

21/40

38/56

46/72

85

92

79

85

800 Continuous

BC

15/24

28/45

35/55

87

93

79

85

800/1000 Alternating

AC

17/32

34/46

43/58

85

92

79

85

2400 Interrupted

AB

19/23

35/56

43/64

89

90

79

85

2400 Continuous

C

21/31

38/59

46/73

85

94

79

85

1200 Interrupted

B

13/19

23/33

27/41

85

91

75

82

Swept Frequency

A

17/24

34/47

43/60

85

92

79

85

Fast Warble

NONE

15/27

30/47

38/59

85

92

79

85

Table 1. SS24ADAS Series Electrical Ratings:

Note 1:

See  Figure 2 for tab clip removal & storage.

Note 2:

All models can be powered using full wave rectified unfiltered
supplies. Under no circumstances can  SS24ADAS or
MASS24ADAS series devices input voltage exceed 33 VDC or be

less than 16 VDC (18-33Vrms for full-wave rectified, unfiltered
supplies).

Note 3:

Measured at 10 feet in an anechoic chamber.

Note 4:

Measured in a UL reverberant room.

The MA12/24D sounder is suitable for outdoor applica-
tions (-35

°

 to 66

°

 C) when it is used with a WBB Weather-

proof Back Box. The signaling strobe is rated for 0

°

 to 49

°

C and is NOT suitable for outdoor use.

The UL-rated light output of the SS2415ADAS,
SS241575ADAS, MASS2415ADAS, and MASS241575ADAS
is 15 cd  (See Figure 1).

NOTE:

The light output at 0

°

 viewing angle for

SS241575ADAS and MASS241575ADAS is 75 cd.

Any one of eight sounds can be selected on the electronic
sounder, as indicated in Table 2.

NOTE:

SS24ADAS, MASS24ADAS AND MAEH24ADAS
SERIES DEVICES OPERATING IN THE SAME
ZONE WILL NOT BE SYNCHRONIZED IF ENER-
GIZED AT DIFFERENT TIMES (I.E., IF MORE
THAN ONE CONTROLLER IS CONTROLLING THE
SAME ZONE.)

Technical Manuals Online! - http://www.tech-man.com

Содержание MASS12/24ADA Series

Страница 1: ...plies Under no circumstances can the MA12 24D input Table 1 SS12 24ADA Series electrical ratings Model Supply Voltage Range Operating Current from Regulated Supply Operating Current from Full Wave Rectified Unfiltered Supply Average Operating Current Peak Current mA 20 30V Peak Current mA 10 5V 17V Inrush Current mA in access of Peak Average Operating Current mArms Peak Current mA 20Vrms 30Vrms Pe...

Страница 2: ...ast once every three seconds meets or exceeds current Un derwriters Laboratories standard 1971 and uses an extremely reliable xe non flash tube The visual warning signal is suitable for direct viewing and must be installed within an area where it can be seen by building occu pants The strobe must not be installed in direct sunlight or areas of high light intensity over 60 foot candles where the vi...

Страница 3: ...ELECT DESIRED TONE COVER SLOT TAB A TAB B TAB C FOR STORING UNUSED CLIPS SLIDE COVER BACK TO ALIGN COVER SLOT WITH CLIP STORAGE POST SLIDE COVER FOR CLIP STORAGE USE A SMALL BLADED SCREWDRIVER TO REMOVE CLIPS TONE SELECTION TABS Figure 2 Figure 3 Multi alert sounder Figure 4 Strobe Figure 5 Multi alert sounder and strobe operating in tandem From panel or previous device To Next Device or EOL VDC V...

Страница 4: ...te to box with screw A 1 Screw sounder to plate 2 Complete field wiring 3 Screw plate sounder to box with screw F 1 Plaster ring should be properly mounted to electrical box with screws supplied with box 2 Screw plate to plaster ring with screw G 3 Complete field wiring 4 Screw sounder strobe to plate with screw A 5 Fill remaining holes with screw B B A A B Signal Strobe Standard Backbox TOP MA 12...

Страница 5: ...ied unfiltered supply Installation For Strobe Replacement See NFPA 72 Chapter 6 All wiring must be installed in compliance with the Na tional Electrical Code and all applicable local codes as well as any special requirements of the authority having juris diction using the proper wire size This also includes all applicable NFPA Standards ANSI UL 1480 and NEC 760 Figure 1 Electrical connections Spec...

Страница 6: ...ltage input power level combina tion being used NEVER connect the yellow jumper to the posts numbered 1 through 6 or the blue jumper to lettered posts A or B Mechanical Slotted head screws are included for attaching the speaker to the electrical junction box Insert the decorative filler plugs supplied into the remaining two holes in the grille Mounting See Figure 2 The speaker can be flush mounted...

Страница 7: ...0 1 0 Note Inrush current lasts on the order of microseconds Table 3 SP100W24MC LO 1 5 cd UL 1638 Strobe M 15 cd UL 1638 Strobe 24 24 VDC Strobe SP100W Round Grille White Speaker SP101W Square Grille White Speaker SP101R Square Grille Red Speaker C Ceiling mount SP1R2415ADA 15 15 cd UL 1971 Strobe 1575 15 cd UL 1971 Strobe 75 75 cd UL 1971 Strobe 110 110 cd UL 1971 Strobe 24 24 VDC Strobe SP1R Squ...

Страница 8: ...d System Sensor recommends that the speaker and signal strobe always be used in combination so that the risks from any of the above limitations are minimized WARNING The Limitations of Speaker Strobes Three Year Limited Warranty System Sensor warrants its enclosed speaker strobe to be free from defects in materials and workmanship under normal use and service for a period of three years from date ...

Страница 9: ...ing model MP SF or MP SFB Model Supply Voltage Range Operating Current from Regulated Supply Operating Current from Full Wave Rectified Unfiltered Supply Average Operating Current Average Operating Current mArms Peak Current mA 20Vrms 30Vrms Peak Current mA 20 30V Inrush Current mA in access of Peak Inrush Current Amps in excess of Peak V4R24110ADA V4R2475ADA V4R2415ADA V4R241575ADA 20 30V 210 470...

Страница 10: ...vice to the control panel must be broken at the device terminal con nection to ensure electrical supervision Figure 1 Vertical and horizontal light distribution Degrees of Rating 0 100 5 25 90 30 45 75 50 55 55 45 60 40 65 35 70 35 75 30 80 30 85 25 90 25 LIGHT 0 45 45 90 90 2 See Figure 2 The speaker is equipped with five posts and an associated plug with red and black wires The center post is CO...

Страница 11: ...holes in the speaker strobe D Plaster Ring Mount See Figure 5 Follow the Semiflush Wall Mount proce dure except attach the semiflush plate to the electrical box using the two 6 32 X 5 8 screws 6 32x5 8 V400 8 32x1 7 16 8 Sht Mtl Signal Strobe 8 32x1 7 16 8 Sht Mtl 6 32x5 8 8 32x5 8 Figure 5 Plaster ring mount A78 1799 01 8 32x1 7 16 8 Sht Mtl 8 Sht Mtl 8 32x1 7 16 Signal Strobe V400 Figure 3 Surfa...

Страница 12: ...robe must have an un interrupted source of DC power in order to operate correctly System Sensor recommends that the speaker and signal strobe always be used in combination so that the risks from any of the above limitations are minimized WARNING The Limitations of Speakers and Speaker Strobes Three Year Limited Warranty System Sensor warrants its enclosed speaker strobe to be free from defects in ...

Страница 13: ...ibution LIGHT 0 45 45 90 90 Vertical Dispersion Horizontal Dispersion Model Supply Voltage Range Operating Current from Regulated Supply Operating Current from Full Wave Rectified Unfiltered Supply Average Operating Current Average Operating Current mArms Peak Current mA 20Vrms 30Vrms Peak Current mA 20 30V Inrush Current mA in access of Peak Inrush Current Amps in excess of Peak RK24110ADA RK2475...

Страница 14: ...appliance is greater than 24 below the ceiling 177 cd if the bottom of the appliance is less than 24 below the ceiling Nonsleeping Bottom of the strobe not less than 80 above the floor and not more than 96 above the floor A Horn Preparation Existing Multi Alert Installations Only 1 Remove the unit from its current mounting 2 Remove the existing strobe if it is present Discon nect the interconnecti...

Страница 15: ...kbox From panel or previous device To Next Device or EOL VDC VDC Note Use uncoded supply only INOUT STROBE ONLY INOUT INOUT STROBE ONLY INOUT From panel or previous device To Next Device or EOL VDC VDC VDC VDC STROBE SOUNDER INOUT STROBE ONLY INOUT INOUT STROBE ONLY INOUT Non Coded Supply Can Be Coded Supply Caution Break off P C B Tabs Screw Types Used In Figures 4 Through 7 A 8 32 x 1 7 16 Slot ...

Страница 16: ...or areas of high light intensity over 60 foot candles where the visual flash might be disre garded or not seen The strobe may not be seen by the visually im paired The signal strobe may cause seizures Individuals who have a positive photic response to visual stimuli with seizures such as epileptics should avoid prolonged exposure to environments in which strobe signals in cluding this strobe are a...

Страница 17: ...Current from Full Wave Rectified Unfiltered Supply Average Operating Current Horn Strobe Peak Current mA 20 30V Peak Current mA 10 5V 17V Inrush Current mA in access of Peak Average Operating Current mArms Horn Strobe Peak Current mA 20Vrms 30Vrms Peak Current mA 10 5Vrms 17Vrms Inrush Current Amps in excess of Peak PS24110ADA PS24110ADAW 20 30V 225 470 500 0 260 400 500 0 08 PS2475ADA PS2475ADAW ...

Страница 18: ...for full wave rectified unfiltered supplies Installation A General Phillips head screws are used to attach PS12 24ADA to semi flush plate or the electrical outlet box Slotted head screws are used to attach semi flush plate to outlet box See Figures 3 and 4 for wiring methods NOTE Do not loop wires under the terminal screw Wires connecting the device to the panel must be broken at the device termin...

Страница 19: ... A78 2603 00 Figure 7 Semi flush mount to 4 box 1 Screw Semi Flush Plate to 4 Box with B Screws 2 Complete Field Wiring See Figure 3 3 Screw PS12 24ADA to Semi Flush Plate with D Screws 1 Complete Field Wiring see Figure 3 2 Screw PS12 24ADA to Outlet Box with A Screws 1 Screw Semi Flush Plate to Box with C Screws 2 Complete Field Wiring See Figure 3 3 Screw PS12 24ADA to Semi Flush Plate with D S...

Страница 20: ...om any of the above limitations are minimized The signal strobe cannot operate from coded power supplies Coded power supplies produce interrupted power The strobe must have an unin terrupted source of DC power in order to operate correctly WARNING The Limitations of Sounder Strobes Three Year Limited Warranty System Sensor warrants its sounder strobe to be free from defects in mate rials and workm...

Страница 21: ...ated Supply Operating Current from Full Wave Rectified Unfiltered Supply Average Operatin Current Peak Current mA 20 30V Peak Current mA 10 5V 17V Inrush Current mA in access of Peak Average Operating Current mArms Peak Current mA 20Vrms 30Vrms Peak Current mA 10 5Vrms 17Vrms Inrush Current Amps in excess of Peak RP24110ADA RP24110ADAW 20 30V 210 470 500 0 245 400 500 0 08 RP2475ADA RP2475ADAW 20 ...

Страница 22: ...Signal Strobe always be used in combination so that the risks from any of the above limitations are minimized The signal strobe cannot operate from coded power supplies Coded power supplies produce interrupted power The strobe must have an unin terrupted source of DC power in order to operate correctly WARNING The Limitations of Sounder Strobes The strobe horn combination is designed for wall moun...

Страница 23: ... Surface mount A78 2601 00 A78 2615 00 B A C C A B 1 Remove Mounting Screws Holding Horn in Place 2 Slide Horn Through Opening in Retrofit Plate 3 Attach Horn to Retrofit Plate Using Screws B and Nuts C 4 Complete Field Wiring See Figures 2 and 3 5 Screw Strobe Horn Combination to Electrical Box Using Screws A 2 340 1 340 1 900 Figure 5 Maximum horn depth allowed Screw Types Used A 8 32 x 3 1 4 Ph...

Страница 24: ...tion Label placement OUT IN OUT IN WIRE STRIP GAGE IN OUT IN OUT Locking Tabs Figure 5 Remove strobe Figure 6 Rotate backplate 180 Figure 8 Final inverted unit OUT OUT IN IN OUT OUT IN IN STRIP GAGE WIRE Figure 7 Snap strobe back into place 4 Snap strobe unit back into place noting the alignment of the text on the back of the strobe unit see Figure 7 5 Place new FIRE label over old print using the...

Страница 25: ...h current du ration is less than 20 m i c r o s e c o n d s 00002 seconds Table 2 Sound output and current ratings for the MA12 24D Sound Hz Clips on Current mA Output dBA UL dBA Tabs DC Regulated Note 3 Ratings Note 1 FWR Unfiltered Note 4 12V 24V 30V 12V 24V 12V 24V Slow Whoop ABC 21 40 38 56 46 72 85 92 79 85 800 Continuous BC 15 24 28 45 35 55 87 93 79 85 800 1000 Alternating AC 17 32 34 46 43...

Страница 26: ...ambient noise at all locations within a room Additional sounders may be needed to ensure sound output level complies with NFPA requirements The Sounder and or Strobe will not work without power The sounder strobe gets its power from the fire security panel monitoring the alarm system If power is cut off for any reason the sounder strobe will not pro vide the desired audio or visual warning The Sou...

Страница 27: ...STORING UNUSED CLIPS SLIDE COVER BACK TO ALIGN COVER SLOT WITH CLIP STORAGE POST SLIDE COVER FOR CLIP STORAGE USE A SMALL BLADED SCREWDRIVER TO REMOVE CLIPS TONE SELECTION TABS Figure 2 Figure 3 Multi alert sounder Figure 4 Multi alert sounder and strobe operating in tandem Figure 5 Strobe From panel or previous device To Next Device or EOL VDC VDC VDC VDC STROBE SOUNDER INOUT STROBE ONLY INOUT IN...

Страница 28: ...137 11 1 Complete field wiring 2 Screw plate sounder to Box with screw F A78 1137 08 C F F C MP F MA 12 24D D D BB D A78 2515 00 A78 2514 00 Figure 9 Strobe surface mount 1 Complete field wiring 2 Screw sounder strobe to box with screw A 3 Fill remaining screw holes with screw B Figure 10 Sounder strobe surface mount MA 12 24D A B B A Signal Strobe Standard Backbox 1 Complete field wiring 2 Screw ...

Страница 29: ...Vrms Vrms NOTE In rush current du ration is less than 20 m i c r o s e c o n d s 00002 seconds Table 2 Sound output and current ratings for the MA12 24EH Sound Hz Clips on Current mA Output dBA UL dBA Tabs DC Regulated Note 3 Ratings Note 1 FWR Unfiltered Note 4 12V 24V 30V 12V 24V 12V 24V Fast Whoop ABC 21 40 38 56 46 72 85 92 79 85 800 Continuous BC 15 24 28 45 35 55 87 93 79 85 800 1000 Alterna...

Страница 30: ...ambient noise at all locations within a room Additional sounders may be needed to ensure sound output level complies with NFPA requirements The Sounder and or Strobe will not work without power The sounder strobe gets its power from the fire security panel monitoring the alarm system If power is cut off for any reason the sounder strobe will not pro vide the desired audio or visual warning The Sou...

Страница 31: ... STORING UNUSED CLIPS SLIDE COVER BACK TO ALIGN COVER SLOT WITH CLIP STORAGE POST SLIDE COVER FOR CLIP STORAGE USE A SMALL BLADED SCREWDRIVER TO REMOVE CLIPS TONE SELECTION TABS Figure 2 Figure 3 Multi alert sounder Figure 4 Multi alert sounder and strobe operating in tandem Figure 5 Strobe From panel or previous device To Next Device or EOL VDC VDC VDC VDC STROBE SOUNDER INOUT STROBE ONLY INOUT I...

Страница 32: ...78 1137 31 1 Complete field wiring 2 Screw plate sounder to box with screw F A78 1137 30 C F F C MP F MA12 24EH D D BB D A78 2515 03 A78 2514 00 Figure 9 Strobe surface mount 1 Complete field wiring 2 Screw sounder strobe to box with screw A 3 Fill remaining screw holes with screw B Figure 10 Sounder strobe surface mount MA12 24EH A B B A Signal Strobe Standard Backbox 1 Complete field wiring 2 Sc...

Страница 33: ...7 volts 24 volt models 20 to 30 volts Flash Rate 1 Flash Per Second Operating Temperature 32 F to 120 F 0 C to 49 C Light Output Models with 15 only in the model number are listed at 15 candela Models with 1575 are listed at 15 candela per UL 1971 but will provide 75 candela on axis straight ahead Models with 75 are listed at 75 candela Models with 110 are listed at 110 candela Sound Output Sound ...

Страница 34: ...p 178 193 152 181 113 164 95 113 91 111 87 120 mech Non 178 193 152 181 113 164 93 110 89 113 88 122 Low Temp NA NA NA NA NA NA 87 104 79 106 75 109 Non NA NA NA NA NA NA 88 104 80 106 75 110 3000 Hz High Temp 179 195 152 183 115 166 100 118 94 116 95 127 Interrupt Non 179 196 152 183 113 168 95 114 93 119 93 130 Low Temp NA NA NA NA NA NA 90 106 83 108 79 113 Non NA NA NA NA NA NA 89 104 82 107 8...

Страница 35: ... and strobe operation Remove factory installed jumpers see Figure 4 System Operation Non Synchronized Devices FROM FACP MODULE OR PREVIOUS DEVICE TO NEXT DEVICE OR EOL HORN STROBE COMBO FACTORY INSTALLED JUMPERS FROM FACP MODULE OR PREVIOUS DEVICE HORNS STROBES TO NEXT STROBE OR EOL HORN AND STROBE TO NEXT HORN OR EOL FACTORY INSTALLED JUMPER WIRES REMOVED NOTE STROBES MUST BE POWERED FOR HORN OPE...

Страница 36: ...t may also mount to a 2 inch box using screws B instead of screws A D MP B Horn with universal mounting plate 1 Slip wires through plate 2 Complete field wiring 3 Mount unit to back box with screws B B Horn direct mount 1 Break off four tabs from unit 2 Complete field wiring 3 Mount unit to back box with screws B Screw types used for mounting A 8 x 1 1 4 plastite B 6 32 x 1 3 8 oval head C 6 32 x ...

Отзывы: